Pembawa SYSVU SystemVu Controller

PERTIMBANGAN KESELAMATAN
- Instalasi lan servis peralatan AC bisa mbebayani amarga tekanan sistem lan komponen listrik. Mung personel layanan sing dilatih lan mumpuni sing kudu nginstal, ndandani, utawa nglayani peralatan AC.
- Personil sing ora dilatih bisa nindakake fungsi pangopènan dhasar kanggo ngresiki gulungan lan saringan lan ngganti saringan. Kabeh operasi liyane kudu ditindakake dening personel layanan sing dilatih. Nalika nggarap peralatan AC, mirsani pancegahan ing literatur, tags lan label sing ditempelake ing unit, lan pancegahan safety liyane sing bisa ditrapake.
- Follow all local building codes and appropriate national electrical codes (in the USA, ANSI/NFPA 70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements. Wear safety glasses and work gloves. Use a quenching cloth for unbrazing operations. Have a fire extinguisher available for all brazing operations.
- It is important to recognise safety information. This is the safety-alert symbol.
Nalika sampeyan ndeleng simbol iki ing unit lan ing instruksi utawa manual, waspada kanggo potensial kanggo bundhas pribadi. - Ngerteni tembung tandha BAHAYA, WARNING, AWAS, lan CATATAN. Tembung-tembung kasebut digunakake kanthi simbol tandha safety. BAHAYA ngenali bebaya paling serius sing bakal nyebabake ciloko pribadi utawa pati. PÈNGET nuduhake bebaya sing bisa nyebabake ciloko utawa pati. AWAS digunakake kanggo ngenali praktik sing ora aman, sing bisa nyebabake cilaka pribadi utawa karusakan produk lan properti. CATETAN digunakake kanggo nyorot saran sing bakal nambah instalasi, linuwih, utawa operasi.
BAHAYA
BAHAYA KESEMPATAN LISTRIK
- Gagal ngetutake bebaya iki bakal nyebabake ciloko utawa pati.
- Sadurunge nindakake operasi servis utawa pangopènan ing unit, mateni saklar daya utama menyang unit banjur pasang kunci lan lockout. tag(s). Mesthekake layanan listrik menyang unit rooftop sarujuk karo voltage lan amperage kadhaptar ing unit rating plate. Unit kasebut bisa uga duwe luwih saka siji saklar daya.
AWAS
- BAHAYA KERUSAKAN UNIT
- This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components or to bypass or otherwise depart from recommended procedures. Any
- Shorting to ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
WARNING
- UNIT OPERASI lan BAHAYA KESELAMATAN
- Gagal ngetutake bebaya iki bisa nyebabake cilaka pribadi, pati lan/utawa karusakan peralatan.
- R-454B is an A2L refrigerant. All service equipment or components must be A2L refrigerant rated. Do not use non-A2L-rated equipment or components on R-454B refrigerant equipment.
WARNING
- PROPERTY UTAWA BAHAYA ciloko pribadi
- Risk of fire. Flammable refrigerant is used.
- To be installed and/or repaired only by trained service personnel. Do not puncture refrigerant tubing.
- Auxiliary devices which may be ignition sources shall not be installed in the ductwork, other than the auxiliary devices listed for use with the specific appliance. See instructions.
- Buang refrigerant kanthi bener miturut peraturan federal utawa lokal.
WARNING
- cilaka pribadi lan BAHAYA LINGKUNGAN
- Gagal ngetutake bebaya iki bisa nyebabake cilaka pribadi utawa pati.
- Ngilangi tekanan lan pulihake kabeh refrigeran sadurunge ndandani sistem utawa pembuangan unit pungkasan.
- Nganggo kaca tingal lan sarung tangan safety nalika nangani refrigeran. Tansah obor lan sumber kontak liyane adoh saka refrigeran lan lenga.
WARNING
RISIKO FIRE UTAWA bledosan
- Yen informasi ing manual iki ora tindakake persis, geni utawa bledosan bisa nyebabake, nyebabake karusakan property, bundhas pribadi utawa mundhut nyawa.
- Aja nyimpen utawa nggunakake bensin utawa uap lan cairan liyane sing gampang kobong ing sacedhake piranti iki utawa piranti liyane.
APA sing kudu ditindakake yen sampeyan mambu gas
- Aja nyoba madhangi piranti apa wae.
- Aja ndemek saklar listrik; aja nggunakake telpon ing bangunan sampeyan.
- Langsung ninggalake bangunan kasebut.
- Langsung hubungi pemasok gas saka telpon tanggane. Tindakake pandhuan panyedhiya gas.
