Danfoss BD350GH 24V

Temperature Sensor 105N9611 for
BD350GH Electronic Unit 24V

Product Information

Specifications

  • Model: ICAD 600A/ICAD 1200A
  • Voltage: 24 Volt DC
  • Maximum Torque: 3 Nm
  • Power Supply: 19 V DC Battery/UPS

Product Usage Instructions

Installation

Ensure all 3 screws are cross-tightened to achieve equal
tightening with a maximum torque of 3 Nm.

Terminal Box Connection

Connect the terminal box following the color codes provided:

  • A – Black
  • B – Brown
  • C – Red
  • D – Orange
  • E – Yellow
  • F – Green
  • G – Blue

Voltage Drop Consideration

Observe the voltage drop between the DC transformer and the ICAD
terminal box. Use the specified cables and transformer to maintain
voltage within the required range based on cable length.

Programming the ICAD

To program the ICAD, follow these steps:

  1. Hold down for 2 seconds to enter programming mode.
  2. Navigate through parameters using the designated keys.
  3. Select the appropriate settings for valve size and input
    signals.
  4. Exit programming mode by holding down for 2 seconds.

FAQ

How do I reset the ICAD to factory settings?

To perform a factory reset, disconnect power, press and hold
specific buttons while reconnecting power, then release the
buttons. The ICAD will start flashing A1 in the display to indicate
a successful reset.

“`

027R9801 027R9801

Installation Guide
ICAD 600A/ICAD 1200A Quick Start Guide
1

Grease

Note! Cross tighten all 3 screws to ensure equal tightening. Max 3 Nm torque.

Quick Start Guide Before you
start using ICAD:
24 Volt DC ONLY
2
Terminal box not supplied by Danfoss

© Danfoss | DCS (ms) | 2020.01

Ref. Colour

Description

A Black

­ Common Alarm

3

B Brown

­ ICM fully open

C Red

­ ICM fully closed

D Orange

­ GND ground

E Yellow

+ 0/4 ­ 20 mA Input

F Green

+

0/2 ­ 10 V input or digital input for on/off control

G Blue

+ 0/4 ­ 20 mA Output

I Black

+

Fail safe supply Battery / UPS* 19 V DC

II White III Brown

+ Supply voltage ­ 24 V DC

* Uninterruptable Power Supply

24 Volt DC ONLY

Please observe cable voltage drop Distance between the applied DC transformer and the ICAD terminal box may cause a voltage drop. Cross section of cables and size of DC transformer must be calculated so that the voltage at all time at the ICAD terminal box*, both during standstill and during operation of ICAD, is within this range:

Prefabricated ICAD cable 1.5 m

3 m

10 m

15 m

length Code number

027H0426 027H0438 027H0427 027H0435

Voltage ICAD terminal Min.

21

22

23

24

(600A/1200A) [V DC] Max.

26.4

* Do not measure inside the ICAD itself

AN213086423355en-000501 | 1

Programming the ICAD

Note:

If the keypad is not operated within

Valve size setup (mandatory)

20 seconds; time out will automatically

exit programming mode.

Decrease

value

Edit / Enter

Increase value

When powering up the ICAD, A1 will flash in the display

4

; 01

; 10

11

; 26

Hold down for 2 seconds to enter programming mode

Press and go to parameter 10.
Press

Press until

Press until

you reach 11 (password). you reach parameter 26

Press

Press

1: ICM 20 with ICAD 600A 6: ICM 65 with ICAD 1200A

0

2: ICM 25 with ICAD 600A 3: ICM 32 with ICAD 600A

7: ICM 100 with ICAD 1200A 8: ICM 125 with ICAD 1200A

; 26

4: ICM 40 with ICAD 1200A 9: ICM 150 with ICAD 1200A

5: ICM 50 with ICAD 1200A 10: CVE pilot with ICAD 1200A

CA

Press or to select ICM size or CVE.
Press

Valve label ID: ICM 20

ICM 25-65

ICM 100-150

ICM/CVE & ICAD is now calibrating

Hold down for 2 seconds to exit programming mode

NOTE ! If media temperature is lower than -30 °C (-22 °F) it is mandatory to set parameter i30 an i31. See separate document attached in ICAD box: document number AN285243155312

Changing analogue input signal (optional)

5

; 01

; 03

2

Hold down for 2 seconds to enter programming mode

Press until you reach parameter 03.
Press

Press or to select analogue input signal

1: 0 ­ 20 mA 2: 4 ­ 20 mA* 3: 0 ­ 10 V 4: 2 ­ 10 V
* default factory setting

; 03
Press

; 03

A3

Hold down for 2 seconds to exit programming mode

If A3 alarm occurs the analogue input signal is out of range

For further functions,

24 Volt DC

programming possibilities and factory settings;

ONLY please see ICAD instruction.

2 | AN213086423355en-000501

Factory reset of ICAD
Disconnect power
Press down and simultaneously while reconnecting power
Release and
Note:
If factory reset has been performed the ICAD will start flashing A1 in the display.
© Danfoss | DCS (ms) | 2020.01

Temperature Sensor Instructions