Westermo RedFox 5728 Series

Industrial routing switches

1. General Information

1.1. Legal Information

The contents of this document are provided “as is”. Except as required by applicable law, no warranties of any kind are made in relation to the accuracy and reliability or contents of this document, either expressed or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose. Westermo reserves the right to revise this document or withdraw it at any time without prior notice.

Under no circumstances shall Westermo be responsible for any loss of data or income or any special, incidental, and consequential or indirect damages howsoever caused.

More information about Westermo can be found at www.westermo.com.

1.2. About This Guide

This guide is intended for installation engineers and users of the Westermo products. It includes information on safety and regulations, a product description, installation instructions and technical specifications.

1.3. Software Tools

Related software tools are available at https://www.westermo.com/support/product-support.

1.4. License and Copyright for Included FLOSS

This product includes software developed by third parties, including Free/Libre Open Source Software (FLOSS). The specific license terms and copyright associated with the software are included in each software package respectively. Please visit the product web page for more information.

Upon request, the applicable source code will be provided. A nominal fee may be charged to cover shipping and media. Please direct any source code request to your normal sales or support channel.

1.5. WeOS

This product runs WeOS 5 (Westermo Operating System). Instructions for quick start, configuration and factory reset are found in the WeOS user documentation at www.westermo.com.

2. Safety and Regulations

2.1. Warning Levels

Warning signs are provided to prevent personal injuries and/or damages to the product. The following levels are used:

Level of warning Description Consequence personal injury Consequence material damage
⚠️ Indicates a potentially hazardous situation Possible death or major injury Major damage to the product
⚠️ Indicates a potentially hazardous situation Minor or moderate injury Moderate damage to the product
ℹ️ Provides information in order to avoid misuse of the product, confusion or misunderstanding No personal injury Minor damage to the product
ℹ️ Used for highlighting general, but important information No personal injury Minor damage to the product

2.2. Safety Information

Before installation:

Read this manual completely and gather all information available on the product. Make sure it is fully understood. Check that your application does not exceed the safe operating specifications for the product.

⚠️ SAFETY DURING INSTALLATION

The product must be installed and operated by qualified service personnel and installed into an apparatus cabinet or similar, where access is restricted to service personnel only.

Refer to chapter Compliance Information to see the required level of qualified service personnel according to safety standards.

Before energising and connecting communication cables to the product, ensure a protective earthing conductor is first connected to the protective earthing terminal (only valid for metallic housings). Westermo recommends a cross-sectional area of at least 4 mm².

Upon removal of the product, disconnect the product from the power supply and all other communication ports before disconnecting the protective earthing conductor.

⚠️ HAZARDOUS VOLTAGE

Do not open an energised product. Hazardous voltage may occur when connected to a power supply.

For RedFox models with a rated voltage above 48 VDC or 30 VAC: Apply the protective cap (delivered with the product) on the power cable.

⚠️ WARNING - PREVENT ACCESS TO HAZARDOUS VOLTAGE CABLE

Apply the protective cap (if delivered with the product) on the power cable, according to the illustrated steps below. The number of pins on the connector plug may vary depending on product.

To prevent accidentally pulling out wires, make sure the power cable and the wires are firmly attached to the protective cap.

For screw connectors, make sure the screws are properly tightened, as well as routing the wires separately from other wires. For connectors with straps, fasten the cable as strain relief, as well as routing the wires separately.

[Illustration: Diagram showing three steps of applying a protective cap to a power cable connector.]

⚠️ PROTECTIVE FUSE

It must be possible to disconnect manually from the power supply. Ensure compliance to national installation regulations.

Replacing the internal fuse must only be performed by Westermo qualified personnel.

⚠️ POWER SUPPLY CONNECTION

There are safety regulations governing the power source that can be used in conjunction with the product. Refer to chapter Interface Specifications.

⚠️ REDUCE THE RISK OF FIRE

To reduce the risk of fire, use only telecommunication line cords with a cable diameter of AWG 26 or larger. Regarding power cable dimensions, see chapter Interface Specifications.

⚠️ CLASS 1 LASER PRODUCT

Do not look directly into a fibre optical port or any connected fibre, although the product is designed to meet the Class 1 Laser regulations and complies with 21 CFR 1040.10 and 1040.11.

⚠️ HANDLING OF SFP TRANSCEIVERS

SFP transceivers are supplied with plugs to avoid contamination inside the optical port. They are very sensitive to dust and dirt. If the fibre optic cable is disconnected from the product, a protective plug must be used on the transmitter/receiver. The protective plug must be kept on during transportation. The fibre optic cable must be handled the same way.

⚠️ CORROSIVE GASES

If the product is placed in a corrosive environment, it is important that all unused connector sockets are protected with a suitable plug, in order to avoid corrosion attacks on the gold plated connector pins.

