Literature-Library-logo

Literature Library FG7T Two Stage, Variable Speed, Condensing Upflow and Downflow Gas Furnaces

Literature-Library-FG7T-Two-Stage,-Variable-Speed,-Condensing-Upflow-and-Downflow-Gas-Furnaces-product

Product Information

Technical Specifications

  • Model: FG7T (E and N Series)
  • Type: Two Stage, Variable Speed, Condensing Upflow and Downflow Gas Furnaces
  • Efficiency: 96% AFUE
  • Input: 60,000 – 115,000 Btuh
  • Location: Can be installed free standing in a utility room, basement, or enclosed in an alcove or closet
  • Certification: Design certified by CSA for application in Canada and the United States

Features and Benefits

  • Flame Sensor
  • Finish Flange
  • Roll-Out Switch
  • Burner Assembly
  • Pressure Switches (Inducer)
  • Main Air Limit Switch
  • Inducer Limit Switch
  • Inducer Assembly
  • Blower Door Switch
  • Air Flow Igniter
  • Gas Valve Furnace Control Board
  • Pressure Switches (Condensate)
  • Transformer
  • Motor Control Box
  • Motor Choke (C & D cabinets only)
  • Motor Control Board Blower Assembly

Product Usage Instructions

Installation

The high-efficiency upflow gas furnace can be installed free-standing in a utility room, or basement, or enclosed in an alcove or closet. Ensure proper clearance and ventilation according to local building codes. Follow the installation instructions provided in the user manual for a safe and proper installation.

Operation

  1. Ensure the gas and electrical connections are properly connected.
  2. Set the desired temperature on the furnace control board.
  3. Turn on the power to the furnace.
  4. The furnace will go through a startup sequence, and the blower will start once the furnace is ready.
  5. Observe the flame sensor, igniter, and burner assembly for proper operation.
  6. Monitor the temperature rise and adjust settings if necessary.
  7. Regularly check and replace the air filters as needed.

Maintenance

To ensure optimal performance and longevity of the gas furnace, regular maintenance is required:

  • Clean or replace air filters regularly.
  • Inspect and clean the burner assembly.
  • Clean the flame sensor.
  • Check and clean the blower assembly.
  • Inspect and clean the venting system.
  • Check for any gas leaks or unusual odors.

Troubleshooting

If you experience any issues with the gas furnace, refer to the troubleshooting section in the user manual. If the issue persists, contact a qualified technician for assistance.

Safety Precautions

When working with or around the gas furnace, always follow these safety precautions:

  • Turn off power to the furnace before performing any maintenance or repairs.
  • Use caution when handling hot surfaces.
  • Ensure proper ventilation during operation.
  • Do not attempt to modify or tamper with any components.
  • Keep flammable materials away from the furnace.

FAQ

  • Q: Where can the high efficiency upflow gas furnace be installed?
    • A: The furnace can be installed free standing in a utility room, basement, or enclosed in an alcove or closet.
  • Q: What certifications does the gas furnace have?
    • A: The gas furnace is design certified by CSA for application in Canada and the United States.
  • Q: How often should I clean or replace the air filters?
    • A: Air filters should be checked regularly and cleaned or replaced as needed. The frequency may vary depending on usage and environmental conditions.

Induced Draft – 96% AFUE
Input 60,000 – 115,000 Btuh

The high efficiency upflow gas furnace may be installed free standing in a utility room, basement, or enclosed in an alcove or closet. The extended flush jacket provides a pleasing “appliance appearance.” Design certified by CSA for application in Canada and the United States.

