SILENT KNIGHT ZONE MODULE

Addressable Zone Interface Module

The SK-ZONE is an addressable two-wire interface module designed for use with Honeywell Silent Knight Series fire alarm control panels (FACPs). It enables a Honeywell Silent Knight FACP to interface with and monitor two-wire conventional smoke detectors, allowing for the retrofitting of existing buildings with conventional devices. The SK-ZONE is addressed via the FACP's signaling line circuit (SLC) loop and transmits the status of one full zone of two-wire detectors to the FACP. Status conditions are reported as normal, open, or alarm. The module supervises the detector zone and the external power supply. All two-wire detectors monitored must be UL compatible with the SK-ZONE.

Image Description: The module is a compact electronic unit featuring various connection terminals and controls. Visible labels include: "SK-ZONE.", "MODEL NO", "MSCOM", "SMOKE DETECTOR", "ZONE 10: A", "T11 Ext SUP (-)", "T10 Ext SUP (+)", "SLC-T1", "SLC T2", "SUP A/B (+)", "SUP A/B (-)", "LOOP ADDRESS", "N04-3854-002", "FOR WARRANTY CLAIMS, RETURN TO SYSTEM SENSOR", "ASSEMBLED IN USA", "ALL CIRCUITS ARE POWER LIMITED", "REMOVAL OF LABEL PROHIBITED", "FOR INDOOR APPLICATIONS SEE 154-3854 REV. 001 FOR INSTALLATION INSTRUCTIONS", and patent number "5,535,389".

INSTALLATION

The SK-ZONE mounts directly into a 4" square electrical box. The electrical box must have a minimum depth of 2-1/8”. A surface mount electrical box, System Sensor® PN SMB500, is available from Honeywell.

COMPATIBILITY

The SK-ZONE is compatible with the following Silent Knight Series FACPs:

  • 6808U
  • 6820U
  • 6808UEVS

FEATURES & BENEFITS

  • Converts a conventional two-wire loop to an SLC loop.
  • Fully supervised.
  • Support for Style B and Style D wiring.
  • Panel-controlled status LED that flashes green in normal state and is solid red in alarm.
  • Rotary address switches for fast installation.
  • SEMS screws for easy wiring.

AGENCY LISTING AND APPROVAL

  • UL Listed
  • FM Approved

TECHNICAL SPECIFICATIONS

SPECIFICATIONS
Physical4.5" H x 4"W x 1.25" D
Shipping Weight6.3oz (196g)
ELECTRICAL RATINGS
Operating Voltage:15 to 32VDC
External Power SupplyAlarm Current: 90mA per module, Standby Current: 13mA @ 24 VDC (nominal)
Max Current5.1 mA (LED ON)
End-of-Line Resistance:3.9k ohm
SLC Loop Impedance:25 ohm
Initiating Device Circuit Wiring Resistance:25W max

ORDERING INFORMATION

ProductDescription
SK-ZONE.Addressable two-wire interface module

ACCESSORIES

ProductDescription
SMB5004" Square surface mount electrical box

ENVIRONMENTAL

ParameterValue
Operating Temperature:32°-120°F (0°C - 49°C)
Humidity:10 to 93% non-condensing

For a complete listing of all compliance approvals and certifications, please visit https://buildings.honeywell.com.

Silent Knight™ is a trademark of Honeywell International, Inc. This document is not intended for installation purposes. Honeywell strives to keep product information up-to-date and accurate but cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For Technical Support, please call 0008000502167.

Honeywell International India Pvt Ltd Sector 36, Pace City II, Gurgaon, Haryana India
https://www.honeywellbuildings.in/

PDF preview unavailable. Download the PDF instead.

hon-ba-fire-sk-zone-datasheet Microsoft Word for Microsoft 365 Microsoft Word for Microsoft 365

Related Documents

Preview Honeywell Silent Knight SK-ISO Line Isolator Module Datasheet
Technical datasheet for the Honeywell Silent Knight SK-ISO Line Isolator Module, detailing its features, specifications, installation, and compatibility with Silent Knight fire alarm control panels.
Preview SK-Duct Air Duct Smoke Detector Installation and Maintenance Manual | Honeywell
Comprehensive installation and maintenance guide for the Honeywell SK-Duct Air Duct Smoke Detector. Covers specifications, installation procedures, wiring, testing, and troubleshooting.
Preview Honeywell Silent Knight 6820/6820EVS Addressable Fire Alarm Control Panel Manual
Comprehensive manual for the Honeywell Silent Knight 6820/6820EVS addressable fire alarm control panel, detailing installation, operation, programming, and system features for fire safety and emergency communication.
Preview Honeywell SK-DUCT-W Duct Smoke Detector: Installation and Maintenance Manual
Comprehensive installation and maintenance guide for the Honeywell SK-DUCT-W Duct Smoke Detector, covering specifications, installation procedures, wiring, testing, cleaning, sensor replacement, and optional accessories.
Preview Honeywell 6820 / 6820EVS Addressable Fire System Installation and Operation Guide
This guide provides comprehensive installation and operation instructions for the Honeywell 6820 / 6820EVS Addressable Fire System, an Emergency Voice System designed for early warning and communication during fire emergencies.
Preview Honeywell XLS3000 Intelligent Addressable Fire Alarm System | Datasheet
Discover the Honeywell XLS3000 Intelligent Addressable Fire Alarm System, designed for robust fire detection and life safety in medium to large-scale facilities. This datasheet details its advanced features like FlashScan technology, Intelligent Sensing, modular design, and extensive device support for comprehensive building protection.
Preview SK-NIC Network Interface Card Installation Guide | Honeywell Silent Knight
Official installation document for the Honeywell Silent Knight SK-NIC Network Interface Card. Details compatibility, specifications, and wiring instructions for Fire Alarm Control Panels (FACPs).
Preview Esserbus Transponder IQ8FCT XS | Honeywell Technical Specification
Technical datasheet for the Honeywell Esserbus Transponder IQ8FCT XS, a fire control transponder and technical alarm module for fire safety systems. Details features, specifications, and accessories.