⚠️ ELECTROSTATIC DISCHARGE (ESD)

Prevent electrostatic discharge damage to internal electronic parts by discharging your body to a grounding point (e.g. use a wrist strap).

⚠️ CABLE TEMPERATURE RATING FOR FIELD TERMINAL WIRES

There may be a requirement on the minimum temperature rating of the cable to be connected to the field wiring terminals, see chapter Interface Specifications.

2.3. Care Recommendations

Follow the care recommendations below to maintain full operation of the product and to fulfill the warranty obligations:

If the product is used in a manner not according to specification, the protection provided by the equipment may be impaired.

If the product is not working properly, contact the place of purchase, the nearest Westermo distributor office or Westermo technical support.

2.4. Product Disposal

This symbol means that the product shall not be treated as unsorted municipal waste when disposing of it. It needs to be handed over to an applicable collection point for recycling electrical and electronic equipment.

Proper disposal of the product helps minimize hazardous substances and prevents potential negative impacts on both the environment and human health.

[Image: WEEE symbol for treatment of product disposal]

2.5. Compliance Information

2.5.1. Agency Approvals and Standards Compliance

Type Approval/Compliance
EMC
  • EN 50121-4/IEC 62236-4, Railway signalling and telecommunications apparatus
  • EN/IEC 61000-6-2, Immunity industrial environments
  • EN/IEC 61000-6-4, Emission industrial environments
  • EN/IEC 61000-6-5, Immunity power station and substation environment
EMI
  • FCC Part 15.105 Class A
Substation automation
  • IEEE 1613, Testing Requirements for Communications Networking Devices Installed in Electric Power Substations
  • IEC 61850-3, Communication networks and systems for power utility automation - Part 3: General requirements
Marinea
  • DNV GL rules for classification - Ships and offshore units
Safety
  • EN/IEC/UL 61010-1, Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 1: General requirements
  • EN/IEC/UL 61010-2-201, Safety requirements for electrical equipment for measurement, control, and laboratory use - Part 2-201: Particular requirements

a.Pending for RedFox-5728(-E)-F24G-T4G-LV/LVLV and HV/HVHV models

2.5.2. EN/IEC/UL 61010-2-201 Notice

This product has been tested and found compliant to EN/IEC/UL 61010-2-201, Safety requirements for electrical equipment for measurement, control, and laboratory use. In accordance with the definitions of the standard, this product shall be handled by skilled service personnel.

2.5.3. FCC Part 15.105 Class A Notice

This product has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.

These limits are designed to provide reasonable protection against harmful interference when the product is operated in a commercial environment.

This product generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the user manual, may cause harmful interference to radio communications. Operation of this product in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at the users own expense.

2.5.4. Simplified Declaration of Conformity

Hereby, Westermo declares that this product is in compliance with applicable EU directives and UK legislations. The full declaration of conformity and other detailed information is available at www.westermo.com/support/product-support.

[Image: European Conformity (CE) and UK Conformity Assessed (UKCA) markings]

3. Product Description

3.1. Product Description

RedFox 5728 takes communication reliability for substations to a new level. Westermo understands that in critical substation automation applications, even the loss of a single piece of data can disturb the operations, and that is why RedFox 5728 brings the highest reliability to your network. Withstanding the toughest environmental conditions, including the high EMI levels derived from load switching and lightning strikes and extreme ambient temperatures, RedFox-5728 ensures 100% uptime, no matter what.

IEC 61850-3 and IEEE 1613 standards define the requirements and test levels for networking devices. They specify two different device reliability classes: Class 1 devices, which allow for communication errors; and Class 2 devices, which do not allow loss of a single transmission package even during the highest electro magnetic disturbances (EMI). RedFox 5728 meets or exceeds all test levels for Class 2 fulfilment, attaining KEMA type test gold certification, ensuring zero down-time, communication losses, delays or errors.

Superior build quality, the exclusive use of industrial grade components and extensive in-house testing results in class-leading MTBF and extended service life. Designed to run efficiently from either one or two power inputs, with dual internal power supplies fully isolated from each other and all other interfaces. The 28-port switch has all connectors located at the front for easy access and a range of different port configurations, customizable with SFP transceivers.

For resilient operations in substations not only is the most robust hardware needed, but also the most robust software. Available with both layer 2 and layer 3 functionality, RedFox 5728 is powered by the next generation WeOS operating system, which ensures continuous operation and support for an expanding range of protocols and features. Intuitive set-up and configuration enable easy and cost-efficient installation and removes the need for specialized IT support or training. Recognizing the growing sophistication of cyberattacks, an extensive suite of cyber security tools is also available.