FEATURES AND BENEFITS

  • iSEERTM: Energy efficient brushless DC (ECM) motor can give up to 1 SEER point efficiency gain in cooling.
  • 100% Fired and Tested: All units and each component are tested on the manufacturing line.
  • Best Packaging in the Industry: Unique corner post design assures product will arrive to the homeowner dent free.
  • 30 Second Blower Delay: At start-up assures a warm duct temperature at furnace start-up. Adjustable blower off settings (60, 90, 120 and 180 seconds).
  • 30 Second Post Purge: Increases life of heat exchanger.
  • Hot Surface Igniter: Innovative application of a silicon nitride type igniter. Utilizes proven Smartlite® technology.
  • Color Coded Wire Harness: Designed to fit the components, all with quick-connect fittings for ease of service and replacement.
  • Flexible Category IV Venting System: May be vertically or horizontally vented using either a one-pipe or two-pipe system for maximum flexibility in installation.
  • High Static Blowers: All models equipped with high static ECM blowers, with 16 speeds for heating & cooling.
  • Low Boy Height: Easy to apply in low ceiling applications, works well with taller high SEER coils, easier to handle and install.
  • Heat Exchanger: Heavy gauge aluminized steel primary heat exchanger and stainless steel secondary heat exchanger assures a long life.
  • 90 Second Fixed Cooling Cycle Blower-Off Delay (TDR): Increases cooling performance when matched with a Nortek Global HVAC coil.
  • LP Convertible: Simple burner orifice and regulator spring change for ease of convertibility (as an accessory).
  • Diagnostic Lights: Dedicated light for flame signal strength and 2 lights in combination to indicate all other fault codes with easy to recognize states without counting0 flashes.
  • Integrated Control Boards: With connections for electronic air cleaner, humidifier, and dehumidification.
  • Two Piece Door Design: Enhances furnace appearance and uses captured screws to prevent losing door screws.
  • Blower Compartment: Sealed door to reduce air leakage and insulated for ultra quiet operation.
  • Sealed Vestibule: Reduces burner and inducer sound levels.
  • Two Stage Inducer: Optimizes efficiency on first stage heat and reduces sound levels.
  •  Furnace Air Leakage: These furnaces comply with Energy Star cabinet air leakage requirement of less than or equal to 2%. Keep the conditioned air flowing to where it’s needed.

LOCATION OF FURNACE COMPONENTS

UPFLOW FURNACE (*TE SERIES)

Literature-Library-FG7T-Two-Stage,-Variable-Speed,-Condensing-Upflow-and-Downflow-Gas-Furnaces-fig-1

DOWNFLOW FURNACE (*TN SERIES)

Literature-Library-FG7T-Two-Stage,-Variable-Speed,-Condensing-Upflow-and-Downflow-Gas-Furnaces-fig-2

DIMENSIONS

FG7TE 96% High Efficiency Upflow Series

Literature-Library-FG7T-Two-Stage,-Variable-Speed,-Condensing-Upflow-and-Downflow-Gas-Furnaces-fig-3

*TE Model #’s Dimension “A” Dimension “B” Dimension “C”
060D-VB1 17 1/2 15 7/8 16 1/8
080D-VC1 21 19 3/8 19 5/8
100D-VC1
115D-VD1 24 1/2 22 7/8 23 1/8

NOTE: Dimensions shown in inches

FG7TN 96% High Efficiency Downflow Series

Literature-Library-FG7T-Two-Stage,-Variable-Speed,-Condensing-Upflow-and-Downflow-Gas-Furnaces-fig-4

Literature-Library-FG7T-Two-Stage,-Variable-Speed,-Condensing-Upflow-and-Downflow-Gas-Furnaces-fig-7

NOTE: Dimensions shown in inches

BLOWER PERFORMANCE

BLOWER PERFORMANCE – FG7TE/TN

NOMINAL HEATING AIRFLOWS (CFM) AND TEMPERATURE RISE (°F)
 

 

 

 

 

“B” CABINET

RISE 30° F TO 60° F

SWITCH SETTINGS FOR HEAT (0 = OFF, 1 = ON) *TE/*TN – 060D – VB1 INPUT (BTU) 60,000
1 2 3 4 CFM TEMP RISE (° F)
1 0 0 0 1,000 53
1 0 0 1 1,100 48
1 0 1 0 1,200 44
1 0 1 1 1,300 41
1 1 0 0 1,400 38
1 1 0 1 1,500 35
1 1 1 0 1,600
1 1 1 1 1,700

 

 

 

 

 

 

