Danfoss BD350GH 24V
Temperature Sensor 105N9611 for
BD350GH Electronic Unit 24V
“
Product Information
Specifications
- Model: ICAD 600A/ICAD 1200A
- Voltage: 24 Volt DC
- Maximum Torque: 3 Nm
- Power Supply: 19 V DC Battery/UPS
Product Usage Instructions
Installation
Ensure all 3 screws are cross-tightened to achieve equal
tightening with a maximum torque of 3 Nm.
Terminal Box Connection
Connect the terminal box following the color codes provided:
- A – Black
- B – Brown
- C – Red
- D – Orange
- E – Yellow
- F – Green
- G – Blue
Voltage Drop Consideration
Observe the voltage drop between the DC transformer and the ICAD
terminal box. Use the specified cables and transformer to maintain
voltage within the required range based on cable length.
Programming the ICAD
To program the ICAD, follow these steps:
- Hold down for 2 seconds to enter programming mode.
- Navigate through parameters using the designated keys.
- Select the appropriate settings for valve size and input
signals. - Exit programming mode by holding down for 2 seconds.
FAQ
How do I reset the ICAD to factory settings?
To perform a factory reset, disconnect power, press and hold
specific buttons while reconnecting power, then release the
buttons. The ICAD will start flashing A1 in the display to indicate
a successful reset.
“`
027R9801 027R9801
Installation Guide
ICAD 600A/ICAD 1200A Quick Start Guide
1
Grease
Note! Cross tighten all 3 screws to ensure equal tightening. Max 3 Nm torque.
Quick Start Guide Before you
start using ICAD:
24 Volt DC ONLY
2
Terminal box not supplied by Danfoss
© Danfoss | DCS (ms) | 2020.01
Ref. Colour
Description
A Black
Common Alarm
3
B Brown
ICM fully open
C Red
ICM fully closed
D Orange
GND ground
E Yellow
+ 0/4 20 mA Input
F Green
+
0/2 10 V input or digital input for on/off control
G Blue
+ 0/4 20 mA Output
I Black
+
Fail safe supply Battery / UPS* 19 V DC
II White III Brown
+ Supply voltage 24 V DC
* Uninterruptable Power Supply
24 Volt DC ONLY
Please observe cable voltage drop Distance between the applied DC transformer and the ICAD terminal box may cause a voltage drop. Cross section of cables and size of DC transformer must be calculated so that the voltage at all time at the ICAD terminal box*, both during standstill and during operation of ICAD, is within this range:
Prefabricated ICAD cable 1.5 m
3 m
10 m
15 m
length Code number
027H0426 027H0438 027H0427 027H0435
Voltage ICAD terminal Min.
21
22
23
24
(600A/1200A) [V DC] Max.
26.4
* Do not measure inside the ICAD itself
AN213086423355en-000501 | 1
Programming the ICAD
Note:
If the keypad is not operated within
Valve size setup (mandatory)
20 seconds; time out will automatically
exit programming mode.
Decrease
value
Edit / Enter
Increase value
When powering up the ICAD, A1 will flash in the display
4
; 01
; 10
11
; 26
Hold down for 2 seconds to enter programming mode
Press and go to parameter 10.
Press
Press until
Press until
you reach 11 (password). you reach parameter 26
Press
Press
1: ICM 20 with ICAD 600A 6: ICM 65 with ICAD 1200A
0
2: ICM 25 with ICAD 600A 3: ICM 32 with ICAD 600A
7: ICM 100 with ICAD 1200A 8: ICM 125 with ICAD 1200A
; 26
4: ICM 40 with ICAD 1200A 9: ICM 150 with ICAD 1200A
5: ICM 50 with ICAD 1200A 10: CVE pilot with ICAD 1200A
CA
Press or to select ICM size or CVE.
Press
Valve label ID: ICM 20
ICM 25-65
ICM 100-150
ICM/CVE & ICAD is now calibrating
Hold down for 2 seconds to exit programming mode
NOTE ! If media temperature is lower than -30 °C (-22 °F) it is mandatory to set parameter i30 an i31. See separate document attached in ICAD box: document number AN285243155312
Changing analogue input signal (optional)
5
; 01
; 03
2
Hold down for 2 seconds to enter programming mode
Press until you reach parameter 03.
Press
Press or to select analogue input signal
1: 0 20 mA 2: 4 20 mA* 3: 0 10 V 4: 2 10 V
* default factory setting
; 03
Press
; 03
A3
Hold down for 2 seconds to exit programming mode
If A3 alarm occurs the analogue input signal is out of range
For further functions,
24 Volt DC
programming possibilities and factory settings;
ONLY please see ICAD instruction.
2 | AN213086423355en-000501
Factory reset of ICAD
Disconnect power
Press down and simultaneously while reconnecting power
Release and
Note:
If factory reset has been performed the ICAD will start flashing A1 in the display.
© Danfoss | DCS (ms) | 2020.01