3.2. Available Models

Art. no. Model No. of SFP ports No. of copper ports Layer
3641-4350 RedFox-5728-F4G-T24G-LV 4 24 Layer 2
3641-4355 RedFox-5728-F4G-T24G-LVLV 4 24 Layer 2
3641-4550 RedFox-5728-F4G-T24G-HV 4 24 Layer 2
3641-4555 RedFox-5728-F4G-T24G-HVHV 4 24 Layer 2
3641-4360 RedFox-5728-F16G-T12G-LV 16 12 Layer 2
3641-4365 RedFox-5728-F16G-T12G-LVLV 16 12 Layer 2
3641-4560 RedFox-5728-F16G-T12G-HV 16 12 Layer 2
3641-4565 RedFox-5728-F16G-T12G-HVHV 16 12 Layer 2
3641-4620 RedFox-5728-F24G-T4G-LV 24 4 Layer 2
3641-4630 RedFox-5728-F24G-T4G-LVLV 24 4 Layer 2
3641-4640 RedFox-5728-F24G-T4G-HV 24 4 Layer 2
3641-4650 RedFox-5728-F24G-T4G-HVHV 24 4 Layer 2
3641-4250 RedFox-5728-E-F4G-T24G-LV 4 24 Layer 3
3641-4255 RedFox-5728-E-F4G-T24G-LVLV 4 24 Layer 3
3641-4450 RedFox-5728-E-F4G-T24G-HV 4 24 Layer 3
3641-4455 RedFox-5728-E-F4G-T24G-HVHV 4 24 Layer 3
3641-4260 RedFox-5728-E-F16G-T12G-LV 16 12 Layer 3
3641-4265 RedFox-5728-E-F16G-T12G-LVLV 16 12 Layer 3
3641-4460 RedFox-5728-E-F16G-T12G-HV 16 12 Layer 3
3641-4465 RedFox-5728-E-F16G-T12G-HVHV 16 12 Layer 3
3641-4720 RedFox-5728-E-F24G-T4G-LV 24 4 Layer 3
3641-4730 RedFox-5728-E-F24G-T4G-LVLV 24 4 Layer 3
3641-4740 RedFox-5728-E-F24G-T4G-HV 24 4 Layer 3
3641-4750 RedFox-5728-E-F24G-T4G-HVHV 24 4 Layer 3

3.3. Hardware Overview

[Illustration: Front view of the RedFox-5728-F16G-T12G-HVHV with numbered ports and indicators.]

No. Description No. Description
1 I/O connection 2 Console port
3 Micro SD 4 LED indicators
5 100/1000 Mbit/s SFP port (number depending on model) 6 10/100/1000 Mbit/s TX ports (number depending on model)
7 Power input 8 Protective earth
9 Label with data matrixa

a.The base MAC address and production date of the product is included in the front label data matrix.

3.4. Connector Information

3.4.1. Power Input

Illustration Position Product marking Direction Description
[Illustration: AC/DC power input terminals] AC/DC1 L(+)
N(-)
PE
Input Line/Phase (AC), positive (DC)
Neutral (AC), negative/return (DC)
Functional earth
[Illustration: AC/DC power input terminals] AC/DC2 L(+)
N(-)
PE
Input Line/Phase (AC), positive (DC)
Neutral (AC), negative/return (DC)
Functional earth

3.4.2. I/O Connection

Illustration Position Product marking Direction Description
[Illustration: I/O connection terminals DI+, DI-, Status NO, Status C, Status NC] Digital in DI+
DI-
Input Digital in+
Digital in-
Status Status NO
Status C
Status NC
Output Alarm (status) relay contact
NO - Normally Open
C - Common
NC - Normally Closed

The Digital in is an opto-isolated digital input, which can be used to monitor external events.

The Status output is a potential free, opto-isolated, alternation (Form-C) solid-state relay. This can be configured to monitor various alarm events within the product, see WeOS user documentation at www.westermo.com. An external load in series with an external DC voltage source is required for proper functionality.

Unit condition Status NO-C Status NC-C
Unpowered / pre-operational or Alarm active OPEN CLOSED
Operational and Alarm inactive CLOSED OPEN

3.4.3. Console Port

The console port can be used to connect to the CLI (Command Line Interface). The console connector is a USB cable that connects to a FTDI FT232R USB to serial converter internally. For drivers, refer to www.ftdichip.com and download the appropriate VCP driver.

Remove the protective cover before inserting the console cable. After removing the console cable, be sure to reassemble the protective cover again.

[Illustration: Close-up of the console port on the front panel, showing how to remove the protective cover.]

3.4.4. Micro SD

To insert the micro SD card correctly, turn the gold plated pins upwards.

[Illustration: Micro SD card being inserted into a slot, with gold plated pins facing upwards.]

3.4.5. SFP Transceivers

The product supports UL/IEC/CSA certified and Westermo labelled SA-approved transceivers only. See Westermo's modular transceivers datasheets 100 Mbit and 1 Gbit for SA-approved SFP transceivers, which can be downloaded from the product support pages at www.westermo.com/support/product-support.