“C” CABINET

RISE 35° F TO 65° F

SWITCH SETTINGS FOR HEAT (0 = OFF, 1 = ON) *TE/*TN – 080D – VC1 INPUT (BTU) 80,000 *TE/*TN – 100D – VC1 INPUT (BTU) 100,000
1 2 3 4 CFM TEMP RISE (° F) CFM TEMP RISE (° F)
# 0 0 0 1,000 1,000
# 0 0 1 1,115 63 1,115
# 0 1 0 1,230 57 1,230
# 0 1 1 1,345 52 1,345 65
# 1 0 0 1,460 48 1,460 60
# 1 0 1 1,575 45 1,575 56
# 1 1 0 1,690 42 1,690 52
# 1 1 1 1,805 39 1,805 49

 

 

 

 

 

 

“D” CABINET

RISE 40° F TO 70° F

SWITCH SETTINGS FOR HEAT (0 = OFF, 1 = ON) *TE/*TN – 115D – VD1 INPUT (BTU) 115,000
1 2 3 4 CFM TEMP RISE (° F)
# 0 0 0 1,500 68
# 0 0 1 1,615 63
# 0 1 0 1,730 59
# 0 1 1 1,845 55
# 1 0 0 1,960 52
# 1 0 1 2,075 49
# 1 1 0 2,190 46
# 1 1 1 2,305 44
  1. Two openings are recommended for airflows above 1,600 CFM if the filter(s) is (are) adjacent to the furnace.
  2. Temperature rises in the table are approximate. Actual temperature rises may vary.
  3. Temperature rises shaded in grey are for reference only. These conditions are not recommended.
  4. Rated static is .5″ ESP in W.C.

COOLING AIRFLOW

“B” CABINET
SWITCH SETTINGS (0 = OFF, 1 = ON)  

CFM

 

NOMINAL A/C & HP CAPACITy

HEAT COOL
1-4 5 6 7 8 LOW HIGH
1 0 0 0 0 470 700     2 TON  
1 0 0 0 1 510 760
1 0 0 1 0 550 820   2.5 TON
1 0 0 1 1 590 880
1 0 1 0 0 630 940  
1 0 1 0 1 670 1000
1 0 1 1 0 710 1060   3 TON
1 0 1 1 1 750 1120
1 1 0 0 0 790 1180  
1 1 0 0 1 830 1240 3.5 TON
1 1 0 1 0 870 1300
1 1 0 1 1 910 1360
1 1 1 0 0 950 1420  
1 1 1 0 1 990 1480
1 1 1 1 0 1030 1540
1 1 1 1 1 1070 1600

 

“C” CABINET
SWITCH SETTINGS (0 = OFF, 1 = ON)  

CFM

 

NOMINAL A/C & HP CAPACITy

HEAT COOL
1-4 5 6 7 8 LOW HIGH
# 0 0 0 0 685 1025     2.5 TON  
# 0 0 0 1 730 1090   3 TON
# 0 0 1 0 775 1155
# 0 0 1 1 815 1220  
# 0 1 0 0 860 1285   3.5 TON
# 0 1 0 1 905 1350  
# 0 1 1 0 950 1415   4 TON
# 0 1 1 1 990 1480
# 1 0 0 0 1035 1545  
# 1 0 0 1 1080 1610
# 1 0 1 0 1120 1675 5 TON
# 1 0 1 1 1165 1740
# 1 1 0 0 1210 1805
# 1 1 0 1 1255 1870  
# 1 1 1 0 1295 1935
# 1 1 1 1 1340 2000

# Switch not used – can be 0 or 1

“D” CABINET
SWITCH SETTINGS (0 = OFF, 1 = ON)  

CFM

 

NOMINAL A/C & HP CAPACITy

HEAT COOL
1-4 5 6 7 8 LOW HIGH
# 0 0 0 0 940 1400   3.5 TON  
# 0 0 0 1 965 1440   4 TON
# 0 0 1 0 990 1480
# 0 0 1 1 1020 1520
# 0 1 0 0 1045 1560  
# 0 1 0 1 1070 1600
# 0 1 1 0 1100 1640
# 0 1 1 1 1125 1680
# 1 0 0 0 1150 1720   5 TON
# 1 0 0 1 1180 1760
# 1 0 1 0 1205 1800
# 1 0 1 1 1235 1840  
# 1 1 0 0 1260 1880
# 1 1 0 1 1285 1920
# 1 1 1 0 1315 1960
# 1 1 1 1 1340 2000

# Switch not used – can be 0 or 1

VENTING

All models are approved for vertical non direct (1 pipe) and direct (2 pipe) venting applications. See Vent Table below for specified sizes and allowable lengths.