- Yen sampeyan ora bisa tekan pemasok gas, hubungi pemadam kebakaran.
TUJUAN
- Tujuan saka document iki kanggo menehi general liwatview of the SystemVu controller (see Fig. 1) and to provide guidance for integration with various other devices and systems. The focus in this
- document will be on networking practices with BACnet®1 and Rnet. For CCN practices follow the Carrier Comfort Network® guide.
Apa SystemVu Controller
- SystemVu is a factory-installed integrated HVAC unit controller utilised in a variety of Carrier Light Commercial products.
- The SystemVu controller is fully communicating and cable-ready for connection to Carrier Comfort Network (CCN) or BACnet MS/TP building systems. The SystemVu controller can also communicate with Rnet Sensors, Equipment Touch™ devices, and System Touch™ devices.
- Merek dagang lan logo pihak katelu minangka properti saka pihak sing duwe.

Protokol Didhukung dening SystemVu
The SystemVu controller supports the following Building Automation System (BAS) protocols.
- CCN (Carrier’s Comfort Network)
- BACnet over MS/TP
Please note that the default BAS Protocol setting (BMS_CFG) for SystemVu is configured as “None”.
KONFIGURASI PROTOKOL
- Setel protokol Komunikasi nggunakake UI (antarmuka pangguna) minangka ditampilake ing Fig. 2.
- Konfigurasi Protokol SystemVu BAS menyang CCN
- For Configuring the SystemVu Communication Protocol to CCN (Carrier Comfort Network®), navigate to “Network Settings” in the User Interface using Menu/Settings/Network Settings/BAS
- PROTOCOL. Controller will prompt for “ENTER PASS-WORD”, Type in “1111” as password and select “1 – CCN” as shown in Fig. 2.

Konfigurasi SystemVu menyang BACnet
- For Configuring the SystemVu Communication Protocol to ‘BACnet’, navigate to “Network Settings” in UI using Menu/Settings/Network Settings/BAS PROTOCOL and select BACNET. Controller will
- Prompt for “ENTER PASSWORD”, Type in “1111” as the password.
Setelan Konfigurasi SystemVu BACnet
SystemVu ndhukung tarif Baud ing ngisor iki kanggo BACnet MS / TP.
- 9600
- 19200
- 8400
- 57600
- 76800
- 115200
CATETAN: 115,200 baud rate can only be used with certain devices, such as the iVu® XT-RB router. It can NOT be used on the same MS/TP network with devices such as RTU Open controllers as they do not support this baud rate.
Kanggo konfigurasi Baud Rate lan Alamat MAC, navigasi menyang Setelan BAS ing Antarmuka pangguna nggunakake Menu / Setelan / Setelan Jaringan / BACNET. Waca Fig. 3.

CATETAN: You must cycle power after changing any Network Settings. SystemVu can be connected to the following devices
- All i-Vu BACnet MS/TP routers
- All current i-Vu CCN devices
- Third-party BACnet MS/TP routers
- System Touch over MS/TP
- Equipment Touch over Rnet
- Carrier Rnet Zone Sensors
CATETAN: SystemVu is a BACnet MS/TP master controller. Valid MAC addresses for master nodes are 0 – 127.
CATETAN: If SystemVu cannot be communicated with over BACnet, then ensure that the protocol has been correctly set and the controller has been power cycled if the protocol settings were changed.
INTEGRASI liwat BACNET MS / TP
- In general, all wiring and installation techniques should follow the Open Controller Network Wiring Guide, Catalogue No. 11-808-461-01, instructions. However, please note the following details and exceptions that MUST be observed on networks containing SystemVu controllers.
Kabel Komunikasi lan Kabel
- Kabel lan kabel komunikasi sing digunakake ing jaringan bisa nyebabake kinerja komunikasi jaringan liwat kabel kasebut. Tindakake rincian sing ditampilake ing Tabel 1 minangka praktik paling apik babagan kabel ing jaringan MS/TP BACnet.
Tabel 1 — Spesifikasi Wiring BACnet MS/TP

CATATAN (S)
- Merek dagang lan logo pihak katelu minangka properti saka pihak sing duwe.
KABEL KABEL KOMUNIKASI
- Partially cut, then bend and pull off 1 in. of the outer jacket of the cable(s). Do not nick the inner insulation. See Fig. 4.
- Strip about 0.25 in. (0.6 cm) of the inner insulation from each wire. See Fig. 4.
- If wiring two cables to the controller, twist together the shield wires from both cables.
- Insert the wires into the appropriate terminal block (see Figs 7 and 8 on page 6). Take care that the drain wire is electrically isolated, where exposed.