Each SFP slot can hold one SFP transceiver. See "Transceiver User Guide 6100-0000" for transceiver handling instructions, which also can be downloaded from the product support pages at www.westermo.com/support/product-support.

In the event of contamination, the optical connectors in the SFP transceivers should only be cleaned by the use of forced nitrogen and some kind of cleaning stick. Recommended cleaning fluids are methyl-, ethyl-, isopropyl- or isobutyl alcohol, hexane or naphtha.

⚠️ HANDLING OF SFP TRANSCEIVERS

SFP transceivers are supplied with plugs to avoid contamination inside the optical port. They are very sensitive to dust and dirt. If the fibre optic cable is disconnected from the product, a protective plug must be used on the transmitter/receiver. The protective plug must be kept on during transportation. The fibre optic cable must be handled the same way.

3.5. LED Indicators

LED Status Description
ON OFF Product has no power
GREEN All OK, no alarm condition
RED Alarm condition, or until product has started up. (Alarm conditions are configurable, see WeOS5 User Guide)
RSTP/ USR1 OFF RSTP disabled
GREEN RSTP enabled
BLINK Product selected as RSTP/STP root switch
USR1 Configurable, see WeOS5 User Guide
FRNT OFF FRNT disabled
GREEN FRNT OK
RED FRNT error
FLASH Product configured as FRNT focal point
DC1 / AC/DC1 OFF Product has no power
GREEN Power OK on DC1 / AC/DC1
RED DC1 / AC/DC1 input voltage is below operating voltage limit
DC2/ AC/DC2a. OFF Product has no power
GREEN Power OK on DC2 / AC/DC2
RED DC 2 / AC/DC2 input voltage is below operating voltage limit
USR2 Configurable, see WeOS5 User Guide
TX/FX ports OFF No link
GREEN Link established
GREEN FLASH Data traffic indication
YELLOW Port alarm, or port is set in blocking state by link redundancy protocol

a.Only available on RedFox-5728 HVHV models

3.6. Dimensions

Dimensions are stated in mm.

[Illustration: Dimensional drawing of the RedFox 5728, showing front, top, and side views with dimensions.]

4. Installation

4.1. Mounting

RedFox-5728 is designed for installation in 19" rack solutions, with a shallow depth of 240 millimetres.

4.1.1. Rack Mounting

The product can be mounted in all directions inside a 19" apparatus cabinet. Use supplied M6x25 (Philips no. 3) or 1/4x1" screws.

[Illustration: RedFox 5728 unit mounted in a 19-inch rack.]

4.2. Protective Earth Connection

For correct function, the earth connection needs to be properly connected to a designated PE rail. Torx: T25 and torque: 3.2 Nm.

[Illustration: Rear view of the RedFox 5728 showing the protective earth connection terminal.]

4.3. Cooling

This product relies on convection cooling. To avoid obstruction of the airflow around the product, follow the spacing recommendations.

For mounting in 19" apparatus cabinet without forced ventilation, a minimum spacing of 1U according to IEC 60297 or 45 mm (1.75") above and below is recommended.

4.3.1. SFP Placement

Ambient temperature effects the lifelength of electronic components, and prolonged exposure to high temperatures can reduce the overall lifelength. To maximize the lifelength of SFPs used in the product, it is recommended to consider the following for optimized placement of the SFPs in the RedFox-F24G products in terms of thermal characteristics and heat dissipation capabilities:

[Illustration: Front view of the RedFox 5728 showing SFP port placement, with labels indicating high-power and low-power SFPs.]

5. Specifications

5.1. Interface Specifications

ℹ️ NOTE - USE OF ANTISTATIC ARM-WRIST BAND

To minimize the risk of exposing the unit to unintentional large static electric fields - if service and maintenance need to be performed during operation, always use an antistatic arm-wrist band.

