SENECA logoSENECA logo2
S311AK Analogue Panel Indicator with 4-Digit Display
Installation Guide
SENECA S311AK Analogue Panel Indicator with 4-Digit Display
MI00173-6-EN

MODULE LAYOUT

SENECA S311AK Analogue Panel Indicator with 4-Digit Display - MODULE LAYOUTWeight: 100 g;
Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.

DRILLING TEMPLATE

SENECA S311AK Analogue Panel Indicator with 4-Digit Display - DRILLING TEMPLATE

PRELIMINARY WARNINGS

The word WARNING preceded by the symbolWarning icon indicates conditions or actions that put the user’s safety at risk.
The word CAUTION preceded by the symbolWarning icon indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

warning 2 WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR-CODE shown on page 1.
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - icon The module must be repaired and damaged parts replaced by the Manufacturer.
The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
Dustbin Icon Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling).
The symbol on the product or its packaging shows the product must be surrendered to a collection center authorized to recycle electrical and electronic waste.

TECHNICAL SPECIFICATIONS

STANDARDS EN61000-6-4 Electromagnetic emissions, industrial environment.
EN61000-6-2 Electromagnetic immunity, industrial environment.
EN60950 Safety
INSULATION SENECA S311AK Analogue Panel Indicator with 4-Digit Display - input
POWER SUPPLY Voltage: 10 = 40 Vac, 19 ÷ 28 Vdc; max. absorption 0.9 W
ENVIRONMENTAL
CONDITIONS
Temperature: -10°C ÷ +65°C
Humidity: 30% ÷ 90% non condensing.
Storage temperature: -30°C = + 85°C
Altitude: up to 2000 m above sea level
ERRORS REFERRING TO THE MEASUREMENT RANGE FOR INPUT VOLTAGES AND CURRENTS
SOLUTION 16 bit 40000 points max
ACCURACY 0.05%
THERMAL
COEFFICIENT
0’005 %°K
LINEARITY
ERROR
0.05%
SENSOR
POWER SUPPLY
16V (Max 25mA)
CONNECTIONS 2-way removable screw terminals, 5.08 mm pitch (Supply) 3-way removable screw terminals, 5.08 mm pitch (Inputs)

INSTALLATION REGULATIONS

The module is designed to be panel-mounted. For optimal operation and duration, ensure adequate ventilation.
Avoid mounting modules over heat-generating equipment.

MENU PARAMETER MODIFICATION

The modification is done digit by digit. The digit to be modified flashes: in the figure, this digit is larger than the others.
The example diagram below refers to 4-digit indicators.

SENECA S311AK Analogue Panel Indicator with 4-Digit Display - icon2 Increases the value of the figure by one unit.
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - icon3 Decreases the value of the digit by one unit.
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - ok Confirms the value of the digit and moves to the next one. If the last digit: confirms the value of the digit and subsequent pressing returns to the parameter just set.

N.B.: Negative values:
The last digit allows entering even the “-” or the value “-1”.

Warning icon CAUTION
THE VALUES OF THE PARAMETERS ENTERED OUTSIDE THE RANGE ARE AUTOMATICALLY RESET WITHIN THE RANGE AND THEN DISPLAYED.

Example:
If parameter SENECA S311AK Analogue Panel Indicator with 4-Digit Display - icon4 is set with a value of 40.0 this will be automatically set to the maximum value which is 20.00.
The same applies to negative values.

PARAMETER CONFIGURATION EXAMPLE

You want to set the instrument to display a 0 ÷ 10 V voltage input with an activated filter:
Access the menu by pressing DOWN + MENU / OK for 3 seconds until the SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Default value10 menu appears;
Press the OK/MENU button and access the SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Default value10sub-menu and set:

SENECA S311AK Analogue Panel Indicator with 4-Digit Display - icon5Press the OK/MENU button and access the SENECA S311AK Analogue Panel Indicator with 4-Digit Display - icon6 sub-menu and set:
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - icon7

ELECTRICAL CONNECTIONS

POWER SUPPLY CURRENT INPUT VOLTAGE INPUT
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - POWER SUPPLY1 SENECA S311AK Analogue Panel Indicator with 4-Digit Display - POWER SUPPLY2With an external power supply from the sensor SENECA S311AK Analogue Panel Indicator with 4-Digit Display - POWER SUPPLY3
With an external power supply from the sensor
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - POWER SUPPLY4
With the power supply supplied by the instrument
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - POWER SUPPLY5With the power supply supplied by the instrument

