Manual iki menehi liwatview lan instruksi instalasi kanggo modul PAD100-SIM. Modul iki mung kompatibel karo sistem geni sing bisa dialamatake sing nggunakake Protokol Alamat PAD. ll terminal daya winates lan kudu kabel sesuai karo syarat NFPA 70 (NEC) lan NFPA 72 (National Fire Alarm Code). Gagal ngetutake diagram pengkabelan ing kaca ing ngisor iki bakal nyebabake sistem ora bisa digunakake kaya sing dikarepake. Kanggo informasi luwih lengkap, waca pandhuan instalasi panel kontrol. Modul kasebut mung kudu dipasang karo panel kontrol sing kadhaptar. Deleng manual instalasi panel kontrol kanggo operasi sistem sing bener.
Katrangan
Modul PAD100-SIM nggunakake siji (1) alamat loop SLC ing loop SLC nalika ngawasi siji (1) sirkuit Kelas B. Modul dipasang ing salah siji kothak 2-geng UL Listed 1-2/2″ utawa kothak kothak 1-1/2″ jero 4″. PAD100-SIM kalebu siji LED abang kanggo nuduhake status modul. Ing kondisi normal, LED sumunar nalika piranti lagi polling dening panel kontrol. Nalika input diaktifake, LED bakal sumunar kanthi cepet. Yen kedhip LED wis dipateni liwat piranti lunak pemrograman, ing kondisi normal LED piranti bakal mati. Kabeh kahanan liyane tetep padha.
Nyetel Alamat
Kabeh detektor lan modul protokol PAD mbutuhake alamat sadurunge sambungan menyang daur ulang SLC panel. Alamat saben piranti PAD (yaiku, detektor lan/utawa modul) disetel kanthi ngganti switch dip sing ana ing piranti kasebut. Alamat piranti PAD kasusun saka saklar dip posisi pitu (7) sing digunakake kanggo program saben piranti kanthi alamat saka 1–127.
Gambar 1. Tabel Alamat Switch Dip Piranti PAD (Alamat 1–127)
Cathetan: Saben kothak "abu-abu" nuduhake yen saklar dip "Aktif," lan saben kothak "putih" nuduhake "Mati."
mantanamples kapacak ing ngisor iki nggambarake setelan ngalih dip piranti PAD: ex 1stample nuduhake piranti ora ono ngendi kabeh setelan ngalih dip ing standar "Off" posisi, 2. nggambarake piranti PAD ono liwat setelan ngalih dip.
Gambar 2. Examples saka Piranti PAD Nuduhake Setelan Ngalih Dip Default (Ora Alamat) & Piranti PAD Alamat
Sadurunge nyambungake piranti menyang loop SLC, tindakake pancegahan ing ngisor iki kanggo nyegah karusakan potensial kanggo SLC utawa piranti.
- Daya kanggo SLC dibusak.
- Wiring lapangan ing modul wis diinstal kanthi bener.
- Wiring lapangan ora duwe sirkuit mbukak utawa cendhak.
Spesifikasi Teknis
- Operasional Voltage: 24.0V
- Max SLC Siaga Arus: 240 μ A
- Max SLC Alarm Saiki: 240 μ A
- Max Wiring Resistance saka IDC: 100 Ω
- Kapasitansi Wiring Max IDC: 1 μF
- Maks IDC Voltage: 2.05 VDC
- Arus IDC maks: 120 μ A
- Resistor EOL: 5.1K
- Kisaran Suhu Operasi: 32 nganti 120 F (0 nganti 49 C)
- Kisaran Kelembapan Operasi: 0 nganti 93% (non-kondensasi)
- Maks. Jumlah Modul Per Loop: 127 unit
- ukuran: 4.17 "L x 4.17" W x 1.14" D
- Pilihan Pemasangan: UL Listed 2-1/2″ jero 2-geng kothak utawa 1-1/2″ jero 4″ kothak kothak
- Bobot pengiriman: 0.6 lbs
Wiring Diagram
Diagram wiring kapacak ing ngisor iki nggambarake carane kabel modul PAD100-SIM minangka Kelas B. Tambahan, diagram instalasi nuduhake carane nginstal modul nggunakake kothak electrical kompatibel.
Gambar 3. Example saka Nginstal PAD100-SIM Nggunakake kothak Listrik Kompatibel
Gambar 4. Exampsaka Wiring a PAD100-SIM minangka Kelas B
Cathetan
- Gaya kabel SLC ndhukung Kelas A, Kelas X lan Kelas B.
- Gaya kabel IDC ndhukung Kelas B.
- SLC daur ulang wiring (SLC +, SLC-) lan wiwitan piranti wiring (IN1) daya winates.
- Wiring kanggo terminal SLC +, SLC- lan piranti wiwitan (IN1) diawasi.
- Modul alamat iki ora ndhukung detektor 2-kabel.
- Kabeh wiring antarane # 12 (max.) lan # 22 (min.).
- Preparation Wire - Copot kabeh kabel 1/4 inci saka pinggir kaya sing dituduhake ing kene:
- Mbusak insulasi sing akeh banget bisa nyebabake kesalahan lemah.
- Stripping sithik banget bisa nyebabake sambungan sing ora apik lan sabanjure sirkuit mbukak.
Pandhuan kasebut ora kalebu kabeh rincian utawa variasi ing peralatan sing diterangake, lan uga ora nyedhiyakake saben kontingensi sing bisa ditindakake sajrone instalasi, operasi lan pangopènan. Spesifikasi bisa diganti tanpa kabar sadurunge. Kanggo Bantuan Teknis hubungi Perusahaan Sinyal Listrik Potter ing 866-956-1211. Kinerja nyata adhedhasar aplikasi prodhuk sing tepat dening profesional sing berkualitas. Yen informasi luwih lanjut dikarepake utawa yen ana masalah tartamtu, sing ora cukup kanggo tujuan panuku, masalah kasebut kudu dirujuk menyang distributor ing wilayah sampeyan.