Kentec - LogoKS-POWER-OUT
Powered Output Module
Kentec KS POWER OUT System Wired Fire Detection - Cover

Features

  • Loop powered
  • Single loop address programmed via TCH-B200
  • 24 VDC output with adjustable current level
  • 2 x Monitored inputs
  • Compact design
  • Colour coded flying leads for easy installation
  • LPCB approved

Description

KS-POWER-OUT is an addressable Powered Output Module which allows ancillary equipment to be powered from the loop for example conventional beam detectors or flame detectors..
A Hochiki SPE protocol device it is compatible with Kentec’s range of Takt is and Syncro addressable control panels.
The module provides a 24 VDC output with an engineer configurable current level, current level can be set through the fire alarm control panel from 2-32 mA in 2 mA increments. This can be used to power a third party device.
Two monitored inputs are provided for monitoring of outputs from the third party device to enable status to be indicated on the control panel i.e. Fire and Fault relays.
KS-POWER-OUT requires a single loop address which is programmed using the TCH-B200 programmer.
The compact design of the KS-POWER-OUT enables it to be installed within third party equipment.

Specification

Ordering Code and Description KS-POWER-OUT  Powered Output Module
Operating Voltage 17 – 41 VDC
Quiescent Current 200 µA (at 41 V)
Alarm Current 2.3 – 32.3 mA
Test Signal Voltage 14 to 30 VDC
Input Ratings Open Circuit >1oo kΩ
Normal State -10 kΩ (EOL resistor provided)
Input Activation -470 Ω (EOL resistor provided)
Short Circuit <50 Ω
Operating Temperature Range -1o °C to + 50 °C
Storage Temperature Range -30 °C to + 6o °C
Max Humidity 95% RH – Non Condensing (at 40 °C)
Colour/Case Material Ivory / ACS
Weight (g) 30
Dimensions (mm) 65 L x 42 W x 19 D
Approvals LPCB approved to EN54-18:2005
KS-POWER-OUT panel configuration settings*
The following table details the configuration options available on the Kentec Taktis and Syncro AS control panels:
Configuration Options Taktis Syncro AS/XT+
Configurable location text
Fault Reporting Delay
Map to zone
Output Options Default ring mode (Fire), Evacuate Output, Alert Output, Pre Alarm Output, Technical Alarm Output Fault Output, Security Output Default ring mode (Fire), Evacuate
Output, Alert Output, Pre Alarm
Output, Technical Alarm Output
Fault Output, Security Output
Silence able
Invert output operation X
Configurable delay
Drop on Reset (If output normally on)
Current Limit
Configurable Operating Duration X
Single Shot Mode
Input Actions Fire, Fault, Pre Alarm, Technical Alarm, Evacuate, Alert, Security, Silence, Reset, Transparent Disablement, Test Mode, Change
sensitivity mode, Status, Acknowledge Alarm Extended Delay, Acknowledge Alarm Only,
Override Delays
Fire, Fault, Pre Alarm, Technical Alarm, Evacuate, Alert, Security, Silence, Reset, Transparent Disablement, Test Mode
Input Action Message
Bypass Output Delay
Input Delay
Latching or Non-Latching
Invert input X
Disablement as a Plant Control Output X

* KS-POWER-OUT will be identified on Takt is and Syncro AS/XT+ control panels and on LE2 software as its Hochiki equivalent part number CHQ-POM.

Kentec - Logo
Datasheet DS215 06/24 Rev.01
For further information visit www.kentec.co.uk
Kentec Electronics Ltd. reserves the right to alter the specification of its products from time to time without notice.
Although every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or represented by Kentec Electronics Ltd. to be a complete and up-to-date description.

Documents / Resources

Kentec KS-POWER-OUT System Wired Fire Detection [pdf] Owner's Manual
KS-POWER-OUT, DS215-KS-POWER-OUT-Rev.01, KS-POWER-OUT System Wired Fire Detection, KS-POWER-OUT, System Wired Fire Detection, Wired Fire Detection, Fire Detection, Detection

References

Leave a comment

Your email address will not be published. Required fields are marked *