Vent-Axia ACM100 B ACM In-Line Penggemar Aliran Campuran
PITUDUH
Instruksi Instalasi lan Wiring kanggo kisaran ACM IN-LINE MIXED FLOW FAN.
PENTING: Waca pandhuan iki sadurunge miwiti INSTALASI
AJA nginstal produk iki ing wilayah sing ana utawa kedadeyan ing ngisor iki:
- Minyak sing gedhe banget utawa swasana sarat minyak.
- Gas, cairan utawa uap sing bisa ngrusak utawa gampang kobong.
- Suhu sekitar luwih saka 40 ° C utawa kurang saka –5 ° C.
- Kemungkinan sing bakal ngalangi akses utawa ngilangi Fan.
- Bends ductwork dadakan utawa transformasi cedhak Fan.
CATETAN KESELAMATAN lan PANDUAN
- Kabeh kabel kudu sesuai karo Peraturan IEE saiki, utawa standar sing cocog ing negara sampeyan lan kudu dipasang dening wong sing nduweni kualifikasi sing cocog.
- Kipas kasebut kudu disedhiyakake karo switch isolator kutub dobel lokal kanthi pamisahan kontak paling sethithik 3mm.
- Priksa manawa pasokan listrik (Voltage, Frekuensi, lan Fase) tundhuk karo label rating.
- Kipas angin mung kudu digunakake bebarengan karo produk Vent-Axia sing cocog.
- Disaranake sambungan menyang terminal konektor penggemar digawe nganggo kabel fleksibel.
- Nalika Kipas digunakake kanggo mbusak udhara saka kamar sing ngemot piranti kobong bahan bakar, pancegahan kudu dijupuk kanggo ngindhari aliran bali saka gas menyang kamar saka flue mbukak saka gas utawa piranti liyane. Priksa manawa panggantos hawa cukup kanggo kipas lan piranti sing ngobong bahan bakar.
- Fan ngirim ora digunakake ing ngendi iku tanggung jawab kanggo tundhuk semprotan banyu langsung kanggo dangu.
- Ing ngendi Kipas ducted digunakake kanggo nangani hawa sing diisi kelembapan, jebakan kondensasi kudu dipasang. Saluran horisontal kudu disusun kanthi miring rada mudhun saka Kipas.
- Piranti iki ora dimaksudake kanggo digunakake dening wong (kalebu bocah-bocah) sing kurang kemampuan fisik, sensori utawa mental, utawa kurang pengalaman lan kawruh, kajaba wis diwenehi pengawasan utawa instruksi babagan panggunaan piranti kasebut dening wong sing tanggung jawab kanggo safety.
- Bocah-bocah cilik kudu diawasi supaya ora dolanan piranti kasebut.
INSTALASI
Unit iki dirancang minangka penggemar saluran ing-line kanggo dipanggonke antarane dawa ducting. Saluran cendhak sing cedhak karo kipas angin (yaiku ing 1.5m) kudu ngemot pelindung sing cocog kajaba kipas dipasang luwih dhuwur tinimbang 2.1m ing ndhuwur lantai. Yen ducting fleksibel digunakake kudu lengkap lengkap kanggo entuk asil paling apik. Posisi kipas ing titik paling dhuwur ing sistem karo loro ducting mlaku sloping mudhun saka titik iki. Arah aliran udara dituduhake ing label rating kanthi panah nuding arah aliran udara.
Jebakan kondensat bakal dibutuhake ing saluran pembuangan ing ngendi tingkat kelembapan sing berlebihan ana ing udhara.
Saluran sing ngliwati kekosongan atap sing ora panas kudu diisolasi.
(Waca Fig 15 kanggo dimensi penggemar sakabèhé lan posisi bolongan mbenakake). Nalika dipasang piranti, priksa manawa ana papan sing cukup kanggo ngidini akses kanggo layanan lan pangopènan.
Kanggo entuk akses menyang bolongan sing dipasang, tindakake ing ngisor iki: -
- Nggunakake obeng salib-kepala, ngeculake loro klip plastik biru kanthi mbatalake loro bolt minangka ditampilake ing Fig 1. Geser metu perakitan impeller motor, ndeleng Fig 2.
