INSTALLATION MANUAL
S311AK
S311AK-4-L version
Analogue panel indicator with 4-digit display
EN

DOCUMENTATION

SENECA s.r.l.
Via Austria, 26 ­ 35127 ­ PADOVA ­ ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287 For manuals in other languages and the configuration software,
visit www.seneca.it/products/s311ak-4-l

MI00173-6-EN

1/6

MODULE LAYOUT

22mm 15mm

96mm

40mm

Weight: 100 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.
DRILLING TEMPLATE

45 mm
92 mm
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user's safety at risk. The word CAUTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR-CODE shown on page 1.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation. Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.
2/6

TECHNICAL SPECIFICATIONS
EN61000-6-4 Electromagnetic emissions, industrial environment. STANDARDS EN61000-6-2 Electromagnetic immunity, industrial environment.
EN60950 Safety

INSULATION

Input

Display

Power Supply

1500 Vac

POWER SUPPLY Voltage: 10 ÷ 40 Vac, 19 ÷ 28 Vdc; max. absorption 0.9 W

Temperature:

-10°C ÷ +65°C

ENVIRONMENTAL Humidity:

30% ÷ 90% non condensing.

CONDITIONS Storage temperature: -30°C ÷ + 85°C

Altitude:

up to 2000 m above sea level

ERRORS REFERRING TO THE MEASUREMENT RANGE FOR INPUT VOLTAGES AND CURRENTS

SOLUTION 16 bit, 40000 points max

ACCURACY 0.05%

THERMAL COEFFICIENT
LINEARITY ERROR

0.005 %°K 0.05%

SENSOR POWER SUPPLY

16V (Max 25mA)

CONNECTIONS

2-way removable screw terminals, 5.08 mm pitch (Supply) 3-way removable screw terminals, 5.08 mm pitch (Inputs)

INSTALLATION REGULATIONS
The module is designed to be panel mounted. For optimal operation and duration, ensure adequate ventilation. Avoid mounting modules over heat-generating equipment.
MENU PARAMETER MODIFICATION
The modification is done digit by digit. The digit to be modified flashes: in the figure this digit is larger than the others. The example diagram below refers to 4-digit indicators.

Increases the value of the figure by one unit.

CAUTION

Decreases the value of the digit by one unit.
Confirms the value of the digit and moves to the next one. If last digit: confirms the value of the digit and subsequent pressing returns to the parameter just set.
N.B.: Negative values: The last digit allows to enter even the "-" or the value "-1".

THE VALUES OF THE PARAMETERS ENTERED OUTSIDE THE RANGE ARE AUTOMATICALLY RESET
WITHIN THE RANGE AND THEN DISPLAYED.
Example:
If parameter HI-E is set with a value of 40.0 this will be automatically set to the maximum value that is 20.00.
The same applies to negative values.

3/6

PARAMETER CONFIGURATION EXAMPLE

You want to set the instrument to display a 0 ÷ 10 V voltage input with activated filter:

Access the menu by pressing DOWN + MENU / OK for 3 seconds until the I.N.P.T menu appears;

Press the OK/MENU button and access the I.N.P.T sub-menu and set:

T.Y.P.E.=0.

L.O.-.E=00.00

H.I.-.E-=10.00

Press the OK/MENU button and access the S.C.A.L sub-menu and set:

L.O.-.E=0.

H.I.-.D.=1000.

D.P.-.D=2

F.I.L.T.=1

ELECTRICAL CONNECTIONS

POWER SUPPLY

CURRENT INPUT

VOLTAGE INPUT

10÷40Vdc 10÷28Vac 1W

0÷20mA

+ -10÷10V

With external power supply from sensor With external power supply from sensor

+ 0÷20mA

+ 0÷10V SSeiggnnaalle++
-

With power supply supplied by instrument With power supply supplied by instrument

ERROR TYPE

nnnn
UUUU NNNN UUUU

A) The value to be displayed is 3% higher than the HI-D parameter set. B) The value to be displayed is higher than 9999 A) The value to be displayed is 3% higher than the LO-D parameter set. B) The value to be displayed is higher than -1999
Quick transition from nnnn to UUUU: overcurrent protection activated (input > 25mA).

4/6

MENU PARAMETER

PARAMETER
PASS
PARAMETER
TYPE
LO-E
HI-E
PARAMETER
HI-D LO-d dp-d FILT
PARAMETER
dfLt CONT
PARAMETER

FUNCTION

C.O.N.F

Default value

Password enabling for menu access

By setting a value other than 5477, the password will be requested to access the menu (always 5477)

5477:
Password disabled.

FUNCTION

I.N.P.T

Default value

Input type

1= Current 0= Voltage

1

Electrical Scale Start
Electrical full scale

Start of scale in volts (voltage input) or in mA (current input). It also defines the value of the input quantity associated with the minimum value shown on the display (LO-d). Minimum settable value 0 (current input), -10.00 (voltage input), maximum value 20.00 (current input), 10.00 (voltage input).
Full scale in volts (voltage input) or in mA (current input). It also defines the value of the input quantity associated with the maximum value shown on the display (HI-d). Minimum settable value 0 (current input), -10.00 (voltage input), maximum value 20.00 (current input), 10.00 (voltage input).

4.00
(mA)
20.00
(mA)

FUNCTION

S.C.A.L.

Default value

Display full scale

Integer values between a minimum of -1999 and a maximum of 9999

1000

Start of the display scale Position of decimal point
Filter level FUNCTION Default settings
Contrast FUNCTION
Menu exit

Integer values between a minimum of -1999 and a maximum of 9999

0

0= No decimal point 1= Decimal point on the 1st digit 000.0 2= Decimal point on the 2nd digit 00.00 etc.
0= No filter 1....5 = Filter activated with level 1 ... 5

No decimal
point
0

s.y.s.

Default value

1 = Overwrites the set parameters with the default values and exits the menu

0

0...3= Adjusts the display contrast.

1

E.X.I.T

Default value

By confirming with OK \ MENU, all the set parameters are saved on the flash memory. The module can be used immediately with the new settings without the need for a reboot.

CONTACT INFORMATION

Technical support

supporto@seneca.it

Product information

commerciale@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.
5/6

Back to

rrn s
i (Sz)
[aM[omd[ifgy[g

[E]Mod[ifay[8
[rn-
(Z;ii(Sz)
fDMtrondBifyS
[]
rzsJb i
M[oOdEif]y[8

Modify
[rn-
fZS)ii(Sz)
fDMtrondBify
[B fZS)i
i(Sz)
M[oadEif]y
[]L
i
[aM[oOd[ifJy[E]

M[oad[ifJy[E]
[ [rn@[E]
fZS)i i(Sz)
Modify
[[][rn[@:E]

(oh
Exit th e menu and return to display

Back to

ACCESS TO THE PROGRAMMING MENU
(Sz) + u) Press the two buttons simultaneously for a few seconds

6/6

