VEC100 Umum RTU Controller, Modulated
Pemanasan lan Staged Cooling Pandhuan Mulai Cepet
LIT-12013360
2021-07-14
Babagan pandhuan iki
Pandhuan wiwitan cepet iki menehi informasi dhasar sing perlu kanggo ngatur lan nginstal Verasys® Equipment Controller (VEC), LC-VEC100-0, nggunakake Verasys generic rooftop unit (RTU) modulated heating lan s.tagaplikasi ed cooling controller. Aplikasi kasebut ngontrol sistem bypass changeover pihak katelu (COBP) utawa unit volume udara variabel pihak katelu (VAV).
Kanggo informasi luwih lengkap, waca Pandhuan Instalasi Versys Equipment Controller (VEC) (24-10143-1272) lan VEC100 Generic RTU Controller, Modulated Heating, lan Staged Cathetan Aplikasi Pendingin (12013361). Tabel 1: Fitur aplikasi
| Pilihan kasedhiya | Nilai sing bisa ditindakake |
| Jumlah Cooling Stagwis diinstal | 0 nganti 4 |
| Katup Pemanasan | • Negara 0: ora diinstal • Negara 1: kumparan banyu |
| Economizer Dipasang | • Negara 0: economizer ora kasedhiya. • Negara 1: economizer kasedhiya. |
| Air Proving Ngalih Setup | • Negara 0: piranti status penggemar • Negara 1: sensor tekanan statis saluran • Negara 2: ora ana |
| Tipe Kontrol Rooftop | • Negara 0: bypass changeover • Negara 1: VAV |
| Batal ASCD Timer | • Negara 0: palsu • Negara 1: bener |
| Panjaluk Fitur Ventilasi | • Negara 0: ventilasi dikarepake mati. • Negara 1: ventilasi dikarepake aktif. |
Pemasangan pengontrol
Kanggo nginstal controller, tindakake langkah ing ngisor iki:
- Pasang bagean 20 cm (8 in.) saka 35 mm (1.3 in.) rel DIN horisontal.
Cathetan: Pasang controller ing posisi horisontal. - Ing mburi controller, ngluwihi rong klip soyo tambah.
Gambar 1: Tarik mudhun klip mounting ngisor
- Selehake controller ing rel DIN.
- Push klip pemasangan ngisor menyang (munggah) kanggo ngamanake controller ing rel DIN.
Gambar 2: Push munggah klip mounting ngisor
Wiring pengontrol
Blok terminal bis area
Blok terminal bis zona abu-abu, bisa dicopot, 4terminal plug sing mathuk menyang Jack Papan-dipasang. Kabel terminal bis zona dipindhah plug plug ing controller ing baris ndhuwur konektor dibandhingke, lan pengontrol lapangan liyane ing konfigurasi daisy-chain nggunakake 3-kabel bengkong, kabel shielded minangka ditampilake ing tokoh ing ngisor iki.
Gambar 3: Kabel blok terminal bus zona

Tabel 2: Konfigurasi daisy-chaining zona bus
| 1 | Piranti mungkasi ing bis zona |
| 2 | Blok terminal bus zona |
| 3 | Daisy-chained nggawe ing bagean bis zona |
| 4 | Nyambung menyang piranti sabanjure ing bis zona. |
Cathetan: Terminal bus zona (SHD) diisolasi lan bisa digunakake kanggo nyambungake (rantai daisy) tameng kanggo kabel bus zona.
Blok terminal bus sensor
Blok terminal bis sensor iku coklat, dipindhah, 4terminal plug sing mathuk menyang Jack Papan-dipasang. Kabel dicopot sensor bis terminal dihubungake ing sisih ngisor konektor dual-dibandhingke kanggo controller, lan piranti bis sensor liyane ing konfigurasi daisy-chain nggunakake 4-kabel bengkong, kabel shielded minangka ditampilake ing tokoh ing ngisor iki.
Gambar 4: Kabel blok terminal bus sensor