- Kipas angin saiki bisa dipasang ing sembarang sudut, nggunakake bolongan sing kasedhiya Fig 3,4,5,6 & 15
- Sawise dhasar wis didandani kanthi aman, geser perakitan impeller motor bali, kaya sing dituduhake ing Fig 7. Ganti sekrup lan kenceng kanggo ngunci rakitan bebarengan Fig 8.
WIRING.
PÈNGET: FAN lan ANCILLARY CONTROL EQUIPMENT kudu diisolasi saka sumber daya sak INSTALASI / UTAWA MAINTENANCE.
Penggemar ACM wis terisolasi pindho lan nggawa tandha. ORA ANA TERMINAL BUMI LAN PENGGEMAR IKI ORA DIBUMI.
- Copot tutup kothak terminal & ngawut-awut lan sijine menyang sisih Fig. 9
- Pilih lan tindakake diagram wiring cocok (Fig. 10-11).
- Priksa kabeh sambungan wis digawe bener lan mesthekake kabeh sambungan terminal lan kabel clamps sing aman fastened. (Gambar 12)
- Entri kabel kudu digawe nggunakake grommet kabel sing kasedhiya
- Ganti tutup kothak terminal & sekrup Fig.13
- Priksa manawa impeller muter lan bebas saka alangan
Pangaturan wektu
Kipas angin kudu disambungake menyang saklar remot (contone, saklar lampu). Nalika diuripake 'ON', penggemar bakal operate ing kacepetan sing dipilih, lan bakal terus mbukak kanggo wektu prasetel sawise penggemar diuripake 'OFF'. Timer disetel ing pabrik kira-kira 15 menit. Periode wektu overrun bisa diatur saka 3-25 menit kanthi ngganti adjuster ing PCB kontrol karo nggunakake screwdriver warata cilik. Gambar 13
Sadurunge nyetel wektu, mateni Pasokan Listrik.
Copot tutup kothak terminal penggemar lan tetep ngawut-awut
Kanggo nambah wektu operasi, nguripake adjuster searah jarum jam. Kanggo nyuda wektu operasi, putar adjuster ANTI-JOCKWISE. Ganti tutup kothak terminal penggemar.
Imbuhan kacepetan
Penggemar nduweni telung kecepatan sing bisa dipilih kanthi ngganti posisi jumper. Penggemar disetel pabrik menyang Setelan 3 - Kacepetan dhuwur. Kanggo ngganti setelan kacepetan, tarik jumper saka pin header lan bali menyang posisi sing dikarepake, ndeleng Fig14.
- Setelan LOW SPEED
- Setelan yaiku MEDIUM SPEED
- Setelan yaiku HIGH SPEED
Variabel Speed Controller
Pangaturan kacepetan kanggo versi dhasar uga bisa digayuh kanthi nggunakake pengontrol kacepetan (referensi saham W300310). Yen pengontrol kacepetan digunakake, setelan kacepetan ing unit penggemar kudu nyetel 3 - Kacepetan Dhuwur. Tindakake pandhuan Instalasi lan kabel kanggo unit pengontrol kacepetan kanggo nginstal pengontrol kanthi bener. Pengontrol kacepetan variabel ora kudu digunakake karo versi timer.
OVER-HEATING pangayoman.
Motor penggemar dilengkapi Perlindhungan Kakehan Termal. Iki minangka sekring termal siji-dijupuk. Yen ana kondisi fault, penggemar bakal dipateni kanthi otomatis. Yen kedadeyan kasebut, isolasi kipas, lan hubungi insinyur layanan sampeyan.
SERVICE lan Maintenance
PÈNGET: KIPAS lan ANCILLARY CONTROL EQUIPMENT kudu diisolasi saka power supply sak Maintenance.
- Ing interval sing cocog kanggo instalasi, penggemar kudu dipriksa lan di resiki kanggo mesthekake yen ora ana rereget utawa celengan liyane.
Penggemar ACM In-Line Mixed Flow wis disegel kanggo bantalan urip, sing ora mbutuhake pelumasan.
