KMC CONTROLS TB210331B Controller Instructions

KMC-CONTROLS-LOGO

KMC CONTROLS TB210331B Controller

KMC-CONTROLS-TB210331B-Controller-PRODUCT

Setup and Use

  1. Disconnect the AppStat from its power source.
  2. Turn the Allen screw in the base of the AppStat clockwise until it clears the mounting base, then swing the controller away from the mounting base (avoid pinching wiring).
  3. Verify the End-of-Line (EOL) jumpers are in the Off position.
  4. Set the multimeter to a resistance range greater than 10k ohms.
  5. Measure resistance between the MS/TP A- pin and the ground (⊥) pin.
  6. Measure resistance between the MS/TP B+ pin and the ground (⊥) connection.
  7. If both readings are greater than 10k ohms, the communication port should operate correctly.
  8. If both readings are less than 10k ohms, the AppStat port is likely damaged, and the AppStat needs replacement; verify the 24 VAC wiring on the mounting base to prevent recurrence.
  9. To reattach: swing the sensor down onto the Allen screw bracket without pinching wiring, then turn the Allen screw counterclockwise until it backs out and engages the case; reconnect power.

ABOUT THIS BULLETIN

  • When there is a communication issue between a BAC-4000 AppStat™ controller and the BACnet MS/TP network to which it is connected, a multimeter can be used to help determine the cause.
  • An AppStat will become damaged if it is allowed to operate continuously with power on an EIA-485 network.
  • The following procedures can be used to test if voltage is present on the network.

MATERIALS

  • Standard multimeter
  • Allen screwdriver (as found on the KMC SP-001)
  • Flathead screwdriver (as found on the KMC SP-001)

PROCEDURES

To measure resistance on the MS/TP terminals.

  1. Disconnect the AppStat from its power source.
  2. Turn the Allen screw in the base of the AppStat clockwise until it clears the mounting base.
  3. Swing the controller away from the mounting base to remove it. Be careful not to pinch any wiring.
  4. Verify that the End-of-Line (EOL) jumpers are in the Off position
  5. Set the multimeter to measure a resistance range of greater than 10k ohms.
  6. At the MS/TP terminals, measure the resistance between the A- pin and the ground (⊥) pin of the AppStat.
  7. At the MS/TP terminals, measure the resistance between the B+ pin and the ground (⊥) connection.
    • If the resistance reads greater than 10k ohms on both pins, then the communication port should operate correctly.
    • To trace network problems from other sources, use the procedures in the KMC document

TROUBLESHOOTING GUIDE, Diagnosing a BACnet MS/TP Network with a Multimeter

  • If the resistance measures less than 10k ohms on both pins, then it is likely the port was damaged by improper phasing of the network or transformer, and the AppStat needs to be replaced.
  • In this event, verify the 24 VAC wiring on the mounting base to prevent the situation from reoccurring.
  • Note: Use the following procedure if the wiring is consistent with the rest of the 24 VAC wiring.

To measure the voltage on the leads from the transformer to the building ground:

  1. Set the multimeter to measure a range of greater than 24 VAC.
  2. Measure the voltage of the hot lead. This should read approximately 24 VAC.
  3. Measure the voltage of the ground lead. This should read 0 VAC. If there is voltage on the ground lead, you may need to wire it to ground.

To reattach the AppStat to its mounting base:

  1. Place the top of the sensor over the top of the mounting base and swing it down over the Allen screw bracket. Be careful not to pinch any wiring.
  2. Turn the Allen screw counterclockwise until it backs out of the mounting base and engages the case.
  3. Reconnect the AppStat to its power source.

See also the following downloadable KMC documents:

HANDLING PRECAUTIONS

  • For digital and electronic sensors, thermostats, and controllers, take reasonable precautions to prevent electrostatic discharges to the devices when installing, servicing, or operating them.
  • Discharge accumulated static electricity by touching one’s hand to a securely grounded object before working with each device.

NOTICE

  • OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES

WE VALUE YOUR FEEDBACK

  • Help us improve this document.
  • Click here to take a 3-minute survey
  • Your input helps us make our documents clearer and more useful.
  • Your input helps us make our documents clearer and more useful.

IMPORTANT NOTICES

  • The KMC logo and KMC Controls are registered trademarks of KMC Controls, Inc. Other products and name brands mentioned may be trademarks of their respective companies or organizations.
  • All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc.
  • The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice.
  • KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document.

SUPPORT

  • Additional resources for product specifications, installation, configuration, application, operation, programming, upgrading and more are available on the KMC Controls website (www.kmccontrols.com). Log in to view all available files.
  • Do you find this document helpful? Click here to share feedback and help us improve: Give Feedback

Troubleshooting Guidance

  • Communication issue between AppStat and BACnet MS/TP network: Use multimeter resistance checks at the MS/TP terminals as described in the procedures. If resistance between both specified pins and ground is greater than 10k ohms, the communication port should operate correctly. If resistance is less than 10k ohms on both pins, the port was likely damaged by improper phasing of the network or transformer; replace the AppStat and verify 24 VAC wiring on the mounting base.
  • If you are tracing network problems from other sources: Use the procedure in the related KMC document titled “TROUBLESHOOTING GUIDE, Diagnosing a BACnet MS/TP Network with a Multimeter.”
  • Note—when wiring is consistent with the rest of the 24 VAC wiring: Measure transformer-to-ground voltage. Set the multimeter to measure a range greater than 24 VAC, measure the hot lead (approximately 24 VAC expected), then measure the ground lead (should read 0 VAC). If voltage is present on the ground lead, wire it to ground.