Tabel 3: Sensor bus daisy-chaining konfigurasi
| 1 | Mungkasi piranti ing bus sensor |
| 2 | Sensor blok terminal bus plug ing piranti terminating |
| 3 | Daisy-chained nggawe segmen bis sensor |
| 4 | Sensor blok terminal bus plug ing piranti daisy-chain |
| 5 | Sambungan kabel shield |
| 6 | Nyambung menyang piranti sabanjure ing bus sensor. |
Cathetan: Terminal PWR nyedhiyakake 15 VDC. Terminal PWR bisa digunakake kanggo nyambungake (chain daisy) 15 daya VDC ndadékaké ing bis sensor.
Blok terminal sumber daya
Blok terminal daya 24 VAC minangka plug 3 terminal abu-abu, bisa dicopot, sing pas karo jack sing dipasang ing papan ing sisih tengen ndhuwur controller.
Sambungake kabel listrik 24 VAC saka trafo menyang terminal HOT lan COM ing plug terminal, kaya sing ditampilake ing gambar ing ngisor iki. Terminal tengah ing blok terminal daya sumber ora digunakake.
Gambar 5: 24 Blok Terminal Daya Pasokan VAC

Cathetan: Werna kabel daya sumber bisa beda-beda ing trafo saka manufaktur liyane. Deleng instruksi produsen trafo lan gambar instalasi proyek kanggo rincian kabel.
Nyetel alamat VEC nggunakake tampilan lokal
Kanggo nyetel alamat VEC nggunakake tampilan lokal, ngrampungake langkah ing ngisor iki:
- Kanggo ngakses menu, penet tombol ENT (Ketik) tombol.
- Navigasi menyang Pengontrol menu kanthi panah munggah lan mudhun, banjur pencet tombol THT tombol.
- Ing Pengontrol menu, navigasi menyang Jaringan banjur pencet tombol THT tombol.
- Ing Parameter Jaringan bagean, navigasi menyang
Alamat banjur pencet tombol THT tombol.
Tampilan nuduhake nilai alamat standar. - Tekan ing THT tombol.
Alamate kedip-kedip. - Gunakake panah munggah utawa mudhun kanggo nambah utawa nyuda alamat menyang nilai sing dikarepake. Tekan ing THT tombol.
Alamat mandheg kedhip lan tampilan nuduhake alamat lawas. - Pencet salah siji panah munggah utawa mudhun. Layar refresh menyang alamat anyar.
- Pencet ESC (Escape) bola-bali, nganti bali menyang layar utama. Priksa manawa layar utama nuduhake yen sistem wis operasional.
Konfigurasi sensor
Kanggo ngatur sensor sing diinstal, tindakake langkah-langkah ing ngisor iki:
- Navigasi menyang Rincian menu.
- Navigasi menyang Layanan menu banjur pilih Input bagean.
- Pilih sensor sing diinstal nggunakake menu gulung mudhun kanggo saben parameter.
Nganyari VEC
Kanggo nganyari VEC karo panas modulated lan stagaplikasi cooling ed, ngrampungake langkah ing ngisor iki:
- Menyang verasyscontrols.com, lan mlebu nganggo kredensial sampeyan.
- Navigasi menyang Informasi & Dhukungan Produk > Nganyari Piranti.
- Ngundhuh paket file kanggo aplikasi menyang folder ROOT saka USB 2.0 drive. Paket file jeneng ing ngisor iki: VEC100-ModHTGStgCLG_xxxx.pkg
Cathetan: Priksa manawa drive USB diformat minangka FAT utawa FAT32. - Lebokake drive USB menyang port USB ing VEC.
- Yen download ora langsung diwiwiti, banjur ing tampilan lokal pengontrol, pilih opsi Nganyari lan Muat Firmware, banjur pilih paket file ing drive USB, banjur pencet Ketik.
- Nalika nganyari aplikasi rampung, gunakake Verasys Smart Building Hub (SBH) utawa tampilan lokal kanggo ngatur controller.
diagram kabel COBP
Gambar 6: Diagram pengkabelan bypass changeover - VEC100