Ukuran (mm) | 100 | 125 | 150 | 200 |
AØ | 98 | 122 | 147 | 198 |
BØ | 178 | 178 | 200 | 220 |
C | 124 | 124 | 138 | 138 |
D | 298 | 259 | 307 | 300 |
E | 96 | 96 | 118 | 130 |
F | 168 | 168 | 192 | 195 |
G FIXING CTRS | 120 | 120 | 162 | 100 |
H FIXING CTRS | 153.5 | 153.5 | 178 | 180 |
FICHE PRODUK
Kanggo Unit Ventilasi Residential (Complying Commission Delegated Regulation (EU) No 1254/2014)
Model dhasar
jeneng: | Vent-Axia | Vent-Axia | Vent-Axia | Vent-Axia |
ID Model (Ref Saham): | ACM100 –
17104010D |
ACM125 –
17105010D |
ACM150 –
17106010C |
ACM200 –
17108010C |
Diumumake minangka: RVU utawa NRVU / UVU utawa BVU | NRVU/UVU | NRVU/UVU | NRVU/UVU | NRVU/UVU |
Speed Drive | Multi Speed | Multi Speed | Multi Speed | Multi Speed |
Tipe HRS (Recuperative, Regenerative, None) | ora ana | ora ana | ora ana | ora ana |
Eff Termal: [ (%), NA(yen ora ana)] | N/A | N/A | N/A | N/A |
Laju Aliran Nominal (m3/s) | 0.06 | 0.07 | 0.11 | 0.18 |
Elektrik sing efektif. Input Daya (kW): (@Nom.Flow Rate&Ext. Pressure) | 0.02 | 0.03 | 0.05 | 0.10 |
SFPint [W/(m3/s)] | N/A | N/A | N/A | N/A |
Kacepetan Pasuryan (m/s) @ Laju Aliran Desain | N/A | N/A | N/A | N/A |
Tekanan Eksternal Nominal: (∆ps, ext) ing Pa | 71 | 74 | 92 | 167 |
Tekanan Internal Drop Komponen Ventilasi (∆ps, int) ing Pa; | N/A | N/A | N/A | N/A |
Tambahan Internal Press. Drop saka Non-Ventilasi Comp.:∆ ps, nambah (Pa) | N/A | N/A | N/A | N/A |
Statik Ef. Saka penggemar digunakake miturut Peraturan (EU) No.. 327/2011; | TBC | TBC | TBC | TBC |
Diumumake: - Tingkat Kebocoran Internal & Eksternal (%) kanggo BVU utawa digawa (mung kanggo penukar panas regeneratif), & Ext. Tingkat Bocor (%) kanggo Ducted UVU; |
N/A |
N/A |
N/A |
N/A |
Kinerja Energi, luwih disenengi klasifikasi energi, saka Filter (informasi sing diumumake babagan AEC sing diwilang) |
N/A |
N/A |
N/A |
N/A |
Peringatan Filter (RVU) | Ora | Ora | Ora | Ora |
Kanggo UVUs (Instruksi Pasang Grilles Façade) | Ing F&W | Ing F&W | Ing F&W | Ing F&W |
Alamat Internet (kanggo Petunjuk Pembongkaran) |
FICHE PRODUK
Kanggo Unit Ventilasi Residential (Complying Commission Delegated Regulation (EU) No 1254/2014) – Terus
Model Timer
jeneng: | Vent-Axia | Vent-Axia | Vent-Axia | Vent-Axia |
ID Model (Ref Saham): | ACM100T -
17104020F |
ACM125T -
17105020C |
ACM150T -
17106020D |
ACM200T -
17108020B |
Diumumake minangka: RVU utawa NRVU / UVU utawa BVU | NRVU/UVU | NRVU/UVU | NRVU/UVU | NRVU/UVU |
Speed Drive | Multi Speed | Multi Speed | Multi Speed | Multi Speed |
Tipe HRS (Recuperative, Regenerative, None) | ora ana | ora ana | ora ana | ora ana |
Eff Termal: [ (%), NA(yen ora ana)] | N/A | N/A | N/A | N/A |
Laju Aliran Nominal (m3/s) | 0.06 | 0.07 | 0.11 | 0.18 |
Elektrik sing efektif. Input Daya (kW): (@Nom.Flow Rate&Ext. Pressure) | 0.02 | 0.03 | 0.05 | 0.10 |
