KMC CONTROLS FlexStat BACnet Advanced Application Controller

Overview
Use this document to facilitate FlexStat model selection according to desired applications and options. For additional specifications, see the BAC-12xxxx/13xxxx Series FlexStat Data Sheet (914-035-01). Additional award-winning resources for configuration, application, operation, program-ming, upgrading and much more are available on the KMC Controls web site (www.kmccontrols. com). To see all available files, you will need to log-in to the KMC Partners site.
Model Code
| BAC-1xmhraCEW: | |||||||||
| BAC- | 1 | x | m | h | r | a | C | E | W |
|
BACnet Device |
Model Series |
CO2
Sensor Type* |
Motion Sensor |
Humidity Sensor |
Number of Relay Outputs | Number of Analog Outputs | Real- Time Clock |
IP/Ethernet Communication |
Case Color |
|
2 = None |
1 =
Included |
1 =
Included |
3 |
3 |
RTC standard on all models |
E = Included |
W =
White |
||
| 3 = Zones with Unoccupied Periods |
0 = None |
0 = None |
6 |
6 |
No E = MS/TP only |
No W
= Light Almond |
|||
| *In models with CO2 sensors, humidity sensors come standard. | |||||||||

Sensor Options
Temperature (Standard)![]()
- Internal temp. sensor standard on all models.
- Optional remote temperature sensor (connected to IN7) allows configuration for onboard (inter-nal), remote, averaging of the two, the lowest reading, or the highest reading.
Humidity![]()
- BAC-1xx1xxC.
- For optional dehumidification (AHU, RTU, HPU, or 4-pipe FCU) or humidification (AHU, RTU, or 4-pipe FCU).
- Comes standard when optional CO2 sensor (BAC-13xxxxC) is ordered.
Motion/Occupancy![]()
- BAC-1x1xxxC.
- For optional occupancy standby and/or override.
CO2 with DCV (Demand Control Ventilation)![]()
- BAC-12xxxxC = No internal sensor, but has built-in DCV sequences and IN9 can be config-ured for remote CO2 sensor.
- BAC-13xxxxC = Internal sensor (with ABC Logic) for applications where concentrations will drop to outside ambient conditions at least three times in a 14 day period. The BAC-13xxxx series (only) has been certified to comply with CA Title 24, Section 121(c), as well as sub-para-graph 4.F.
NOTE: DCV is only available when using an AHU, RTU, or HPU application with a modulating economizer option enabled. For additional important information about the CO2 sensors and DCV, see the FlexStat Data Sheet and FlexStat Operation Guide!
Usage Instruction
Application Options
- Supported AHU, FCU, HPU, and RTU options depend on whether the FlexStat is a BAC-1xxx36C (3 relays and 6 analog outputs) or a BAC-1xxx63C (6 relays and 3 analog outputs).
- See Applications and Models.

BACnet Network Communication Options
MS/TP (Standard)
- Integral peer-to-peer BACnet MS/TP LAN net-work communications standard on all models, including those with Ethernet/IP option.
- Screw terminal blocks accept twisted-pair wire size 14–22 AWG, and a data port on the under-side of the case enables easy temporary com-puter connection to the BACnet network (access with a KMD-5624 cable—requires use of KMD-5576 or third-party interface).
- BAC-1xxxxxCE.
- “E” versions add BACnet over Ethernet, BACnet over IP, and BACnet over IP as Foreign Device.
- “E” versions add RJ-45 jack for Ethernet cable.

Color Options
- White (Standard)
- BAC-1xxxxxCW.
- Standard on all models.

- Light Almond
- BAC-1xxxxxC (W removed).
- Optional on all models.

