BAC-9300A Series BACnet Unitary Controller
“
Product Information
Specifications
- Dimensions: A – 6.744 inches, B – 5.500 inches, C – 5.000
inches - Room Sensor Port
- Output Terminals
- 10/100 Ethernet Ports
- Power Terminals
- Power/Status LED
- Input Terminals
- NFC Target
- (Optional) Differential Air Pressure Port
Product Usage Instructions
Setup Choices using STE-9000 Series Digital Sensor
- Install the STE-9000 series digital sensor permanently as the
room sensor or use it temporarily as a technician’s service
tool. - Access simple menu-driven setup choices on the controller using
the sensor.
Quick Configuration using NFC
- Connect a smart phone, tablet, or computer with the KMC Connect
LiteTM app to the controller via NFC while the controller is
unpowered.
Configuration via Web Browser
- For Ethernet-enabled models, configure the controller by
connecting an HTML5-compatible web browser to the built-in
configuration web pages.
Custom Programming with KMC ConnectTM Software
- Customize and program the controllers using KMC ConnectTM
software and KMC ConvergeTM module for Niagara Workbench.
Creating Custom User-Interface
- Use KMC Converge and TotalControlTM software to create custom
graphical web pages hosted on a remote web server for a custom
user-interface for the controllers.
FAQ
What types of unitary equipment can the BAC-9300A Series
controllers be used with?
The controllers can be used with RTU, HPU, FCU, AHU, and
ventilator units. Some applications may require custom
programming.
How can I configure the controllers without power?
You can use NFC (Near Field Communication) from a smart device
with the KMC Connect LiteTM app to configure the controller even
when it is unpowered.
What options are available for custom programming of the
controllers?
The controllers are fully programmable, and custom configuration
and programming can be done using KMC ConnectTM software and KMC
ConvergeTM module for Niagara Workbench.
Can I create a custom user interface for the controllers?
Yes, you can use KMC Converge and TotalControlTM software to
create custom graphical web pages hosted on a remote web server as
a custom user-interface for the controllers.
“`
BAC-9300A Series
BACnet Unitary Controllers (B-BC)
DESCRIPTION
Do you find this document helpful? Click here to share feedback and help us improve:
KMC ConquestTM BAC-9300A series controllers are designed
Give Feedback
to operate unitary and terminal equipment. The integrated
(BAC-9301ACE
alarming, scheduling, and trending enable these BACnet
Shown)
Building Controllers to be powerful edge devices for the modern
smart building ecosystem.
The factory-supplied programming covers common unitary applications. The controllers feature simple, menu-driven setup choices using an STE-9000 series digital sensor, which can be installed permanently as the room sensor or used temporarily as a technician’s service tool.
Alternately, quick configuration of controller properties can be done using NFC (Near Field Communication) from a smart phone, tablet, or computer (using the KMC Connect LiteTM app) while the controller is unpowered.
The Ethernet-enabled BAC-93x1ACE models can also be configured by connecting an HTML5-compatible web browser to the built-in configuration web pages.
To meet the most demanding building automation custom requirements, these controllers are also fully programmable. Custom configuration and programming, with wizards for application programming selection/configuration, are enabled by KMC ConnectTM software and the KMC ConvergeTM module for Niagara Workbench.
KMC Converge and TotalControlTM software additionally provide the capability of creating custom graphical web pages (hosted on a remote web server) to use as a custom user-interface for the controllers.
MODELS
APPLICATIONS
Can be used with the following types of unitary equipment:
· Air handling units (AHU) · Chilled beams · Constant air volume (CAV) with external actuator · Fan coil units (FCU) · Heat pump units (HPU) · Roof top units (RTU) · Unit ventilators · Variable air volume (VAV) with external actuator
(Some applications require custom programming. See also Sample Installation on page 6.)
