The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document. All examples in this document are only intended to improve understanding of the functionality and handling of the equipment. Beijer Electronics AB cannot assume any liability if these examples are used in real applications. In view of the wide range of applications for this software, users must acquire sufficient knowledge themselves in order to ensure that it is correctly used in their specific application. Persons responsible for the application and the equipment must themselves ensure that each application is in compliance with all relevant requirements, standards, and legislation in respect to configuration and safety. Beijer Electronics AB will accept no liability for any damage incurred during the installation or use of equipment mentioned in this document. BeijerElectronics AB prohibits all modification, changes, or conversion of the equipment.
Head Office
Beijer Electronics AB
Box 426
201 24 Malmö, Sweden
www.beijerelectronics.com / +46 40 358600
About This Manual
This manual contains information on the software and hardware features of the Beijer Electronics GT-122F Digital Input Module. It provides in-depth specifications and guidance on installation, setup, and usage of the product.
Symbols Used in This Manual
This publication includes Warning, Caution, Note and Important icons where appropriate to point out safety-related or other important information. The corresponding symbols should be interpreted as follows:
Safety
Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions! In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product.The images, examples and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.
Product Certifications
The product has the following product certifications.
General Safety Requirements
WARNING
- Do not assemble the products and wires with power connected to the system. Doing so cause an “arc flash”, which can result in unexpected dangerous events (burns, fire, flying objects, blast pressure, sound blast, heat).
- Do not touch terminal blocks or IO modules when the system is running. Doing so may cause electric shock, short circuit or malfunction of the device.
- Never let external metallic objects touch the product when the system is running.Doing so may cause electric shock, short circuit or malfunction of the device.
- Do not place the product near inflammable material. Doing so may cause a fire.
- All wiring work should be performed by an electrical engineer.
- When handling the modules, ensure that all persons, the workplace and the packing are well grounded. Avoid touching conductive components, the modules contain electronic components that may be destroyed by electrostatic discharge.
CAUTION
- Never use the product in environments with temperatures over 60℃. Avoid placing the product in direct sunlight.
- Never use the product in environments with over 90% humidity.
- Always use the product in environments with pollution degree 1 or 2.
- Use standard cables for wiring.
About the G-series System
System overview
- Network Adapter Module – The network adapter module forms the link between the field bus and the field devices with the expansion modules. The connection to different field bus systems can be established by each of the corresponding network adapter module, e.g., for MODBUS TCP, Ethernet IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial etc.
- Expansion Module – Expansion module types: Digital IO, Analog IO, and Special modules.
- Messaging – The system uses two types of messaging: Service messaging and IO messaging.
IO Process Data Mapping
An expansion module has three types of data: IO data, configuration parameter, and memory register.The data exchange between the network adapter and the expansion modules is made via IO process image data by internal protocol.
Data flow between network adapter (63 slots) and expansion modules
The input and output image data depend on the slot position and the data type of the expansion slot. The ordering of input and output process image data is based on the expansion slot position. Calculations for this arrangement are included in the manuals for network adapter and programmable IO modules. Valid parameter data depends on the modules in use. For example, analog modules have settings of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module provides a description of the parameter data.
Specifications
Environmental Specifications
Operating temperature | -20°C – 60°C |
UL temperature | -20°C – 60°C |
Storage temperature | -40°C – 85°C |
Relative humidity | 5% – 90% non-condensing |
Mounting | DIN rail |
Shock operating | IEC 60068-2-27 (15G) |
Vibration resistance | IEC 60068-2-6 (4 g) |
Industrial emissions | EN 61000-6-4: 2019 |
Industrial immunity | EN 61000-6-2: 2019 |
