Danfoss AK-HS 1000 Temperature Sensor Installation Guide
Mounting
![]() |
|
![]() For controllers with non-galvanic separated power supply |
![]() |
Calibration
In order to achieve an accuracy better than ±1 K of the temperature controlled, the accuracy of the sensor and the connecting cables must be better than ±0.6 K.
The cable resistance expressed in Kelvin can be calculated by using the formula below:
R = Cable resistance expressed in Kelvin
ρ = Specific resistance of the material [Ω/m/mm²]
L = The length of the wire [in m there and back]
q = Cross-section of the wire [mm2]
Example:
ρ = 0.018
L = 10 m x 2 = 20 m
q = 0.75 mm2
Pt 1000 ohm / 0 °C
°C | ohm | °C | ohm |
0 | 1000.0 | 0 | 1000.0 |
1 | 1003.9 | -1 | 996.1 |
2 | 1007.8 | -2 | 992.2 |
3 | 1011.7 | -3 | 988.3 |
4 | 1015.6 | -4 | 984.4 |
5 | 1019.5 | -5 | 980.4 |
6 | 1023.4 | -6 | 976.5 |
7 | 1027.3 | -7 | 972.6 |
8 | 1031.2 | -8 | 968.7 |
9 | 1035.1 | -9 | 964.8 |
10 | 1039.0 | -10 | 960.9 |
11 | 1042.9 | -11 | 956.9 |
12 | 1046.8 | -12 | 953.0 |
13 | 1050.7 | -13 | 949.1 |
14 | 1054.6 | -14 | 945.2 |
15 | 1058.5 | -15 | 941.2 |
16 | 1062.4 | -16 | 937.3 |
17 | 1066.3 | -17 | 933.4 |
18 | 1070.2 | -18 | 929.5 |
19 | 1074.0 | -19 | 925.5 |
20 | 1077.9 | -20 | 921.6 |
21 | 1081.8 | -21 | 917.7 |
22 | 1085.7 | -22 | 913.7 |
23 | 1089.6 | -23 | 909.8 |
24 | 1093.5 | -24 | 905.9 |
25 | 1097.3 | -25 | 901.9 |
26 | 1101.2 | -26 | 898.0 |
27 | 1105.1 | -27 | 894.0 |
28 | 1109.0 | -28 | 890.1 |
29 | 1112.8 | -29 | 886.2 |
30 | 1116.7 | -30 | 882.2 |
35 | 1136.1 | ||
40 | 1155.4 | ||
45 | 1174.7 | ||
50 | 1193.9 |
CERTIFICATE OF PERFORMANCE
It is herewith approved that AK-HS 1000 product sensors for temperature logging in combination with the HACCP corticated ADAP-KOOL® controllers comply with EN 13485 in respect to temperature monitoring according to the EC regulation. 2005/37/EC.
Name and Address of Manufacturer within the European Community
Danfoss A/S
Nordborgvej 81
DK 6430 Nord borg
Denmark
Description of Equipment
Product Temperature sensor for refrigerated cabinets and cold rooms requiring monitoring for HACCP documentation and alarm.
Technical Summary
Temperature Range: -30 °C to +20 °C
Accuracy: +/- 0,3 °C at 0 °C and +/- 0,005 °C x temp
Time Constant: T90 = 3–15 mins.
Sensor Type: Platinum-based sensors, Pt-1000 Ohm according to EN 60751 Class B
Cable Connection: AK temperature sensors are two-wire devices, (Cable: 2 x 0.22 ~ 1.5 mm2). All connections are interchangeable
Enclosure: IP54 [Materials: Cover: ABS / Base: Polycarbonate (PC)] thereby protecting the sensor against heat radiation from external ambient
Nordborg 2014-11-20
______________
Place and date of issue
Thomas Matzen n
______________
Production Quality Manager r
To be completed by Installer/Contractor for site HACCP Manager Reference and Documentation
This AK-HS 1000 has been applied to the following application:
Location Name/Address: _______________________
Cabinet / Cold Room Reference: _________________
Installer / Contractor Name: ____________________
Signed: ____________
Date: _____/_____/_______