- All connections should be made with power turned off to all the network devices and SystemVu controllers.

AWAS
POSSIBLE COMMUNICATIONS FAILURE
- Do not allow more than 0.125 inch (0.3 cm) bare communication wire to protrude. See Fig. 5.
- If bare communication wire contacts the cable’s foil shield, shield wire, or a metal surface other than the terminal block, communications may fail.
- Best practice is to tape wires up to the BAS plug to prevent contact with any metal. See Fig. 6.

CATETAN: Do not ground the shield to earth ground or to the controller’s power ground. The PROT485 and the individual controllers allow the shield to float a limited amount so that there are no ground loops. If the voltage ing tameng dadi gedhe banget, relatif kanggo lemah bumi, banjur keluwihan voltage getihen karo piranti protèktif ing PROT485 utawa ing pengontrol.
Desain Jaringan
Kanthi pengontrol bias lokal, miturut standar RS-485, jumlah maksimal sing disaranake simpul saben segmen / batang gumantung saka baud rate jaringan.
- 38,400 baud = maksimal 15 simpul lan router
- 76,800 baud = maksimal 31 simpul lan router
Please note that the SystemVu controller is a LOCALLY biased device as opposed to the OPEN product line, which are NETWORK biased device.
- Therefore, the BT485 device is NOT used in a SystemVu-only network, and NOT used in a network composed of SystemVu and OPEN products together.
- In addition, the end-of-line / end-of-net switches on OPEN products and routers are NOT used with SystemVu controllers on the bus. Since these switches may also add network biasing, they are not needed with a locally biased product. There are no end-of-line switches on SystemVu products.
- CATETAN: Wigati: Resistor 120 Ohm kudu digunakake kanggo mungkasi bus ing ujung loro miturut syarat standar RS-485. Piranti TERM485 dianjurake.
- With careful wiring practices, one network segment can use up to 4,000 feet of network wire. However, the best results are achieved when the total wire length on a trunk is limited to 2000 feet.
- In addition, the use of a repeater (the REP485 is the only currently allowed repeater) for network segments over 2000 feet of wire is encouraged, but not mandatory. Please refer to the Open Controller
- Network Wiring Guide for detailed REP485 installation instructions. Note that the REP485 counts as a node on both network segments it connects.
- Panggunaan piranti PROT485 dianjurake banget kanggo kabeh segmen jaringan kanthi pengontrol SystemVu. Mangga deleng Open Controller Network Wiring Guide kanggo rinci instruksi instalasi PROT485.
- Finally, please note that rigorous adherence to the wiring hygiene recommendations here and in the Open Controller Network Wir-ing Guide will produce the best network results.
- Pengontrol SystemVu kudu duwe kabel BAS sing disambungake menyang plus, minus, lan kabel tameng menyang COM minangka ditampilake ing Fig. 7 lan 8.


Topologi Jaringan
- All BACnet MS/TP networks should be wired in a true “daisy-chain” configuration.
- BACnet MS/TP network best practices dictate that the MAC ad-dressing of the nodes on the network should be sequential with the physical location of the units. For example, yen router iku simpul pisanan ing jaringan, kudu alamat MAC paling. Unit sabanjuré ing daisy-chain kudu alamat MAC siji nomer luwih, etc.
Grounding lan Polaritas
- Lemah bumi sing berkualitas penting kanggo njamin operasi unit sing tepat lan fungsi komunikasi BAS sing tepat.
- There is not one standard ground resistance threshold that is recognised by all agencies.
- However, the NFPA (National Fire Protection Association) and IEEE have recommended a ground resistance value of 5.0 ohms or less. The NEC has stated: “Make sure that system impedance to
- ground is less than 25 ohms specified in NEC 250.56.” In facilities with sensitive equipment, it should be 5.0 ohms or less. The telecommunications industry has often used 5.0 ohms or less as its value for grounding and bonding.
- If you suspect you may have grounding issues at a facility, specialised earth grounding testers are used by qualified electrical contractors to test for correct grounding.
- In addition, control power polarity should be maintained throughout the BAS network AND communication wiring polarity should be maintained as well. Per the recommendations in the Open Controller Network Wiring Guide regarding the PROT485, shield wires should NOT be grounded to any earth ground or to the controller’s power ground. The PROT485 and the individual control-lers allow the shield to float a limited amount so that there are no ground loops. If the voltage ing tameng dadi gedhe banget relatif kanggo lemah bumi, banjur keluwihan voltage getihen karo piranti protèktif ing PROT485 utawa ing pengontrol.