 

 

FURNACE MODELS (BTU)

 

 

FURNACE INSTALLATION

SINGLE PIPE LENGTH (FT.)

with 1 long radius elbow**

DIRECT VENT,

DUAL PIPE LENGTH (ft.) WITH

1 long radius elbow on each pipe**

OUTLET OUTLET INLET/OUTLET INLET/OUTLET
2” Diameter 3” Diameter 2” Diameter 3” Diameter
 

60,000

Upflow 90 90 60 90
Downflow 30 90 30 90
 
 

80,000

Upflow 40 90 40 90
Downflow 30 90 30 90
 
 

100,000

Upflow 30 90 30 90
Downflow 30 90 25 90
 
 

115,000

Upflow N/A 90 N/A 90
Downflow N/A 90 N/A 90

*NOTES

  1. Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3 inch long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Subtract 5ft for each 2” tee and 8ft for each 3” tee.
  2. Two 45 degree elbows are equivalent to one 90 degree elbow.
  3. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.

MODEL IDENTIFICATION CODE

Literature-Library-FG7T-Two-Stage,-Variable-Speed,-Condensing-Upflow-and-Downflow-Gas-Furnaces-fig-5

SPECIFICATIONS

FG7TE/TN MODELS NUMBERS:  

-060D-VB1

 

-080D-VC1

 

-100D-VC1

 

-115D-VD1

Input – Btuh (a) 60,000 / 39,000 80,000 / 52,000 100,000 / 65,000 115,000 / 74,750
Heating Capacity – Btuh 57,600 / 37,440 76,800 / 49,920 96,000 / 62,400 110,400 / 71,760
AFUE 96 96 96 96
Motor FLA 6.2 8.7 8.7 11.70
Rated Ext. SP – In. W.C. 0.5 0.5 0.5 0.5
Temperature Rise Range – ºF 30-60 35-65 35-65 40-70
Shipping Weights 125lbs 135lbs 145lbs 160lbs

Note: All models are 115V, 60 Hz. Gas Connections are 1/2″ N.P.T. AFUE = Annual Fuel Utilization Efficiency (a) Ratings to 2,000 ft. Over 2,000 ft. reduce 4% for each 1,000 ft. above sea level.

ACCESSORIES

FG7TE/TN KITS
Description SKU
2″ Concentric Vent Kit 904177
3″ Concentric Vent Kit 904176
2″ Concentric Vent Kit (Canadian Approved) 904952
3″ Concentric Vent Kit (Canadian Approved) 904953
“A” Cabinet Downflow Sub Base Kit 902974
“B”, “C”, “D” Cabinet Downflow Sub Base Kit 904911
2″ Side Wall Vent Kit 904617
3″ Side Wall Vent Kit 904347
U.S. LP Conversion Kit (0 to 10,000 ft.) 905028
Canada LP Conversion Kit (0 to 4,500 ft.) 905029
Bottom Return Filter 20 per Box, “B” Cabinet 904916
Bottom Return Filter 20 per Box, “D” Cabinet 904918
Side Return Filter Kit 541036
Neutralizer Kit 902377

LIMITED WARRANTY

GENERAL TERMS OF LIMITED WARRANTY

  • Nortek Global HVAC, LLC will furnish a replacement for any part of this product which fails in normal use and service within the terms and conditions of the warranty.
  • For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the Nortek Global HVAC, LLC warranty department for a copy.

Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (06/2017)

Literature-Library-FG7T-Two-Stage,-Variable-Speed,-Condensing-Upflow-and-Downflow-Gas-Furnaces-fig-6

Documents / Resources

Literature Library FG7T Two Stage, Variable Speed, Condensing Upflow and Downflow Gas Furnaces [pdf] Owner's Manual
FG7T Two Stage Variable Speed Condensing Upflow and Downflow Gas Furnaces, FG7T, Two Stage Variable Speed Condensing Upflow and Downflow Gas Furnaces, Condensing Upflow and Downflow Gas Furnaces, Upflow and Downflow Gas Furnaces, Downflow Gas Furnaces

References

Leave a comment

Your email address will not be published. Required fields are marked *