Gambar 7: Changeover bypass wiring diagram – IOM3711

Tabel 4: Diagram wiring bypass changeover
| Nomer | Katrangan | Jeneng obyek (yen diwenehi) |
| 1 | Ekonom Damper Output (opsional) | MAD-O |
| 2 | Nyedhiyakake output kipas (kanggo penggemar VFD) | SF-O |
| 3 | Output katup pemanasan | HTG-O |
| 4 | Kirim perintah penggemar (kanggo penggemar VFD) | SF-C |
| 5 | Pendinginan stage 1 dhawuh | CLG1-C |
| 6 | Pendinginan stage 2 dhawuh | CLG2-C |
| 7 | Pendinginan stage 3 dhawuh | CLG3-C |
| 8 | Pendinginan stage 4 dhawuh | CLG4-C |
| 9 | 24 V PANAS kanggo dampe motor | n/a |
| 10 | 24 V COM kanggo dampe motor | n/a |
| 11 | 24 V KOM | n/a |
| 12 | 24 V PANAS | n/a |
| 13 | Saka piranti pungkasan | n/a |
| 14 | Kanggo piranti sabanjure | n/a |
| 15 | Sensor kelembapan zona - mung monitor (opsional) | ZN-H |
| 16 | ngasilake CO2 udara Range: 0 ppm nganti 2,000 ppm, 0 VDC nganti 10 VDC |
RA-CO2 |
| 17 | Sensor suhu udara bali | RA-T |
Tabel 4: Diagram wiring bypass changeover
| Nomer | Katrangan | Jeneng obyek (yen diwenehi) |
| 18 | Sensor suhu udara njaba |
OA-T |
| 19 | Discharge sensor tekanan statis udara Range: 0 ing WC kanggo 5 ing WC, 0 VDC kanggo 5 VDC |
DA-P |
| 20 | Discharge sensor suhu hawa | DA-T |
| 21 | Status pasokan penggemar (saklar pembuktian udara, opsional) | SF-S |
| 22 | Purge input (opsional) | PURGE-S |
| 23 | Status Filter (opsional) | FILTER-S |
| 24 | Saka piranti SA pungkasan | n/a |
| 25 | Sensor suhu udara campuran |
MA-T |
diagram pengkabelan VAV
Gambar 8: Diagram pengkabelan VAV – VEC100