Power port
Rated voltagea. LV and LVLV models: 24-48 VDC
HV and HVHV models: 110-240 VAC, 50-60 Hz, 110-240 VDC
Operating voltage LV and LVLV models: 18-60 VDC
HV and HVHV models: 85-264 VAC, 47-63 Hz, 85-264 VDC
Rated currentb.c. RedFox-5728-(E-)F4G-T24G-LV
RedFox-5728-(E-)F4G-T24G-LVLV
RedFox-5728-(E)-F16G-T12G-LV
RedFox-5728-(E)-F16G-T12G-LVLV
RedFox-5728-(E-)F24G-T4G-LV
RedFox-5728-(E-)F24G-T4G-LVLV
RedFox-5728-(E-)F4G-T24G-HV
RedFox-5728-(E-)F4G-T24G-HVHV
RedFox-5728-(E-)F16G-T12G-HV
RedFox-5728-(E-)F16G-T12G-HVHV
RedFox-5728-(E-)F24G-T4G-HV
RedFox-5728-(E-)F24G-T4G-HVHV
1.08 A at 24 VDC and 0.54 A at 48 VDC
1.22 A at 24 VDC and 0.61 A at 48 VDC
1.30 A at 24 VDC and 0.65 A at 48 VDC
0.13 A at 240 V AC/DC and 0.26 A at 110 V AC/DC
0.15 A at 240 V AC/DC and 0.30 A at 110 V AC/DC
0.16 A at 240 V AC/DC and 0.34 A at 110 V AC/DC
Fuse rating LV and LVLV models: 4A(T), 125 VDC, breaking capacity 100 A, UL248-14
HV and HVHV models: 4A(T), 350 VAC/VDC, breaking capacity 100 A, UL248-14
Rated frequency LV and LVLV models: DC
HV and HVHV models: DC, 50-60 Hz
Inrush current, I2td. LV and LVLV models: 120 mA²s at 24 VDC
350 mA²s at 48 VDC
HV and HVHV models:
4 mA²s at 240 VAC, 50 HzDC, 50-60 Hz
0.4 mA²s at 110 VAC, 60 Hz
2 mA²s at 240 VDC
0.1 mA²s at 110 VDC
Startup currente. 2x nominal current
Polarity Reverse polarity protected
Redundant power input Yes (LV models)
Redundant power supply Yes (LVLV and HVHV models)
Shielded cable Not required
Isolation All other ports
Connector Detachable screw terminal
Conductor cross section (flexible) 0.5-1.5 mm² (AWG 20-16). Use copper conductors only.
Stripping length cable 6-7 mm
Cable temperature rating Minimum temperature rating of the cable to be connected to the field wiring terminals is +77 °C
Tightening torque, terminal screw 0.34 Nm
Tightening torque, screw flange 0.34 Nm
a.For LV and LVLV models, only compliant Class I or Class II power supplies with SELV/PELV output shall be used with the product
b.For HVHV models, AC/DC1 shall be regarded as the primary supply input, which gives the highest efficiency. When both AC/DC1 and AC/DC2 inputs are energized, some portion of the unit's power consumption will be drawn from AC/DC2, while AC/DC1 will utilize the majority of the power consumption. For LVLV models, the redundant power supplies works in a load sharing mode so the current consumption will be split in half.
c.Including SFP transceivers
d.Measured for 0.1 second at startup
e.Recommended external supply current capability for proper startup
I/O connection, Digital inputa.
Isolation to All other ports.
Connector Detachable screw terminal
Conductor cross section (flexible) 0.08-1.5 mm² (AWG 28-16). Use copper conductors only.
Stripping length cable 7 mm
Cable temperature rating Minimum temperature rating of the cable to be connected to the field wiring terminals is +77 °C
Tightening torque, terminal screw 0.22-0.25 Nm
Terminal torque, screw flange 0.3 Nm
Circuit type SELV
Maximum voltage/current 60 VDC, IIN ≤ 2.9 mA at 60 VDC
Voltage levels Logic one: >8 VDC
Logic zero: <5 VDC
a.External circuits connected to I/O connectors shall be SELV-rated circuits, galvanic isolated from mains.
I/O connection, Relay output
Contact resistance Maximum 30 Ω
Isolation to All other ports.
Connector Detachable screw terminal
Conductor cross section (flexible) 0.08-1.5 mm² (AWG 28-16). Use copper conductors only.
Stripping length cable 7 mm
Cable temperature rating Minimum temperature rating of the cable to be connected to the field wiring terminals is +77 °C
Tightening torque, terminal screw 0.22-0.25 Nm
Terminal torque, screw flange 0.3 Nm
Circuit type SELV
Type of switch Solid state, DC general use, DC Pilot duty
Maximum withstand across open contacts 60 VDC (continous)
Permissible current 80 mA (continous), 120 mA (short term 1 s.)
Ethernet TXa.
Electrical specification IEEE std 802.3
Data rate 10 Mbit/s, 100 Mbit/s, 1 Gbit/s, manual or auto
Duplex Full or half, manual or auto
Circuit type SELV according to EN/IEC/UL 61010-2-201
PELV according to EN/IEC 60255-27
TNV-1 according to IEC 62151
Transmission range Up to 100 m with CAT5e cable or better
Isolation All other ports
Cabling Shielded cable CAT5e or better is recommended
Conductive chassis Yes
a.10/100/1000 Mbit/s ports are:
RedFox-5728-F4G-T24G-HV, -HVHV, -LV and -LVLV: 5-28
RedFox-5728-F16G-T12G-HV, -HVHV, -LV and -LVLV: 7-10, 15-18, 23-26
RedFox-5728-F24G-T4G-HV, -HVHV, -LV and -LVLV: 23-26
SFP portsa.
Optical/Electrical specification IEEE std 802.3
Data rate 100 Mbit/s, 1 Gbit/s
Duplex Full or half, manual or auto
Transmission range Depending on transceiver
Connector SFP slot holding fibre transceiver
a.SFP ports are:
RedFox-5728-F4G-T24G-HV, -HVHV, -LV and -LVLV: 1-4
RedFox-5728-F16G-T12G-HV, -HVHV, -LV and -LVLV: 1-6, 11-14, 19-22, 27-28
RedFox-5728-F24G-T4G-HV, -HVHV, -LV and -LVLV: 1-22,27-28
Console port
Electrical specification USB 2.0 device interface
Data rate Up to 480 Mbps (high-speed mode)
Circuit type PELV
Maximum supply current 100 mA
Connector USB Micro B connector in device mode
Micro SD
Electrical specification Secure Digital 2.0
Maximum supply current 100 mA
Connector Micro SD connector