ERROR TYPE

SENECA S311AK Analogue Panel Indicator with 4-Digit Display - value1 A)The value to be displayed is 3% higher than the SENECA S311AK Analogue Panel Indicator with 4-Digit Display p- value4parameter set.
B)The value to be displayed is higher than SENECA S311AK Analogue Panel Indicator with 4-Digit Display - value5
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - value2 A)The value to be displayed is 3% higher than the SENECA S311AK Analogue Panel Indicator with 4-Digit Display - value6parameter set.
B)The value to be displayed is higher thanSENECA S311AK Analogue Panel Indicator with 4-Digit Display - value7
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - value3 Quick transition from SENECA S311AK Analogue Panel Indicator with 4-Digit Display - value1 to SENECA S311AK Analogue Panel Indicator with 4-Digit Display - value2: overcurrent protection activated (input > 25mA).

MENU PARAMETER

PARAMETER FUNCTION SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER11 Default value
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER1 Password
enabling for
menu access
By setting a value other than 5477, the password will be requested
to access the menu (always 5477)
5477:
Password
disabled.
PARAMETER FUNCTION SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER12 Default value
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER2 Input type 1= Current
0= Voltage
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER18
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER Electrical Scale
Start
Start of scale in volts (voltage input) or in mA (current input).
It also defines the value of the input quantity associated with the
the minimum value is shown on the display (LO-d). Minimum settable
value 0 (current input), -10.00 (voltage input), maximum value
20.00 (current input), 10.00 (voltage input).
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Default value1
(mA)
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER4 Electrical full
scale
Full scale in volts (voltage input) or in mA (current input).
It also defines the value of the input quantity associated with the
maximum value shown on the display (HI-d). Minimum settable
value 0 (current input), -10.00 (voltage input), maximum value
20.00 (current input), 10.00 (voltage input).
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Default value2
(mA)
PARAMETER FUNCTION SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER15 Default value
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER5 Display full scale Integer values between a minimum of -1999 and a maximum of
9999
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Default value3
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER6 Start of the
display scale
Integer values between a minimum of -1999 and a maximum of
9999
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Default value4
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER7 Position of
decimal point
0= No decimal point
1= Decimal point on the 1 st  digit 000.0
2= Decimal point on the 2 nd digit 00.00 etc.
No decimal point
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER8 Filter level 0= No filter
1….5 = Filter activated with level 1 … 5
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Default value4
PARAMETER FUNCTION SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER16 Default value
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER9 Default settings 1 = Overwrites the set parameters with the default values and exits
the menu
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Default value4
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER10 Contrast 0…3= Adjusts the display contrast. SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER18
PARAMETER FUNCTION SENECA S311AK Analogue Panel Indicator with 4-Digit Display - PARAMETER17 Default value
Menu exit By confirming with OK \ MENU, all the set parameters are saved on the flash memory. The module can be used immediately with the new settings without the need for a reboot.

CONTACT INFORMATION

Technical support supporto@seneca.it Product information commerciale@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorized.
The content of this document corresponds to the described products and technologies.
Stated data may be modified or supplemented for technical and/or sales purposes.

SENECA S311AK Analogue Panel Indicator with 4-Digit Display - Back to

ACCESS TO THE PROGRAMMING MENU
SENECA S311AK Analogue Panel Indicator with 4-Digit Display - icob8 Press the two buttons simultaneously for a few seconds

SENECA S311AK Analogue Panel Indicator with 4-Digit Display - qr codewww.seneca.it/products/s311ak-4-l

CE SYMBOL SENECA s.r.l.
Via Austria, 26 – 35127 – PADOVA – ITALY
Tel. +39.049.8705355 – 8705359 – Fax +39.049.8706287
For manuals in other languages and the configuration software,
visit www.seneca.it/products/s311ak-4-l

Documents / Resources

SENECA S311AK Analogue Panel Indicator with 4-Digit Display [pdf] Installation Guide
S311AK Analogue Panel Indicator with 4-Digit Display, S311AK, Analogue Panel Indicator with 4-Digit Display, Analogue Panel Indicator, Panel Indicator, Indicator
SENECA S311AK Analogue Panel Indicator With 4 Digit Display [pdf] Instruction Manual
S311AK, S311AK-4-L, S311AK Analogue Panel Indicator With 4 Digit Display, S311AK, Analogue Panel Indicator With 4 Digit Display, Panel Indicator With 4 Digit Display, Digit Display, Display

References

Leave a comment

Your email address will not be published. Required fields are marked *