Niko P49LR Presence Detector
Article Number: 353-752521
Presence Detector P49LR, DALI-2, BMS, 32-37 m, for surface mounting, white
Product Description
Proposed product description according to BIPS 4.7.9: Presence Detector P49LR, DALI-2, BMS, 32-37 m, for surface mounting, white.
Specifications
Configuration | BMS |
Detector Technology | PIR |
Mounting | Surface mounting |
Input Voltage | DALI Bus |
Detector Output | DALI-2 |
Luminance Range | 0 lux - 10360 lux |
Maximum Current Consumption | 10 mA |
Detection Angle | 360° (3 x 120°) |
Detection Range (PIR) | Ø 37 m at a height of 3 m |
Ambient Temperature | -25 - +40 °C |
Mounting Height | 2 - 3.5 m |
Impact Resistance | IK04 |
Protection Class | IP54 |
Marking | CE |
Functional Description
Proposed functional description according to BIPS 4.7.10:
Mounting
The detector is suitable for surface mounting on all types of ceilings.
Configuration
The detector is DALI-2 certified (according to EN/IEC 62386-301/302/303/304) and must be connected to a DALI bus of a DALI-2 Application Controller (BMS System). The detector must be commissioned using the BMS software.
Commissioning App
The local sensitivity adjustment in 4 levels can be configured via the app using the 2-way Bluetooth® communication between a smartphone or tablet PC and the detector. The firmware of the detector can be updated via the app.
Bluetooth® Communication
Bluetooth® communication can be deactivated via the BMS software.
PIN Code Protection
The detector can be protected with a 4-digit PIN code in the app to prevent other users from controlling the detector or changing its settings.
Connection Terminals
The wires are connected via plug-in terminals.
Event Log
The event log in the app shows all changes made to the settings of a specific detector.
Sensitivity
The 360° detection range can be divided into three sectors of 120° each. The sensitivity of these sectors can be adjusted separately in 4 levels and even completely switched off.
Documentation
The documentation is available in digital form on an online portal. This portal also allows saving, reviewing, and releasing settings in PDF and/or Excel format. Detectors can be organized in specific projects or groups. Existing detector settings can be used as a template for new detectors.
Detection Range
The detection range is documented according to EN/IEC 63180.