Applications & Models
KMC Controls FlexStat Models and Outputs
| Applications and Options | 6 Relays and 3 Analog Outputs | 3 Relays and 6 Analog Outputs | ||||||
|---|---|---|---|---|---|---|---|---|
| BAC-1x0063CW | BAC-1x0163CW | BAC-1x1063CW | BAC-1x1163CW | BAC-1x0036CW | BAC-1x0136CW | BAC-1x1036CW | BAC-1x1136CW | |
| Packaged Unit (Air Handling Unit and Roof Top Unit) | ||||||||
| 1 Heat and 1 Cool | ✓ | ✓ | ✓ | ✓ | ||||
| 1 or 2 Heat and 1 or 2 Cool | In all BAC-1xxx63 models, but appears in RTU menu only | |||||||
| 1 or 2 Heat and Modulating Cool | ✓ | ✓ | ✓ | ✓ | ||||
| Modulating Heat and 1 or 2 Cool | ✓ | ✓ | ✓ | ✓ | ||||
| Modulating Heat and Modulating Cool | In all BAC-1xxx63 models, but appears in AHU menu only | ✓ | ✓ | ✓ | ✓ | |||
| Optional Outside Air Damper, Modulating | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| Optional Outside Air Damper, 2 Position | In all BAC-1xxx63 models, but appears in RTU menu only | ✓ | ✓ | ✓ | ✓ | |||
| Optional Fan Speed Control | ✓ | ✓ | ✓ | ✓ | ||||
| Optional Dehumidification (with Humidity) | ✓ | ✓ | ✓ | ✓ | ||||
| Optional Humidifier (with Humidity) | ✓ | ✓ | ||||||
| Optional Motion/Occupancy Sensor | ✓ | ✓ | ✓ | ✓ | ||||
| Optional CO2 Sensor with DCV | BAC-13xxxx; BAC-12xxxx has no CO2 sensor | |||||||
| Optional IP/Ethernet Communications | Add an E to the model number: BAC-1xxxxxxCEx (see Model Code section) | |||||||
| FCU (Fan Coil Unit) | ||||||||
| 2 Pipe, Modulating | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| 2 Pipe, 2 Position | ✓ | ✓ | ✓ | ✓ | ||||
| 4 Pipe, Modulating | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| 4 Pipe, 2 Position | ✓ | ✓ | ✓ | ✓ | ||||
| Optional Dehumidification (4 pipe only) | ✓ | ✓ | ✓ | ✓ | ||||
| Optional Humidifier (4 pipe only) | ✓ | ✓ | ||||||
| Optional Fan Speed (With 3-speed fan) | With 3-speed fan | With 3-speed fan | ||||||
| Optional CO2 Sensor (DCV N/A for FCU) | DCV N/A for FCU Applications (but sensor will still show CO2 levels) | |||||||
| HPU (Heat Pump Unit) | ||||||||
| Compressor Support | 1 or 2 compressors with auxiliary and emergency heat | N/A | ||||||
| Optional Outside Air Damper, Modulating | ✓ | ✓ | ✓ | ✓ | ||||
| Optional Dehumidification | ✓ | ✓ | ||||||
| Optional Motion/Occupancy Sensor | ✓ | ✓ | ||||||
| Optional CO2 Sensor with DCV | BAC-13xxxx; BAC-12xxxx has no CO2 sensor | |||||||
| Optional IP/Ethernet Communications | Add an E to the model number: BAC-1xxxxxxCEx (see Model Code section) |
Model Chart
| Model* | Outputs** | Optional Sensors*** | Typical Applications |
|---|---|---|---|
| BAC-12xxxx models (e.g., BAC-120036CW) are standard and do not have a CO2 sensor. BAC-13xxxx models (e.g., BAC-130036CW) have CO2 sensors to add Demand Control Ventilation to the applications below. DCV is only available when using an AHU, RTU, or HPU application with a modulating economizer option enabled. | |||
| BAC-1x0036CW | 3 Relays and 6 Analog Outputs | None |
|
| BAC-1x0136CW | Humidity**** |
|
|
| BAC-1x1036CW | Motion/Occupancy |
|
|
| BAC-1x1136CW | Humidity and Motion/Occupancy**** |
|
|
| BAC-1x0063CW | 6 Relays and 3 Analog Outputs | None |
|
| BAC-1x0163CW | Humidity**** |
|
|
| BAC-1x1063CW | Motion/Occupancy |
|
|
| BAC-1x1163CW | Humidity and Motion/Occupancy**** |
|
|
|
- For additional specifications, see the BAC-12xxxx/13xxxx Series FlexStat Data Sheet (914-035-01).
- NOTE: For specifications on the older BAC-10000 Series FlexStats (with only three external inputs and no Ethernet or CO2 options), see the data sheet (913- 035-01) for that series.
- FlexStats come with a printed Installation Guide. Additional award-winning resources for configuration, application, operation, programming, upgrading, and much more are available on the KMC Controls web site (www.kmccontrols.com). To see all available files, you will need to log-in to the KMC Partners site.