Segmentasi Paket
- Tumpukan BACnet sing digunakake karo produk SystemVu saiki ora ndhukung segmentasi paket.
- Segmentasi kudu dipateni ing piranti pihak katelu.
- Please be aware that the segmentation feature is NOT required for the current BTL (BACnet Testing Laboratories) certification.
i-Vu Integration Tips – Source Files lan Variasi Versi
- The current SystemVu products are compatible with i-Vu versions 7.0 and later. Older versions of i-Vu software may not work cor-rectly with current SystemVu products.
- Kabeh patch i-Vu saiki kudu diinstal nalika nyambung menyang produk SystemVu. Iki bisa dipikolehi saka bagean "Download Kontrol" saka HVACPartners utawa saka Kontrol Pembawa webbagean lunak situs.
- Asring perlu kanggo nambah sumber SystemVu kanthi manual files to the i-Vu server and place them into the appropriate folder.
- Elinga yen sumber files dumunung ing HVACPartners (Saiki dumunung ing TAB Dhukungan> POST SALE Dhukungan> SERVICE SOFTWARE).
COV (Ganti Nilai) lan Router Pihak Katelu
- Fitur COV ing BACnet MS/TP digunakake sacara ekstensif dening sawetara vendor pihak katelu.
- Nanging, SystemVu mung ndhukung sawetara titik COV sing winates. Panjaluk router kanggo titik COV sing ora didhukung dening pengontrol SystemVu bisa nyebabake kesalahan jaringan lan kinerja jaringan sing ora apik.
- Mateni fungsi COV ing piranti pihak katelu bisa dadi alat sing migunani nalika ngatasi masalah lalu lintas jaringan.
- Situs proyek utawa pelanggan tartamtu mbutuhake fitur COV digunakake.
- Yen ngono, Tabel 2 nuduhake titik COV sing tepat sing didhukung dening pengontrol SystemVu.
Tabel 2 — Obyek SystemVu Ndhukung COV-Guide
| DESKRIPSI | BACNET OBJEK NAME | BACNET TYPE | BACNETINSTANCE NUMBER | DESKRIPSI BACNET |
| Mode peralatan linkage dilaporake menyang zona. | lnk_mode | saka: | 261 | Mode Peralatan Linkage |
| A discrete hardware input that when configured for use can beused as part of the logic that determines the occupied or unoccupied state of the control. | remocc | BV: | 29 | RemoteOccupancy Switch |
| Indoor Air Quality that has been resolved from all of the possible indoor air quality sources available in the system. | iaq | saka: | 1009 | Tingkat Kualitas Udara ing njero ruangan |
| Kualitas udara njero ruangan sing ditampa liwat jaringan. | iaq_net | saka: | 7001 | Nilai IAQ jaringan |
| Tingkat Kualitas Udara Luar Ruangan (OAQ) (sensor). | oaq | saka: | 1012 | Tingkat Kualitas OA |
| Sensor Tingkat Kualitas Udara Luar Ruangan (OAQ). | oaq_net | saka: | 7002 | Nilai OAQ jaringan |
| Kelembapan Relatif ing njaba sing wis ditanggulangi saka kabeh sumber kelembapan udara ruangan sing kasedhiya ing sistem kasebut. | oarh | saka: | 1022 | Kelembapan Relatif OA |
| Sensor jaringan kelembapan relatif udara ruangan. | oarh_net | saka: | 7003 | Nilai OARH Jaringan |
| Suhu Udara ing njaba sing wis ditanggulangi saka kabeh sumber suhu udara ruangan sing kasedhiya ing sistem kasebut. | oa_temp | saka: | 1003 | Suhu Udara Luar Ruangan |
| Suhu udara njaba saka jaringan BMS. | oat_net | saka: | 7007 | Nilai OAT Jaringan |
| Outdoor Air CFM sing ditampa liwat jaringan. | ocfm_net | saka: | 371 | Nilai OACFM jaringan |
| Outdoor fan: High temperature override. | odfhtovr | saka: | 9066 | Suhu Override ODF |
| Return Air Relative Humidity is the result of the engineering conversion performed on the sensor in the return air ductwork. | rarh | saka: | 30 | RA Asor relatif |
| Relative Air Relative Humidity (RARH) Sensor read in from the network sensor. | rarh_net | saka: | 7004 | Nilai RARH jaringan |
| Return Air Temperature that has been resolved from all of the possible return air temperature sources available in the system. | ra_temp | saka: | 1010 | Bali Suhu Udara |
| Bali suhu udhara saka jaringan. | rat_net | saka: | 7005 | Suhu Udara Bali Jaringan |
| Supply Air Temperature that has been resolved from all of the possible supply air temperature sources available in the system. This represents the temperature of the air being output from the packaged unit. | sa_temp | saka: | 1008 | Suplai Suhu Udara |