Gambar 9: Diagram pengkabelan VAV – IOM3711

Tabel 5: diagram kabel VAV
| Nomer | Katrangan | Jeneng obyek (yen diwenehi) |
| 1 | Ekonom Damper Output (opsional) | MAD-O |
| 2 | Nyedhiyakake output kipas (kanggo penggemar VFD) | SF-O |
| 3 | Output katup pemanasan | HTG-O |
| 4 | Kirim perintah penggemar (kanggo penggemar VFD) | SF-C |
| 5 | Pendinginan stage 1 dhawuh | CLG1-C |
| 6 | Pendinginan stage 2 dhawuh | CLG2-C |
| 7 | Pendinginan stage 3 dhawuh | CLG3-C |
| 8 | Pendinginan stage 4 dhawuh | CLG4-C |
| 9 | 24 V PANAS kanggo dampe motor | n/a |
| 10 | 24 V COM kanggo dampe motor | n/a |
| 11 | 24 V KOM | n/a |
| 12 | 24 V PANAS | n/a |
| 13 | Saka piranti pungkasan | n/a |
| 14 | Kanggo piranti sabanjure | n/a |
| 15 | Sensor kelembapan zona - mung monitor (opsional) | ZN-H |
| 16 | ngasilake CO2 udara Range: 0 ppm nganti 2,000 ppm, 0 VDC nganti 10 VDC |
RA-CO2 |
| 17 | Sensor suhu udara bali | RA-T |
Tabel 5: diagram kabel VAV
| Nomer | Katrangan | Jeneng obyek (yen diwenehi) |
| 18 | Sensor suhu udara njaba Posisi sensor ing area sing peteng ing sisih lor bangunan. |
OA-T |
| 19 | Discharge sensor tekanan statis udara Range: 0 ing WC kanggo 5 ing WC, 0 VDC kanggo 5 VDC |
DA-P |
| 20 | Discharge sensor suhu hawa | DA-T |
| 21 | Status pasokan penggemar (saklar pembuktian udara, opsional) | SF-S |
| 22 | Purge input (opsional) | PURGE-S |
| 23 | Status Filter (opsional) | FILTER-S |
| 24 | Saka piranti SA pungkasan | n/a |
| 25 | Sensor suhu udara campuran |
MA-T |
Komisioning sistem
Kanggo ngaktifake output lan verifikasi operasi sistem, navigasi menyang Komisioning menu, ganti Miwiti Komisi kanggo Pemicu, lan nyetel output individu.
Tabel ing ngisor iki nerangake Rincian > Layanan > Pabrik pilihan menu.
Tabel 6: Rincian: Layanan: Pabrik
| Obyek utawa parameter | Katrangan | Bisa diatur | Defaults | Enum set utawa sawetara |
| Jumlah Cooling Stagwis diinstal | Nyetel nomer cooling stages diinstal. | Bisa diatur | 2 | 0 nganti 4 |
| Katup Pemanasan | Nyetel instalasi katup pemanas. | Bisa diatur | Ora Dipasang | 0 = Ora Dipasang 1 = Koil Banyu |
| Economizer Dipasang | Nyetel apa economizer wis diinstal. | Bisa diatur | Ora | 0 = Ora 1 = Ya |
| Air Proving Ngalih Setup | Milih jinis persiyapan kanggo bukti aliran udara. | Bisa diatur | ora ana | 0 = Piranti Status Penggemar 1 = Sensor Tekanan Statis Saluran 2 = Ora ana |
| Equalize Cooling Stagiku Runtime | Mbisakake kompresor bisa mlaku ing mode timbal / lag adhedhasar runtime. | Bisa diatur | Ora | 0 = Ora 1 = Ya |
| OAT Cooling Suhu Lockout | Nyetel suhu nalika lockout cooling njaba dumadi. | Bisa diatur | 50°F (10°C) | 0°F nganti 100°F (-18°C nganti 38°C) |
| Suhu Lockout Pemanasan OAT | Nyetel suhu nalika lockout pemanasan njaba kedadeyan. | Bisa diatur | 55°F (12.77°C) | 0°F nganti 100°F (-18°C nganti 38°C) |
| Setpoint Posisi Minimal Economizer | Nyetel hawa njaba minimal dampposisi er. | Bisa diatur | 20% | 0% nganti 100% |
| Tipe Kontrol Rooftop | Nyetel jinis pengontrol kanggo ngganti bypass utawa VAV. | Bisa diatur | Ngganti Bypass | 0 = Ngganti Bypass 1 = WAV |
| Variabel Speed Drive | Nyetel apa VEC100 ngontrol penggemar VFD tinimbang bypass damper nalika jinis controller rooftop disetel kanggo bypass changeover. | Bisa diatur | Palsu | 0 = Palsu 1 = Bener |
| Offset Weker Suhu Udara Supply | Yen SAT ora ana ing kisaran nilai iki, wektu tundha weker SAT diwiwiti. Examples: Yen setpoint online sumber 55 ° F lan iki disetel kanggo 5 ° F, banjur online sumber kudu ing 60 ° F, utawa wektu tundha diwiwiti. Yen titik setel udhara sumber 110°F lan disetel dadi 5°F, mula udhara sumber kudu ndhuwur 105°F, utawa wektu tundha diwiwiti. | Bisa diatur | 5 delta °F (2.78 delta °C) | 0 delta °F nganti 25 delta °F (0 delta °C nganti 14 delta °C) |
| Supply Air Suhu Weker wektu tundha | Nyetel jumlah wektu sing kudu dilewati sadurunge weker SAT kedadeyan. | Bisa diatur | 20 min | 0 menit nganti 120 menit |
| Batal ASCD Timer | Ngreset wektu urip lan mati minimal. | Bisa diatur | Palsu | 0 = Palsu 1 = Bener |
| Panjaluk Fitur Ventilasi | Ngaktifake utawa mateni fitur ventilasi dikarepake. | Bisa diatur | Mati | 0 = Mati 1 = Urip |
Garansi produk
Produk iki dijamin dening garansi winates, sing bisa ditemokake ing www.johnsoncontrols.com/buildingswarranty.
syarat piranti lunak
Panggunaan piranti lunak sing ana ing (utawa dadi) produk iki, utawa akses menyang awan, utawa layanan sing di-host sing ditrapake kanggo produk iki, yen ana, tundhuk lisensi pangguna pungkasan, informasi piranti lunak open-source, lan syarat-syarat liyane sing disetel. metu ing www.johnsoncontrols.com/techterms. Panganggone produk iki minangka persetujuan kanggo istilah kasebut.
Titik kontak tunggal
| APAC | Eropah | NA/SA |
| JOHNSON KONTROL C/O KONTROL MANAJEMEN PRODUK NO. 32 CHANGJIJANG RD NEW KABUPATEN PROVINSI WUXI JIANGSU 214028 CHINA |
JOHNSON KONTROL WESTENDORF 3 45143 ESSEN JERMAN |
JOHNSON KONTROL 507 E MICHIGAN ST MILWAUKEE WI 53202 USA |
Informasi kontak
Hubungi kantor cabang lokal sampeyan: www.johnsoncontrols.com/locations
Kontak Johnson Controls: www.johnsoncontrols.com/contact-us
© 2021 Johnson Controls. Kabeh hak dilindhungi undhang-undhang. Kabeh spesifikasi lan informasi liyane ditampilake saiki nalika revisi dokumen lan bisa diganti tanpa kabar.
Dokumen / Sumber Daya
![]() |