5.2. Type Tests and Environmental Conditions

Environmental phenomena Basic standard Description Test levels
ESD EN 61000-4-2 Enclosure Contact: ±8 kV
Air: ±15 kV
Fast transients EN 61000-4-4 AC power port
DC power port
Earth port
I/O port
Ethernet ports
±4 kV, direct coupling
±4 kV, capacitive coupling clamp
Surge EN 61000-4-5 AC power port
DC power port
I/O port
Ethernet ports
±4.0 kV L-E: 12 Ω/9 µF, 1.2/50 µs
±2.0 kV L-L: 2 Ω/18 µF, 1.2/50 µs
±4.0 kV L-E: 42 Ω/0.5 µF, 1.2/50 µs
±2.0 kV L-L: 42 Ω/0.5 µF, 1.2/50 µs
±4.0 kV L-E: 2 Ω Direct on shield
Power frequency magnetic field EN 61000-4-8 Enclosure 100 A/m, cont.
Pulsed magnetic field EN 61000-4-9 Enclosure 1000 A/m, 3 s
Damped oscillatory magnetic field EN 61000-4-10 Enclosure 300 A/m (peak)
Voltage dips and interruptions (AC port) EN 61000-4-11 AC power port 70% UT, 1 period
40% UT, 50 periods
0% UT, 5 periods
0% UT, 50 periods
Conducted CM disturbances EN 61000-4-16 AC power port
DC power port
I/O port
Ethernet ports
30V to 3V, 15 to 150 Hz
3V, 150 Hz to 1.5 kHz
30V to 10V, 1.5 to 15 kHz
30V, 15 to 150 kHz
Mains frequency voltage 30V continuous, DC, 50 and 60 Hz, 300V for 1s
Ripple on DC power supply EN 61000-4-17 DC power port 10% of UN, 100 Hz and 120 Hz
Damped oscillatory wave EN 61000-4-18 AC power port
DC power port
I/O port
Ethernet ports
CM: ±2.5 kV 200 Ω/0.5 µF, 1 MHz
CM: ±2.0 kV 50 Ω/33 nF, 10 MHz
DM: ±2.5 kV 200 Ω/0.5 µF, 1 MHz
CM: ±2.5 kV 200 Ω/0.5 µF, 1 MHz
DM: ±2.5 kV 200 Ω/0.5 µF, 1 MHz
CM: ±2.5 kV 200 Ω/1 µF, 1 MHz direct of shield
Voltage dips and interruptions (DC port) EN 61000-4-29 DC power port 70% UT, 100 ms
40% UT, 100 ms
0% UT, 50 ms
Radiated RF immunity EN 61000-4-3
IEEE Std C37.90.2
Enclosure 20 V/m, 80% AM (1 kHz) at 80 MHz to 2 GHz, Spot freq.: 80, 160, 380, 450, 900, 1600, 1850 MHz
10 V/m, 80% AM (1 kHz) at 2 to 6 GHz, Spot freq.: 2150, 3800 MHz
20 V/m, pulse keying (2 Hz) at 80 MHz to 1 GHz, Spot freq.: 1732, 1800 MHz
10 V/m, pulse keying (2 Hz), Spot freq.: 2310, 2450, 5800 MHz
Conducted RF immunity EN 61000-4-6 AC power port
DC power port
I/O port
Ethernet ports
10 V 0.15 to 80 MHz, Spot freq.: 27, 68 MHz
Radiated RF emission CISPR 16-2-3
ANSI 63.4
Enclosure Class A (FCC Part 15B)
Conducted RF emission CISPR 16-2-1
ANSI 63.4
CISPR 22
Power ports
Ethernet ports
Class A (FCC Part 15B)
Class A
Dielectric strength IEC 60255-27 Power port (AC)
to all other ports
Power port (DC)
to all other ports
I/O port to all
other ports
Ethernet ports
to all other ports
2000 VAC rms, 60 s
1500 VAC rms, 60 s
Impulse withstand IEC 60255-27 Power port (AC)
Power port (DC)
I/O port
Ethernet ports
5 kV
1 kV