| Space Relative Humidity (SPRH) Sensor read in from the network sensor. | sprh_net | saka: | 376 | Nilai SPRH Jaringan |
| Space Temperature is a legacy point that has typically been used for writing space temperature values over a CCN network. | space_temp | saka: | 2007 | Nilai Temp Space Pilot |
| Temperatur Ruang yaiku maca saka jaringan. | spt_net | saka: | 7006 | Nilai Suhu Ruang Jaringan |
| Maca Suhu Ruang Tutul Sistem saka jaringan. | stst_net | saka: | 8023 | Nilai Suhu Tutul Sistem |
Tabel 3 - Singkatan Example saka Point List
| POINT DESCRIPTION | POINT ACESS | UNIT | BACnet OBJEK NAMA | ID BACnet | RANGE VALUE | CNN POINT EQUIVALENT |
| BACnet device for IAQ | R/W | devlag | AV:8001 | 0 nganti 4194303 | DEAVIAQ | |
| BACnet device for OAQ | R/W | devoaq | AV:8002 | 0 nganti 4194303 | DEVOAQ | |
| BACnet device for OARH | R/W | devoarh | AV:8004 | 0 nganti 4194303 | DEVOARH | |
| BACnet device for OAT | R/W | devoat | AV:8003 | 0 nganti 4194303 | DEVOAT | |
| BACnet device for RARH | R/W | devrarh | AV:8005 | 0 nganti 4194303 | DEVRARH | |
| BACnet device for RAT | R/W | devrat | AV:8006 | 0 nganti 4194303 | DEVRAT | |
| BACnet device for SPRH | R/W | devsprh | AV:8028 | 0 nganti 4194303 | DEVSPRH | |
| BACnet device for SPT | R/W | devspt | AV:8007 | 0 nganti 4194303 | DEVSPT |
APDU Timing, Polling Rates, etc. with Third-Party Routers
- Ora umum yen sampeyan kudu nyetel sawetara setelan router sing beda-beda gumantung saka proyek menyang proyek.
- Sayange, ora ana nilai "diset ing watu" sing bisa digunakake ing saben proyek.
- Wigati dimangerteni manawa sawetara nilai kasebut kalebu tarif wektu entek APDU, tarif polling, lan tarif wektu entek NPDU.
- In general, longer polling rates for BACnet objects are to be preferred (polling too frequently increases bus traffic). Polling/refresh rates should not be set below every 30 seconds. It is best to keep the polling/refresh rates between 1 and 5 minutes. In general, the recommendations in Othe APN022 application tip regarding read and write rates should be observed.
- It is a best practice to set timeout rates, such as APDU timeout rates at the highest timeout rate of any device on the network. Many devices default at 3000 milliseconds. SystemVu is defaulted to 6000ms and cannot be changed. When applying SystemVu controls on a BACnet bus with other devices, all devices should be set to match SystemVu at 6000ms. The SystemVu APDU segment length is fixed at 480 bytes. Since the BACnet stack used for SystemVu controllers does NOT support packet segmentation, some third-party routers may need to have the APDU segment size or RPM “chunking” or “bin packing” algorithms mare manually adjusted to properly work with features such as Read Property Multiples.
Frame Rate lan Router Pihak Katelu
- Many third-party vendors default their router “MS/TP Max Info Frames” value to “100”. This is too high for SystemVu nodes – a value of “20” will provide a more stable network.
- All legacy production SystemVu software versions have the “Max Info Frames” value default to “10”. Older versions defaulted to “1” which can cause network issues. If a network with an older SystemVu
- units is experiencing issues; upgrading to current production software is recommended.
- Unit produksi A2L saiki duwe tingkat pigura sing bisa diatur lan nilai master maksimal.
INTEGRASI SYSTEMVU karo SYSTEM TOUCH liwat MS / TP PORT
Apa Sistem Tutul
- The System Touch is a touchscreen device with a color LCD dis-play that provides as a user interface to controllers on a single BACnet network. The System Touch has built-in temperature and humidity sensors. These values can be read by controllers to con-trol equipment. You can also wire an external thermistor to the System Touch and use its value instead of the built-in temperatur e sensor’s value.
For more details about the System Touch, refer the below docu-ments available on HVACPartners or the Carrier Controls Websitus
- System Touch Installation and Setup Guide
- Pandhuan Pangguna Tutul Sistem
- System Touch Product data sheet.
