APG Sensors RST-5003 Web Enabled Control Module
Product Information
Specifications
- Model: RST-5003
- Series: Web Enabled
- Manufacturer: Automation Products Group, Inc.
- Part Number: 122950-0012
- Address: 1025 W 1700 N Logan, UT 84321
- Revision: B
- Website: www.apgsensors.com
- Phone: 888-525-7300
- Email: sales@apgsensors.com
Description
The RST-5003 control module is part of the Web Enabled Series by Automation Products Group, designed to provide advanced control and monitoring capabilities for various applications.
Dimensions
Dimensions of the product are as follows: 7/8 G2 BAN 4 DV 4 4 1/2.
Product Usage Instructions
Installation Procedure
- Connect any 4-20 mA sensor, relays, or switched inputs first.
- Connect the RST to Ethernet/network.
- If not using POE, connect an independent 12-28 VDC supply.
- Connect and set up one Modbus sensor at a time.
Important: Each Modbus sensor must be added to the network individually and assigned a unique Sensor Number before adding the next sensor.
Note: If you can control power to each Modbus sensor individually, you can connect them all simultaneously and power them on individually.
Power Supply Wiring Diagrams
For External 12-28VDC Power Supply Wiring:
Frequently Asked Questions (FAQ)
- What is the warranty coverage for the RST-5003 control module?
The product is covered by APG’s warranty for 24 months against defects in material and workmanship under normal use. For more details, visit APG’s Warranty Page. - How can I return the product for evaluation?
Contact Technical Support to receive a Return Material Authorization (RMA) before shipping the product back. You can find more information on the return process on the APG website or by contacting them via email, phone, or online chat.
Thank You
Thanks for purchasing a RST-5003 control module from us! We appreciate your business and your trust. Please take a moment to familiarize yourself with the product and this manual before installation. If you have any questions, don’t hesitate to call us at 888-525-7300.
Description
The RST-5003 Web Enabled Control Module offers a wide degree of integrated and flexible remote and local control and monitoring for your system. The RST-5003 can control up to ten APG Modbus sensors—any combination of level, pressure, magnetostrictive, and ultrasonic—along with one 4-20 mA sensor, and two input or out relay terminals. All readings are available for control and monitoring via TCP/IP for local or remote network access. The RST-5003 also has flexible power options: it can use either POE or an independent 12-28 VDC power source.
How To Read Your Label
- Each label comes with a full model number, a part number, and a serial number. The model number for the RST-5003 will look something like this:
SAMPLE: RST-5013 - The model number correlates with all the configurable options and tells you exactly what you have. Compare the model number to the options on the datasheet to identify your exact configuration. You can also call us with the model, part, or the serial number and we can help you.
Warranty and Return Information
- This product is covered by APG’s warranty to be f ree f rom defects in material and workmanship under normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit https://www.apgsensors.com/resources/warranty-certifications/warranty-returns/. Contact Technical Support to receive a Return Material Authorization (RMA) before shipping your product back.
- If your radar level sensor needs to be returned for evaluation, contact us via email, phone, or on-line chat on our website. We will issue you an RMA number with instructions. You can also find the form on our website by clicking “RMA” in the web footer, or go to
https://share.hsforms.com/1rPTIAWbsTMiD0XD_SkBs6g2rio0.- Phone: 888-525-7300
- Email: sales@apgsensors.com
- Online chat at www.apgsensors.com
Please have your part number and serial number available.
Installation Procedure
- Installing your RST-5003 is easy if you follow a few simple steps:
- STEP 1: Connect any 4-20 mA sensor, relays, or switched inputs first.
- STEP 2: Connect RST to Ethernet/network.
- STEP 3: Connect independent 12-28 VDC supply if not using POE.
- STEP 4: Connect and set up one Modbus sensor at a time.
- Please keep the following limitations in mind:
- Up to 10 Modbus sensors can be connected to the RST-5003 in any combination.
- Only one 4-20 mA sensor can be connected to the RST-5003.
IMPORTANT: Each Modbus sensor must be added to the network individually and assigned a unique Sensor Number before the next sensor can be added.
NOTE: If you can control power to each Modbus sensor individually, you can connect them all simultaneously, and power them on individually.
Dimensions
Power Supply Wiring Diagrams
Modbus System Wiring Diagrams
Accessing the RST-5003’s Embedded Webpage
Each Modbus sensor attached to your RST-5003 must be configured via the RST-5003’s embedded webpage before the next sensor can be added. The easiest way to access the embedded webpage is to type rst_xxx into a web browser on a computer connected to the same local network as the RST-5003. xxx represents the numeric portion of the RST-5003’s serial number. See Figures 8.1 and 8.2.
IMPORTANT: See your RST-5003 User Manual for complete Modbus programming instructions and troubleshooting tips.
NOTE: Refer to each sensor’s user manual for sensor specific wiring instructions. User Manuals for all APG sensors and equipment are available at www.apgsensors.com.
NOTE: Port 6700 must be open on your local network for the RST-5003 to connect.
General Care
- Your RST-5003 is very low maintenance and will need little care as long as it is installed correctly. However, in general, you should:
- Avoid applications for which the control module was not designed, such as extreme temperatures, contact with incompatible corrosive chemicals and fumes, or other damaging environments.
Removal Instructions
- STEP 1: Disconnect power source to control module.
- STEP 2: Disconnect sensors and network cable to control module.
- STEP 3: Remove the control module and store it in a dry place, at a temperature between -40° F and 180° F.