Environmental and mechanical conditions

Environmental phenomena Basic standard Description Test levels
Temperatures EN 60068-2-1
EN 60068-2-2
EN 60068-2-14
Operational
Storage and transport
-40 to +70°C (-40 to +158°F)a.
-50 to +85°C (-58 to +185°F)
Humidity EN 60068-2-30
EN 60068-2-78
Operational
Storage and transport
5-95% relative humidity
Altitude Operational 2000 m/80 kPa
Service life Operational 10 years
MTBF hours RedFox model MIL-HDBK 217F Operational 5728-(E-)F4G-T24G-LV: 344,000
5728-(E-)F4G-T24G-LVLV: 274,000
5728-(E-)F4G-T24G-HV: 316,000
5728-(E-)F4G-T24G-HVHV: 269,000
5728-(E-)F16G-T12G-LV: 356,000
5728-(E-)F16G-T12G-LVLV: 282,000
5728-(E-)F16G-T12G-HV: 353,000
5728-(E-)F16G-T12G-HVHV: 295,000
5728-(E-)F24G-T4G-LV: 371,000
5728-(E-)F24G-T4G-LVLV: 291,000
5728-(E-)F24G-T4G-HV: 386,000
5728-(E-)F24G-T4G-HVHV: 318,000
Telcordia 5728-(E-)F4G-T24G-LV: 645,000
5728-(E-)F4G-T24G-LVLV: 514,000
5728-(E-)F4G-T24G-HV: 678,000
5728-(E-)F4G-T24G-HVHV: 549,000
5728-(E-)F16G-T12G-LV: 674,000
5728-(E-)F16G-T12G-LVLV: 532,000
5728-(E-)F16G-T12G-HV: 710,000
5728-(E-)F16G-T12G-HVHV: 570,000
5728-(E-)F24G-T4G-LV: 870,000
5728-(E-)F24G-T4G-LVLV: 647,000
5728-(E-)F24G-T4G-HV: 931,000
5728-(E-)F24G-T4G-HVHV: 703,000
Vibration IEC 60255-21-1 Operational Class 2, 10 to 60 Hz at ±0.075 mm,
60 to 150 Hz at 1g
1 sweep cycle in each axis, 1 octave/
min.
IEC 60255-21-3,
method A
Non-
operational,
endurance test
Class 2, 10 to 150 Hz at 2g
20 sweep cycles in each axis, 1 octave/
min.
EN 60068-3-3 Operational,
seismic test
Class 2
Horizontal: 1 to 8 Hz at ±7.5 mm, 8 to
35 Hz at 2g
Vertical: 1 to 8 Hz at 3.5 mm, 8 to 35 Hz
at 1g
1 sweep cycle in each axis (3x5), 1
octave/min
EN
60068-2-64
Operational 5 to 8 Hz at ±7.5 mm
8 to 500 Hz at 2g
5 sweep cycles in each axis (3x5), 1
octave/min
2.3 m/s² random, 5 to 2000 Hz, 3x1.5h
Shock IEEE 1613 Operational Class V.S.3 1 to 150 Hz at <30 mm/s
IEC 60255-21-2 Operational
Non-operational
Class 2, 10g/11 ms, 3x6 shocks
Class 2, 30g/11 ms, 3x6 shocks
Bump Class 2, 20g/16 ms, 6x1000 bumps
Fall IEEE 1613 Non-operational Height of fall = 100 mm
Device Reliability Class IEC 61850-3
IEEE 1613
Class 2: Error free, uninterrupted communication
Enclosure EN/IEC/UL 61010-1 Aluminium Fire enclosure
Weight 3.8 kg
Degree of protection EN 60529 Enclosure IP40
Cooling EN/IEC/UL 61010-1 Convection
Pollution degree EN/IEC/UL 61010-1 PD2 Macro and Micro Environment
Overvoltage category EN/IEC/UL 61010-1 LV and LVLV models: OVC II
HV and HVHV models: OVC III
Insulation class EN/IEC/UL 61010-1 LV and LVLV models: Class III equipment
HV and HVHV models: Class I equipment
Location EN/IEC/UL 61010-1 Indoor use
a.Depending on SFP types used