Steps to Connect SystemVu and System Touch over MS/TP Port
NOTE: You must configure the SystemVu Communication Protocol to ‘BACnet’ for proper System Touch interface with the SystemVu controller and System Touch device.
- Update the SystemVu to the latest firmware.
- Enable BACnet in the BAS Protocol (Menu > Settings > Network Settings).
- Connect System Touch to SystemVu over MS/TP as shown in Fig. 9.
- Once the connection is established, click on ‘Setup’ of System Touch from the home screen.
- Enter the password (the default password is ‘admin’)
- Click on the “Discovery”. Verify System Touch tries to communicate with SystemVu and displays the SystemVu controller.
- For more details about the System Touch, refer to the documents mentioned above.
Using System Touch’s Temperature and Humidity Sensors
Sensor Suhu lan Sensor Kelembapan Sistem Tutul bisa dijaluk dening pengontrol SystemVu. Kanggo njaluk nilai kasebut saka Sistem Tutul, kita kudu ngatur kaya ing ngisor iki.
- Connect the System Touch and the SystemVu Board as described above.
- On System Touch, navigate to Setup > Touchscreen Setup > Sensor Setup.
- Select “Internal” and “Deg F” as shown in Fig. 10.
Using UI on the SystemVu board, navigate to SETTINGS > NETWORK SETTINGS > BACNET > SYSTEM TOUCH.- Set DEVICE INSTANCE to System Touch Device Instance.
- Set POLLING Rate (System Touch Poll Rate) to at least 10. NOTE: The default is 0 to prevent scanning.
- Set SPACE TEMP AI = 1.
- Set SPACE RH AI = 4.
- With these settings, SystemVu Board will poll the Space Temperature and Humidity Sensor values from System Touch.
- For more information about the default value and the configuration values, refer to “APPENDIX A” in the Controls and user manual document for the SystemVu unit you are using.
SYSTEMVU INTEGRASI WITH EQUIPMENT TOUCH liwat RNET
Apa iku Equipment Touch
- The Equipment Touch is a touchscreen device with a colour LCD display that you connect to the SystemVu controller to view utawa ngganti nilai properti, jadwal peralatan, view tren lan weker, lan liyane, tanpa kudu ngakses server i-Vu.
For more details about the Equipment Touch, refer to the documents below available on HVACPartners or the Carrier Controls Websitus.
- Equipment Touch User Guide
- Equipment Touch Installation and Setup Guide
- i-Vu Equipment Touch Product Data Sheet
Steps to Connect SystemVu and Equipment Touch over Rnet Port
CATETAN: You must configure the SystemVu Communication Protocol to ‘BACnet’ for proper Equipment Touch interface with th e SystemVu controller and Equipment Touch device.
- Update the SystemVu to latest firmware.
- Enable BACnet in the BAS Protocol (Menu > Settings > Network Settings).
- Connect the Equipment Touch to SystemVu over Rnet as shown in Fig. 11.
- Once the connection is established, Equipment Touch will start uploading the touch file saka piranti SystemVu, minangka ditampilake ing Fig. 12.


- After successful upload, Equipment Touch displays the following screen (Fig. 13).

- For more details about the Equipment Touch, see the Equipment Touch Installation and Setup Guide.
Using Equipment Touch Temperature and Humidity Sensors
Sensor Suhu Tutul lan Kelembapan Peralatan bisa digunakake dening pengontrol SystemVu. Kanggo njaluk nilai kasebut saka Equipment Touch, kita kudu ngatur kaya ing ngisor iki.
- Connect Equipment Touch and SystemVu Board as described above.
- On Equipment Touch, navigate to Setup > Touchscreen Setup > Sensor Setup.
- Select the check box ‘Enable Transmit’ for both ‘Tempera-ture Sensor’ and ‘Humidity Sensor’ (see Fig. 14).
With these settings, Equipment Touch will transmit the Temperature Sensor and Humidity Sensor Values to SystemVu.
PROSES UPGRADE FIRMWARE kanggo TOUCH PERALATAN / TOUCH SISTEM
Langkah Update Firmware
- Create a folder on the flash drive called “touch”, then put the ETxxxxx.hex or STxxxxx.hex file ing folder.
- Plug the flash drive into the Equipment/System Touch’s USB port.
- From the System Screen, touch Setup > Touchscreen Setup > Reload Firmware.
- Pesen bebaya katon. Tutul Ya kanggo nerusake.
- The following series of messages appears:
- Verifying Firmware Image.
- Reading Firmware image from USB.
- Installing Application.
- Verifying Firmware Image.
- Aftera successful firmware update, remove the flash drive.