APPLICATIONS
INPUTS
OUTPUTS
RTU, HPU, FCU,
AHU, and unit
1 opt. air pressure
ventilator
sensor and 8 (total)
VAV/CAV (with
external tri-state actuator), RTU/
HPU static pressure monitoring/control
standard:
· 2 analog (temp. sensor port)
· 6 universal inputs (software configurable as analog, binary, or accumulator
10 total:
· 6 triacs (binary) · 4 universal
(software configurable as analog or binary)
on terminals)
FEATURES
Air Pressure Real Time Sensor (Input) Clock (RTC)
Ethernet Port
MS/TP Port
MODEL
BAC-9301A
BAC-9301AC
BAC-9301ACE
BAC-9311A BAC-9311AC
BAC-9311ACE
KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 / 877-444-5622 / Fax: 574-831-5252 / www.kmccontrols.com
SPECIFICATIONS
A
B C
E F
D
A 6.744 inches B 5.500 inches C 5.000 inches
DIMENSIONS
171 mm D 6.000 inches 140 mm E 1.500 inches 127 mm F 6.279 inches
152 mm 38 mm 159 mm
Room Sensor Port
Output Terminals
10/100 Ethernet Ports
Power Terminals
Power/Status LED
Input Terminals
NFC Target
(Optional) Differential
Air Pressure
Port
TERMINAL COLOR CODE
Black 24 VAC/VDC Power Green Inputs and Outputs
Inputs and Outputs
Inputs, Universal (6 on Terminal Blocks)
Universal inputs Termination
Resolution
Configurable as analog, binary, or accumulator objects
1K and 10K ohm sensors, 012 VDC, or 020 mA (without need for an external resistor)
16-bit analog-to-digital conversion
Protection Wire size
Overvoltage protection (24 VAC, continuous)
1224 AWG, copper, in removable screw terminal blocks
Input, Dedicated Room Sensor Port
Connector Cable
Modular connector for STE-9xx1 series digital wall sensors or STE6010/6014/6017 analog temperature sensors
Uses standard Ethernet patch cable up to 150 feet (45 meters)
Outputs, Universal (4 on Terminal Blocks)
Universal outputs Power/protection
Resolution Wire size
Configurable as an analog (0 to 12 VDC) or binary object (0 or 12 VDC, on/off)
Each short-circuit protected universal output capable of driving up to 100 mA (at 012 VDC) or 100 mA total for all outputs
12-bit digital-to-analog conversion
1224 AWG, copper, in removable screw terminal blocks
Outputs, Triac (6 Binary)
Triac outputs Power
Optically isolated zero-crossing triac output configured as a binary object
Maximum switching 24 VAC at 1.0 A for each output; maximum total for controller is 3.0 A
Wire size
1224 AWG, copper, in removable screw terminal blocks
Input, Integrated Air Pressure Sensor (BAC-9311ACE)
D pressure range Sensor accuracy
Connections
0 to 2″ wc (0 to 500 Pa)
±4.5% of the reading or (when near zero) 0.0008″ wc (0.2 Pa), whichever is greater (@ 25° C); internally linearized and temperature compensated
Barbed for 1/4 inch FR (Flame Retardant) tubing
2
Feedback? Give yours here.
Communication Ports
Configurability
MS/TP (optional)
Ethernet (optional) NFC Room sensor
One EIA-485 port (removable terminal block) for BACnet MS/TP, operating at 9.6, 19.2, 38.4, 57.6, 76.8, or 115.2 kilobaud; max. length of up to 4,000 feet (1,200 meters) of 18 AWG shielded, twisted-pair, no more than 51 pf/ft (167 pf/m); use repeaters for longer distances
Two 10/100BaseT Ethernet connectors for BACnet IP, Foreign Device, and Ethernet 802.3 (ISO 8802-3); segmentation supported; up to 328 ft (100 m) between controllers (using T568B Category 5 or better cable)
NFC (Near Field Communication) up to 1 inch (2.54 cm) from the top of the enclosure
Modular STE connection jack for STE-9000 series digital sensors and STE-6010/6014/6017 analog sensors
OBJECTS*
Inputs and Outputs
Analog, binary, or accumulator input
Analog or binary output Values Analog value Binary value Multi-state value Program and Control Program (Control Basic) PID loop Schedules Schedule Calendar
MAXIMUM #
8 for
9 for
BAC-9301 BAC-9311
10
120 80 40
10 10
2 1
Logs
Trend log
20
Trend log multiple (must be created)
4 (default 0)
Alarms and Events
Notification class
5
Event enrollment
40
Tables
Input tables
20
Control Basic tables
20
*Configuration allows creation and deletion of objects (maximum number of objects shown). The number and configuration of default objects depends on the selected application. For lists of default objects, see the KMC Conquest Controller Application Guide. See also the PIC statement for all supported BACnet objects.