Accessories
Damper (OAD/RTD) Actuators (Fail-Safe)
- MEP-7552: 22.5 ft2 max. damper area, 180 in-lb., 0–10 VDC, 25 VA
- MEP-7852: 40 ft2 max. damper area, 320 in-lb., 0–10 VDC, 40 VA

Mounting Hardware
- HMO-10000: Horizontal or 4 x 4 handy box wall mounting plate for BAC-12xxxx models (not needed for BAC-13xxxx models), light almond (shown)
- HMO-10000W: HMO-10000 in white

- SP-001: Screwdriver (KMC branded) with flat blade (for termi-nals) and hex end (for cover screws)
Network Communications and Firmware
- HTO-1104: FlexStat firmware upgrade kit

- KMD-5567 : Network surge suppressor

- KMD-5575: Network repeater/ isolator

- KMD-5624: PC data port (EIA-485) cable (FlexStat to USB Communica-tor)—included with the KMD-5576 (buy for third-party EIA-232 interfaces)

Relays (External)
- REE-3112: (HUM) SPDT, 12/24 VDC con-trol relay
Sensors (External)
- CSE-110x: (FST) differential air pressure switch
- STE-1402: (DAT) duct tempera-ture sensor with 8-inch rigid probe

- STE-1416: (MAT) flexible 12-foot duct averaging temp. sensor
- STE-1451: (OAT) outside air temp. sensor
- STE-6011: Remote space temp. sensor
- SAE-10xx: Remote CO2 sensor, space or duct

- STE-1454/1455: (W-TMP) 2-inch strap-on water temp. sensor (with or without enclosure)
Transformers, 120 (or more) to 24 VAC (TX)
- XEE-6111-040: 40 VA, single-hub
- XEE-6112-040: 40 VA, dual-hub
- XEE-6311-050: 50 VA, dual-hub
- XEE-6311-075: 75 VA, single-hub
- XEE-6311-100: 96 VA, dual-hub

Valves (Heating/Cooling/Humidification)
- VEB-43xxxBCL: (HUMV/CLV/HTV) Fail-safe control valve, w/ MEP-4×52 proportional actuator, 20 VA
- VEB-43xxxBCK: (VLV/CLV/HTV) control valve w/ MEP-4002 proportional actuator, 4 VA

- VEZ-4xxxxMBx:(VLV/CLV/HTV) fail-safe control valve, 24 VAC, 9.8 VA
NOTE: For details, see the respective product data sheets and installation guides. See also the FlexStat Application Guide.
Troubleshooting
- DCV not operating as expected: Verify the system configuration meets the documented requirement: DCV is only available with an AHU, RTU, or HPU application that has a modulating economizer option enabled.
- CO2/DCV sensor behavior mismatch: For BAC-13xxxx models, CO2 is an internal sensor using ABC Logic; for BAC-12xxxx models, CO2 uses built-in DCV sequences with IN9 configurable for a remote CO2 sensor.
- Humidity sensor missing when CO2 is used: If the model has a CO2 sensor (BAC-13xxxx), humidity sensors come standard in those models.
- Network connection issues (MS/TP): Ensure twisted-pair wire is 14–22 AWG on the MS/TP screw terminal blocks.
- Ethernet/IP not present: Confirm the model includes the “E” option (E versions add BACnet over Ethernet/IP and add an RJ-45 jack).
Support
- 19476 Industrial Drive New Paris,
- IN 46553, U.S.A
- www.kmccontrols.com
- info@kmccontrols.com
To Order:
- Telephone: 877.444.5622 (574.831.5250)
- Fax: 574.831.5252

Documents / Resources
![]() | FlexStat BACnet Advanced Application Controller |
References
- trols.comtrols.com
- kmccontrols.comwww.kmccontrols.com
- kmccontrols.com/products/productFamilyDetail.aspx?dsid=914-035-01www.kmccontrols.com
- kmccontrols.com/www.kmccontrols.com
- kmccontrols.com/product/accessory-wallplate-digital-tstat-controller-almond/www.kmccontrols.com
- kmccontrols.com/product/accessory-wallplate-digital-tstat-controller-white/www.kmccontrols.com
- kmccontrols.com/product/actuator-proportional-failsafe-24vac-vdc-180-in-lbs/www.kmccontrols.com
- kmccontrols.com/product/actuator-proportional-failsafe-24vac-vdc-320-in-lbs/www.kmccontrols.com
- kmccontrols.com/product/cable-rj11-local-access-4-conductor/www.kmccontrols.com
- kmccontrols.com/product/digital-lighting-surge-supressor/www.kmccontrols.com
- User Manualmanual.tools