SYSTEMVU INTEGRASI WITH ZS SENSOR liwat RNET
Sensor ZS Kab
- ZS Sensors are thermistor-based temperature sensors that can op-tionally sense humidity, motion, and either CO2 or VOC. ZS Sen-sors communicate with the HVAC system through the Rnet.
Fungsi Sensor ZS ditemtokake dening:
- The sensor models
- The sensor’s sensing capabilities (temperature, humidity, motion, CO2, VOC)
- The control program that runs the associated equipment’
ZS Sensors are wired to the Rnet port on SystemVu controllers. For more information about Zone Sensor, refer to the documents available on HVACPartners or the Carrier Controls Websitus.
- ZS Sensors User Guide
- ZS Sensors Installation Guide
Steps to Connect SystemVu and ZS Sensor Over Rnet Port
- Each ZS Sensor connected via the Rnet port must have a unique address, but addresses do not have to be sequential.
- Open the hinged cover on the sensor enclosure, and then use the DIP switches to set an address from 0 to 14. (1 is factory default.) Each DIP switch has the value shown in Figure 15 below. Turn on as many DIP switches as you need so that their total value equals the address.
EXAMPKOWE: DIP switches 1 and 4 below are on. Their values (1 + 8) total 9, so the sensor’s address is 9.
- . Connect the SystemVu Controller and Zone Sensor over the Rnet Port as shown in Fig. 16-17.
- On SystemVu User Interface, navigate to SETTINGS / NET-WORK SETTINGS / ZS SENSOR CFG and set the ZS Sen-sor address (see Fig. 18).
- SystemVu supports up to 5 Zone Sensors which can be connected over Rnet Port (see Fig. 19).
- Please note that there is a 500mA VA limit for the Rnet plug. Check the total VA consumption of the sensors prior to connecting them to the SystemVu board.





Konektor SystemVu RNET
INDIKATOR KEGIATAN DEWAN
LED Status Abang
Operasi sing tepat saka Papan SystemVu bisa dipriksa kanthi visual kanthi ndeleng LED status abang (ndeleng Fig. 20).

Tabel 4 nyedhiyakake informasi babagan LED Status.
|
Kondisi LED Status Merah
|
Status Piranti Lunak Papan
|
|
OFF terus-terusan
|
The board is unpowered or the power supply is defective
|
|
KEDIPUT ON 200 ms, OFF 200 ms
|
Board is in Bootloader mode
|
|
KEDIPUT ON 1000 mbak, OFF 1000 ms
|
The boot loader is not running, application software is running
|
|
ON terus-terusan or FLASHING at sembarang other frequency
|
The board or software is defective
|
LED Status Hijau
- The SystemVu controller has one Green LED. This LED (indicates Local Equipment Network) should always be blinking whenever power is ON. If LENLED is not blinking, check LEN connection for
- potential communication errors (MBB J15, J16, J17, and J2 on the Display).
- LED Status Kuning
- Yellow LED is used to indicate Building Automated Systems (BAS) communication activity. The LED will blink when the MBB transmits a message on the BACnet bus.
NGANGGO MASALAH BACNET MS/TP
Konfigurasi BACnet MS/TP
- SystemVu can use the BACnet MS/TP protocol for communications. This section in the document contains Carrier’s recommendations for configuring and wiring an MS/TP network that will provide the best network performance with Carrier controllers. However, Carrier controllers will work on any BACnet-compliant MS/TP network. Controllers can communicate on an MS/TP network at 9600 bps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 76.8 kbps, or 115.2 kbps.
- For configuring SystemVu BACnet Baud Rate, navigate to the menu below in the user interface and select the Baud Rate. UI Menu > SETTINGS / NETWORK SETTINGS / BACNET
- Wigati dimangerteni sumber kasebut files dibutuhake kanggo deteksi tepat Unit SystemVu dening sistem i-Vu. Sumber files are included in cumulative patches, OR can be manually imported into i-Vu. Source files and the process for importing them are located on HVACPartners.
i-Vu MODSTAT
- For additional debugging on iVu systems, use the MODSTA T command in i-Vu which, when requested, will trigger the System Software Information along with BACnet Firmware version as shown in the images below.
- Select the Controller listed under Router (see Fig. 21).
- Right click and select the MODSTAT (Module Status) command. (see Fig. 22). A new Pop up window will come with the list of Controller Software and BACnet firmware versions as shown in Fig. 23.

Pengalamatan pengontrol
- Each SystemVu controller on the MS/TP network must have a unique BACnet MS/TP MAC address, which is set by the User In-terface Menu. Valid addresses are 1-99.