Installation position | Vertical and horizontal |
Product certifications | CE, FCC, UL, cUL |
General Specifications
Power dissipation | Max. 50 mA @ 5 VDC |
Isolation | I/O to logic: Photocoupler isolation |
UL field power | Supply voltage: 24 VDC nominal, class 2 |
Field power | Supply voltage: 24 VDC nominal Voltage range: 15 – 30 VDC
Power dissipation: 0 mA @ 24 VDC |
Wiring | Connector type, up to AWG22
Module connector: HIF3BA-20D-2.54DSA |
Weight | 52 g |
Module size | 12 mm x 99 mm x 70 mm |
Dimensions
Module dimensions (mm)
Input Specifications
Inputs per module | 16 points, source type |
Indicators | 16 green input status |
On-state voltage | 24 VDC nominal
15 – 30 VDC @ 60 ℃ |
On-state current | 2.25 mA @ 24 VDC
3 mA @ 30 VDC |
Off-state voltage | 9.3 VDC @ 25 ℃ |
Input signal delay | OFF to ON: Max. 0.3 ms
ON to OFF: Max. 0.3 ms |
Input filter | Adjustable, up to 10 ms |
Nominal input impedance | 10.2 kΩ typical |
Common type | 16 points / 2 COM (universal) |
Wiring Diagram
Pin no. | Signal description |
1 | Input channel 0 |
2 | Input channel 1 |
3 | Input channel 2 |
4 | Input channel 3 |
5 | Input channel 4 |
6 | Input channel 5 |
7 | Input channel 6 |
8 | Input channel 7 |
9 | Input channel 8 |
10 | Input channel 9 |
11 | Input channel 10 |
12 | Input channel 11 |
13 | Input channel 12 |
14 | Input channel 13 |
15 | Input channel 14 |
16 | Input channel 15 |
17 | Field power 0 V |
18 | Field power 0 V |
19 | Common (field power 24 V) |
20 | Common (field power 24 V) |
LED Indicator
LED no. | LED function / description | LED color |
0 | INPUT channel 0 | Green |
1 | INPUT channel 1 | |
2 | INPUT channel 2 | |
3 | INPUT channel 3 | |
4 | INPUT channel 4 | |
5 | INPUT channel 5 | |
6 | INPUT channel 6 | |
7 | INPUT channel 7 | |
8 | INPUT channel 8 | |
9 | INPUT channel 9 | |
10 | INPUT channel 10 | |
11 | INPUT channel 11 | |
12 | INPUT channel 12 | |
13 | INPUT channel 13 | |
14 | INPUT channel 14 | |
15 | INPUT channel 15 |
LED Channel Status
Status | LED | Indication |
No signal | Off | Normal operation |
On signal | Green | Normal operation |
Mapping Data Into the Image Table
Input module data
D7 | D6 | D5 | D4 | D3 | D2 | D1 | D0 |
D15 | D14 | D13 | D12 | D11 | D10 | D9 | D8 |
Input image value
Bit no. | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
Byte 0 | D7 | D6 | D5 | D4 | D3 | D2 | D1 | D0 |
Byte 1 | D15 | D14 | D13 | D12 | D11 | D10 | D9 | D8 |
Parameter Data
Valid parameter length: 2 bytes
Bit no. | Bit 7 | Bit 6 | Bit 5 | Bit 4 | Bit 3 | Bit 2 | Bit 1 | Bit 0 |
Byte 0 | Input filter value: 0 – 10 (unit: ms) | |||||||
Byte 1 | Reserved |
Hardware Setup
CAUTION
- Always read this chapter before installing the module!
- Hot surface! The surface of the housing can become hot during operation. If the device is used in high ambient temperatures, always let the device cool down before touching it.
- Working on energized devices can damage the equipment! Always turn off the power supply before working on the device.
Space Requirements
The following drawings show the space requirements when installing the G-series modules. The spacing creates space for ventilation and prevents conducted electromagnetic interference from influencing the operation. Installation position is valid vertically and horizontally. The drawings are illustrative and may be out of proportion.
CAUTION
Not following the space requirements may result in damaging the product.
Mount Module to DIN Rail
The following chapters describe how to mount the module to the DIN rail.
CAUTION
The module must be fixed to the DIN rail with the locking levers.
Mount GL-9XXX or GT-XXXX Module
The following instructions apply to these module types:
- GL-9XXX
- GT-1XXX
- GT-2XXX
- GT-3XXX
- GT-4XXX
- GT-5XXX
- GT-7XXX
GN-9XXX modules have three locking levers: one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module.
Mount GN-9XXX Module
To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example GN-9251 or GN-9371, see the following instructions:
Field Power and Data Pins
Communication between the G-series network adapter and the expansion module, as well as system / field power supply of the bus modules is carried out via the internal bus. It is comprised of 2 Field Power Pins and 6 Data Pins.
WARNING
Do not touch the data and field power pins! Touching can result in soiling and damage by ESD noise.
Pin no. | Name | Description |
P1 | System VCC | System supply voltage (5 VDC) |
P2 | System GND | System ground |
P3 | Token output | Token output port of processor module |
P4 | Serial output | Transmitter output port of processor module |
P5 | Serial input | Receiver input port of processor module |
P6 | Reserved | Reserved for bypass token |
P7 | Field GND | Field ground |
P8 | Field VCC | Field supply voltage (24 VDC) |