3
Feedback? Give yours here.
Configuring, Programming, and Designing Installation
SETUP PROCESS
Config- Programming Web Page uration (Control Basic) Graphics*
KMC CONTROLS TOOL
Conquest NetSensor
Internal configuration
web pages in Conquest
Ethernet “E” models**
KMC Connect LiteTM (NFC) app***
KMC ConnectTM software
**** ****
TotalControlTM software
KMC ConvergeTM module for Niagara WorkBench
KMC Converge GFX
module for Niagara
WorkBench
Power Supply voltage
Required power Wire size
24 VAC (50/60 Hz) or 24 VDC; 15%, +20%; Class 2 only; non-supervised (all circuits, including supply voltage, are power limited circuits)
8 VA, plus external loads
1224 AWG, copper, in a removable screw terminal block
Enclosure and Mounting
Weight Case material
Mounting
14 ounces (0.4 kg)
Green and black flame retardant plastic
Direct mounting to panels or on DIN rails
Environmental Limits
Operating
32 to 120° F (0 to 49° C)
*Custom graphical user-interface web pages can be hosted on a remote web server, but not in the controller.
**Conquest Ethernet-enabled “E” models with the latest firmware can be configured with an HTML5 compatible web browser from pages served from within the controller. For information, see the Conquest Ethernet Controller Configuration Web Pages Application Guide.
***Near Field Communication via enabled smart phone or tablet running the KMC Connect Lite app.
****Full configuration and programming of KMC Conquest controllers is supported starting with TotalControl ver. 4.0.
Shipping Humidity
40 to 160° F (40 to 71° C)
0 to 95% relative humidity (non-condensing)
Warranty, Protocol, and Approvals
Warranty KMC Limited Warranty 5 years (from mfg. date code)
BACnet Protocol
Hardware Features
Processor, Memory, and Clock
Standard Type
Meets or exceeds the specifications in ANSI/ASHRAE BACnet Standard 135-2010 for Building Controllers
BTL-certified as a B-BC controller type
Processor Memory
RTC
32-bit ARM® Cortex-M4
Programs and configuration parameters are stored in nonvolatile memory; auto restart on power failure
Real time clock with (capacitor) power backup for 72 hours (“C” model only) for network time synchronization or full stand-alone operation
Indicators and Isolation
Regulatory Approvals
UL
BTL
RoHS 2 FCC
UL 916 Energy Management Equipment listed
BACnet Testing Laboratory listed as Building Controller (B-BC) (pending)
RoHS 2 compliant
FCC Class A, Part 15, Subpart B and complies with Canadian ICES-003 Class A*
LED indicators
Power/status and Ethernet status
*This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept
4
Feedback? Give yours here.
any interference received, including interference that may cause Network Communications
undesired operation. (NFC operation meets FCC compliance while the controller is in an unpowered state.)
BAC-5051AE
BACnet router with single MS/TP and IP/Ethernet ports
ACCESSORIES
NOTE: For accessory details, see the respective product data sheets and installation guides.
HPO-0055
HPO-5551 HPO-9003 HSO-9001
Replacement network bulb assembly (pack of 5) Router technician cable kit NFC Bluetooth/USB module (fob) Ethernet patch cable, 50 feet
Actuators
HSO-9011
Ethernet patch cable, 50 feet, plenum rated
NOTE: See also the selection chart in the Connecting a Remote Actuator to a BAC-9311A section of the KMC Conquest Controller Application Guide.