- BACnet MS/TP network best practices dictate that the MAC ad-dressing of the nodes on the network should be sequential with th e physical location of the units. I.E. If the router is the first node on the
- network, it should have the lowest MAC address. The next unit on the daisy-chain should have a MAC address one number higher, etc.
Pedoman ngatasi masalah
- Yen controller SystemVu ora dideteksi liwat MS / jaringan TP, verifikasi kabeh setelan konfigurasi kaya Baud Rate, alamat MAC lan setelan Protokol BAS. Ing jaringan i-Vu, priksa manawa sumber files
- have been manually imported.
- NOTE: Use the same polarity throughout the network. Also, use a 120-ohm resistor at each end of the network.
- Network troubleshooting needs to be deliberate and sequential. In the event of rolling communication failures or no communications at all, the best approach is to start with the physical layer, then
- progress to the network layer, and finally the application layer.
LAPISAN FISIK
- The use of an oscilloscope as described in the Open Controller Network Wiring guide is always the first step. If your wave-forms are not clean, packet collisions will occur, which will cause losses of communication. Waveforms should look similar to the one shown in Fig. 24, NOT like the distorted (noisy ) waveform shown in Fig. 25.

- Sawetara faktor bisa nyebabake distorsi gelombang ing lapisan fisik. Kebersihan kabel sing kurang apik, segmen kabel sing rusak, sirkuit transceiver RS-485 sing rusak ing papan individu, lan gangguan listrik saka lingkungan "rame" mung sawetara masalah sing bisa nyebabake distorsi lapisan fisik. Ngisolasi bagean saka segmen jaringan kanthi misahake bis komunikasi dadi setengah bola-bali, nalika mboseni, minangka teknik paling apik kanggo ngisolasi cacat lapisan fisik.
- Please note that collisions caused by incorrect network software settings can also lead to distorted waveforms. While not as common as physical layer defects, this should be taken into consideration – see section addressing the network layer.
- Priksa manawa kabel sing bener digunakake lan disambungake kanthi bener ing saben piranti lan router. Resistor terminasi kudu ana ing wiwitan lan pungkasan saben segmen bis. Priksa manawa resistor bias jaringan ora digunakake amarga SystemVu wis bias lokal. Item kasebut minangka masalah sing paling umum ditemokake nalika ngatasi masalah.
LAYER JARINGAN
- Once any physical layer issues are resolved, the next step is to analyse the network layer. The use of network bus traffic monitoring tools is very valuable when trying to isolate network problems. There are a number of tools available, such as Wireshark®1, which allows the diagnosis of issues such as COV over polling, APDU timing, duplicate MAC addresses, etc.
- The most common network layer issues are with APDU timeout, BACnet point writes, COV increments, and segmentation settings. SystemVu products are hard-set to a 6000ms APDU timeout; all devices on the same bus should be set to 6000ms for best results. COV should be disabled unless clearly being used. If COV is being used, ensure the refresh increments are set so that COV requests do not occur too frequently. The goal should be for COV requests to occur no more often than every 60 seconds. Ensure BACnet writes/refresh or broadcast rates are reasonable and not occurring too frequently. Usually, point writes should not be greater than once per minute. Lastly, ensure packet segmentation is disabled on the network bus.
APLIKASI LAYER
- Gumantung saka router sing digunakake, yen masalah lapisan fisik lan lapisan jaringan wis dirampungake, studi rinci babagan weker lan tandha sing ana ing router bisa mbukak wektu, sumber. file, lan masalah piranti lunak. Praktek paling apik kanggo kabeh router lan piranti ing jaringan duwe patch perangkat kukuh sing dianyari lan patch kumulatif sing ditrapake.
DAFTAR POINT NETWORK FOR BACNET
- Daftar Poin SystemVu BACnet
- The BACnet point list may vary from product to product and software version to software version of SystemVu. For the specific list of supported BACnet Points, refer to “APPENDIX E – BACNET
- POINTS LIST” in the Controls document for the SystemVu product you are using
Dhaptar Alarm SystemVu
- The alarms list may vary from product to product and software version to software version of SystemVu. For the list of alarms supported, refer to the Controls document for the SystemVu product you are using.
Pitakonan
Can untrained personnel perform maintenance on the SystemVu controller?
Untrained personnel can perform basic maintenance tasks such as cleaning coils and filters, but all other operations should be handled by qualified service personnel.
Dokumen / Sumber Daya
![]() |
Pembawa SYSVU SystemVu Controller [pdf] Pandhuan pangguna SYSVU-001-SUPP, SYSVU SystemVu Controller, SYSVU, SystemVu Controller, Controller |