SFPint [W/(m3/s)] | N/A | N/A | N/A | N/A |
Kacepetan Pasuryan (m/s) @ Laju Aliran Desain | N/A | N/A | N/A | N/A |
Tekanan Eksternal Nominal: (? ps, ext) ing Pa | 71 | 74 | 92 | 167 |
Tekanan Internal Drop Komponen Ventilasi (?ps, int) ing Pa; | N/A | N/A | N/A | N/A |
Tambahan Internal Press. Drop saka Non-Ventilasi Comp.: ?p s, nambah (Pa) | N/A | N/A | N/A | N/A |
Statik Ef. Saka penggemar digunakake miturut Peraturan (EU) No.. 327/2011; | TBC | TBC | TBC | TBC |
Diumumake: - Tingkat Kebocoran Internal & Eksternal (%) kanggo BVU utawa digawa (mung kanggo penukar panas regeneratif), & Ext. Tingkat Bocor (%) kanggo Ducted UVU; |
N/A |
N/A |
N/A |
N/A |
Kinerja Energi, luwih disenengi klasifikasi energi, saka Filter (informasi sing diumumake babagan AEC sing diwilang) |
N/A |
N/A |
N/A |
N/A |
Peringatan Filter (RVU) | Ora | Ora | Ora | Ora |
Kanggo UVUs (Instruksi Pasang Grilles Façade) | Ing F&W | Ing F&W | Ing F&W | Ing F&W |
Alamat Internet (kanggo Petunjuk Pembongkaran) |
Ditrapake mung kanggo produk sing diinstal lan digunakake ing Inggris. Kanggo rincian jaminan ing njaba Inggris hubungi supplier lokal.
Vent-Axia njamin produke suwene rong taun wiwit tanggal tuku saka bahan utawa pengerjaan sing salah. Yen ana bagean sing rusak, produk kasebut bakal didandani, utawa kanthi pilihan Perusahaan diganti, tanpa biaya, yen produk kasebut:-
- Wis diinstal lan digunakake miturut pandhuan sing diwenehake karo saben unit.
- Ora disambungake menyang sumber listrik sing ora cocog. (Sumber listrik sing bener voltage ditampilake ing label rating produk sing dipasang ing unit).
- Wis ora kena kanggo nyalahi panggunaan, watak cerobo utawa karusakan.
- Ora diowahi utawa didandani dening wong sing ora sah dening perusahaan.
Perwakilan Sah EU: Vent-Axia Bedrijvenweg 17 7442 CX Nijverdal Nederland. authorisedrep@vent-axia.nl
PUSAT PANGGILAN NASIONAL UK, Newton Road, Crawley, West Sussex, RH10 9JA
PERTANYAAN SALES: Telp: 0344 8560590 Fax: 01293 565169
DUKUNGAN TEKNISTelp : 0344 8560594 Fax : 01293 532814
Kanggo rincian babagan prosedur babar pisan lan bali, waca www.vent-axia.com utawa nulis menyang Vent-Axia Ltd, Fleming Way, Crawley, RH10 9YX
Dokumen / Sumber Daya
![]() |
Vent-Axia ACM100 B ACM In-Line Penggemar Aliran Campuran [pdf] Instruksi Manual ACM100 B, 17104010D, ACM100 T, 17104020F, ACM125 B, 17105010D, ACM100 B ACM Penggemar Aliran Campuran In-Line, ACM100 B, Penggemar Aliran Campuran ACM In-Line, Penggemar Aliran Campuran ACM125, 17105020 ACM, Penggemar Arus Campuran ACM, 150 ACM, 17106010 ACM , 150C, ACM17106020 T, 200D, ACM17108010 B, 200C, ACM17108020 T, XNUMXB |
![]() |
Vent-Axia ACM100 B ACM Ing Line Mixed Aliran Fans [pdf] Instruksi Manual Penggemar ACM100 B ACM In Line, ACM100, B ACM In Line Kipas Aliran Campuran, Penggemar Aliran Campuran Garis, Penggemar Aliran Campuran, Penggemar Aliran |