HSO-9012
Ethernet patch cable, 75 feet, plenum rated
MEP-4xxx MEP-7xxx
Actuators, 25 to 90 in-lb., fail-safe and non-fail-safe
Actuators, 180 and 320 in-lb., failsafe and non-fail-safe
Differential Air Pressure Sensors
SSS-1012 SSS-1013 SSS-1014
Sensor, 3-5/32 inches (80 mm) length Sensor, 5-13/32 in. (137 mm) length Sensor, 7-21/32 in. (194 mm) length
SSS-1015
Sensor, 9-29/32 in. (252 mm) length
Room Sensors, Analog
STE-6010W10
Temperature sensor, white
STE-6014W10
Sensor with rotary setpoint dial, white
STE-6017W10
Sensor with rotary setpoint dial and override button, white
HPO-9005
Room sensor adapter allows the use of other sensors and optional setpoint potentiometers (with wire leads or terminal blocks) to be used instead of STE-601x sensor models with modular jacks
Miscellaneous Hardware
HCO-1103 HCO-1035 HCO-1036
Steel control enclosure with DIN rail mounting, 10 x 7.5 x 2.5 inches (257 x 67 x 193 mm)
Steel control enclosure, 20 x 24 x 6 inches (508 x 610 x 152 mm)*
Steel control enclosure, 24 x 36 x 6 inches (610 x 914 x 152 mm)*
SP-001 HPO-9901
Screwdriver (KMC branded) with a hex end (for NetSensor cover screws) and a flat blade end (for controller terminals)
Controller replacement parts kit with terminal blocks (1 gray, 1 black, 2 green 3-terminal, 4 green 4-terminal, 2 green 5-terminal, 2 green 6-terminal) and DIN clips (2 small for router and 1 large for controllers)
*NOTE: For smoke control applications, the controller must be mounted in a UL Listed FSCS enclosure or listed enclosure with minimum dimensions. The HCO-1035 and HCO-1036 are approved for such applications.
NOTE:
Other STE-6000 series sensors are not fully compatible with the dedicated sensor port. However, various other models can be used with an HPO-9005 adapter or with the controller screw terminals. See the STE-6000 series data sheet for more information. For digital sensor information, see the STE-9000 series.
NOTE:
To order the STE-601x sensor with light almond color instead of white, drop the W on the end of the model number (e.g., STE-6010W is white and STE-6010 is light almond).
Room Sensors, Digital (LCD Display)
STE-9000 Series HPO-9001
KMC Conquest NetSensor digital room temperature sensors for viewing, configuring, and optional humidity, occupancy, and CO2 sensing
NetSensor distribution module
Sensors, Miscellaneous
STE-1405
DAT sensor with plenum-rated cable
STE-1451
OAT sensor
5
Feedback? Give yours here.
Transformers, 120 to 24 VAC
XEE-6111-050
50 VA, single-hub
XEE-6112-050
50 VA, dual-hub
XEE-6112-100
96 VA, dual-hub (approved for smoke control applications)
SAMPLE INSTALLATION
Communication with Other Network Devices and Remote Monitoring
Configuration via NFC-Enabled
Smart Phone
Air Pressure Sensor (BAC-9311ACE)
Up to 6 Sensors (to terminal blocks)
STE-9xx1 NetSensor (to modular connector)
4 Universal and 6 Triac Outputs
BAC-5051AE Router
Quick (temporary) Network Access Through
Computer Data Port
For more information about installation and operation, see:
· BAC-9300 Series Controller Installation Guide · KMC Conquest Controller Application Guide · KMC Conquest Wiring: BAC-9300 Series Controllers (Video) · Smoke Control Manual for KMC Conquest Systems
WE VALUE YOUR FEEDBACK!
Help us improve this document.
Click here to take a 3-minute survey.
Your input helps us make our documents clearer and more useful.
SUPPORT
Additional resources for installation, configuration, application, operation, programming, upgrading, and much more are available on the web at www.kmccontrols.com. Log-in to see all available files.
© 2025 KMC Controls, Inc.
Specifications and design are6subject to change without notice
925-035-08D