6. Revision Notes

Revision Date Change description
Rev. I May 2025 Illustrations updated, RedFox-5728-(E-)F24G-T4G-HV and -HVHV models added - 2.5.1 Agency Approvals and Standards Compliance updated, 3.2 Available Models updated, 4.3 Cooling; text updated, 4.3.1 SFP Placement updated, 5.1 Interface Specifications updated, 5.2 Type Tests and Environmental Conditions updated
Rev. H Dec. 2024 2.2. Safety Information; Warning - Prevent access to hazardous voltage cable updated, 2.4 Product Disposal updated, 2.5.1 Agency Approvals and Standards Compliance updated, 3.2 Available Models updated, 3.4.2. I/O Connection updated, 4.3 Cooling; text updated, 4.3.1 SFP Placement; new chapter, 5.1 Interface Specifications updated with references to new RedFox-5728-(E-)F24G-T4G-LV and -LVLV models, 5.2 Type Tests and Environmental Conditions updated with references to new RedFox-5728-(E-)F24G-T4G-LV and -LVLV models
Rev. G April 2024 2.5.1 Agency Approvals and Standards Compliance updated with DNV approval, 3.2 Available Models updated, 5.1 Interface Specifications (Power port table, Ethernet TX and SFP ports) updated, 5.2 Type Test and Environmental Conditions (MTBF hours) updated with new models
Rev. F April 2023 3.5 LED Indicators updated (ON; Blink deleted)
Rev. E Oct. 2022 5.1 Interface Specifictions updated (rated current)
Rev. D Jan. 2022 2.2 Safety Information updated; (Warning Safety during installation), 2.5.1 Agency Approvals and Standards Compliance updated, 2.5.2 FCC Part 15.105 Class A Notice added, 3.2 Available Models updated, 3.4.1 Power Input updated (table 5 and note), 5.1 Interface Specifictions updated (Power port table, Ethernet TX table, SFP ports table and footnote for inrush current), 5.2 Type Tests and Environmental Conditions updated (altitude, MTBF hours, enclosure, degree of protection, overvoltage category and insulation class)
Rev. C Nov. 2021 Added LV models, 3.2 Available Models updated, 3.4.1 Power Input updated, 3.4.3 Console port, text added, 3.4.5 SFP Transceivers updated, 3.5 LED Indicators updated, 5.1 Interface Specification updated, 5.2 Type Tests and Environmental Conditions updated
Rev. B April 2021 Product illustrations updated, 1.5 WeOS updated, 2.5.3 Simplified Declaration of Conformity updated, 3.4.3 Console port updated, 3.6 Dimensions updated, 5.1 Interface Specifications, Ethernet TX table updated, Console table updated, 5.2 Type Tests and Environmental Conditions updated
Rev. A Nov. 2020 First version of the user guide

Westermo
Metallverksgatan 6, SE-721 30 Västerås, Sweden
Tel +46 16 42 80 00 Fax +46 16 42 80 01
E-mail: info@westermo.com
www.westermo.com

Models: RedFox 5728 Series Industrial Routing Switches, RedFox 5728 Series, Industrial Routing Switches, Routing Switches, Switches

File Info : application/pdf, 32 Pages, 6.09MB

PDF preview unavailable. Download the PDF instead.

westermo ug 6641-25001 redfox-5728 revi

References

Antenna House Formatter V7.4 MR9 Amazon Linux 2 Graviton2 : 7.4.10.66079 (2025-03-06T17:05 09) Antenna House PDF Output Library 7.4.1932

Related Documents

Preview Westermo WeOS 5.25.2 Release Notes: Software Updates, Bug Fixes, and Known Issues
Detailed release notes for Westermo WeOS version 5.25.2, covering new features, bug fixes, known limitations, and important user information for industrial network devices. Includes information on security enhancements and CLI changes.
Preview Westermo Lynx 5600 Series User Guide: Industrial Gigabit Ethernet Switch
Comprehensive user guide for the Westermo Lynx 5600 Series industrial Gigabit Ethernet switch, covering installation, safety, specifications, and compliance. Learn about its features for substation automation.
Preview Westermo Viper 20A Series User Guide: 20-Port M12 Ethernet Switches
Comprehensive user guide for the Westermo Viper 20A Series, detailing installation, specifications, safety regulations, and hardware overview for 20-port M12 Ethernet switches designed for demanding environments.
Preview Westermo Lynx 3000 Series User Guide: Industrial Ethernet Switch
Comprehensive user guide for the Westermo Lynx 3000 Series industrial Ethernet switches. Learn about product features, specifications, installation, safety regulations, and compliance information.
Preview Westermo WeConfig v2: Network Configuration and Maintenance Software
Westermo WeConfig v2 is an efficient software tool for optimizing the configuration and maintenance of industrial networks. It offers features like automatic device discovery, firmware updates, diagnostics, and security management, enhancing network robustness and reducing manual effort.
Preview Network Rail Certificate of Acceptance PA05/05858 for Westermo LAN Switches
Details the Network Rail acceptance of Westermo L108-F2G-S2 and L208-F2G-S2 LAN Switches with RS232/RS485 support, including product specifications, conditions of use, and compliance information.
Preview Westermo Viper-20A Series Managed Gbps Routing Switch
Westermo Viper-20A Series: A compact, rugged, 20-port managed Gbps routing switch designed for railway vehicles and demanding industrial environments. Features Layer 3 routing, high cybersecurity, and compliance with EN 50155 and other relevant standards.
Preview Westermo Lynx RedBox Industrial Switches User Guide
Comprehensive user guide for Westermo Lynx RedBox industrial switches, covering installation, specifications, safety regulations, and product features. This guide is intended for installation engineers and users of Westermo products.