PAMBUKA

LCT-485 minangka modul antarmuka jaringan RS-485 kanggo sensor suhu inframerah ExTemp.
Unit iki, nalika disambungake ing sisih aman saka isolator Intrinsically Aman utawa alangi, ngidini suhu diukur diwaca saka sensor ExTemp liwat protokol Modbus RTU mbukak. Parameter konfigurasi sensor uga bisa ditliti lan diganti.

Saben unit LCT-485 ngidini komunikasi karo siji sensor ExTemp. Isolator utawa penghalang sing dipilih kudu kompatibel karo transmisi data digital sing ditumpangake liwat sinyal analog 4-20 mA. Iki ngidini LCT-485 komunikasi digital karo ExTemp.

LCT-485 minangka piranti Budak; munggah 224 piranti bisa disambungake menyang Modbus Master pihak katelu.

INFORMASI PENTING kanggo nggunakake:

LCT-485 ora cocok digunakake ing wilayah sing mbebayani. MUNGKIN kudu disambungake ing wilayah sing aman, lan dilindhungi dening isolator utawa penghalang Intrinsik Aman sing cocog.
Aja nyoba ndandani unit sing rusak. Hubungi vendor kanggo ngatur bali.

NOMER MODEL LCT-485
RS-485 modul antarmuka jaringan kanggo sensor ExTemp

SPESIFIKASI

  • Pemasangan rel DIN (35 mm)
  • Komunikasi Terisolasi RS-485 Modbus RTU Budak
  • Ukuran 114(d) x 18(w) x 107(h) mm
  • Sambungan Terminal sekrup kanggo RS-485, daya, lan loop sensor (cocok kanggo konduktor 0.2 nganti 2.5 mm²)
  • Pasokan voltage 24 V DC (6 V DC min / 28 V DC maks)
  • Max tarik saiki 50 mA
  • Baud rate 1200 bps kanggo 57600 bps, dideteksi kanthi otomatis
  • Paritas format bit: Ganjil / Genap / Ora Ana
  • Stop bit: 1 utawa 2
  • Suhu sekitar -20°C nganti 70°C
  • Loop resistor 270 Ω, dibangun ing
  • Kesesuaian EMC BS EN 61326-1:2013, BS EN 61326-2-3:2013
  • Maks. Jumlah Piranti Nganti 224 x LCT-485 piranti budak saben Modbus Master
  • Reply Delay (ing 9600 baud) ExTemp register: 1 s max LCT-485 registers: 30 ms (single register) 50 ms (whole address space)

PREPARASI INSTALASI

Suhu sekitar
Antarmuka jaringan iki dirancang kanggo beroperasi ing suhu sekitar saka -20°C nganti 70°C.
Gangguan Listrik
Kanggo nyuda gangguan elektromagnetik utawa 'gangguan', antarmuka jaringan kudu dipasang adoh saka motor, generator lan liya-liyane.
Wiring
Priksa jarak antarane isolator utawa penghalang Intrinsik Aman, Master Modbus, lan antarmuka jaringan LCT-485. LCT-485 cocog karo standar industri kanggo kompatibilitas elektromagnetik kanthi kabel nganti 30 m sing dipasang ing sisih RS-485, lan kabel 30 m ing sisih 4-20 mA.

Power Supply
Priksa manawa sampeyan nggunakake sumber daya DC 24 V.

INSTALASI MEKANIKAL
Pemasangan
LCT-485 dirancang kanggo dipasang ing rel DIN 35 mm liwat klip sing kalebu.

INSTALASI LISTRIK

LCT-485 ora disertifikasi kanggo digunakake ing wilayah sing mbebayani. Iku mung kudu disambungake ing sisih aman saka isolator utawa alangi Aman Intrinsik.

Sambungan karo Isolator Aman Intrinsik

Antarmuka Jaringan CALEX LCT-485 kanggo Sensor Suhu Inframerah ExTemp-1

Sambungan karo Zener Barrier

Antarmuka Jaringan CALEX LCT-485 kanggo Sensor Suhu Inframerah ExTemp-2

  • Maks. dawa kabel 30 m
  • Maks. dawa kabel 30 m (nggunakake RS-485 Modbus repeater ngidini kabel maneh ing sisih Master)

Terminal meneng

Antarmuka Jaringan CALEX LCT-485 kanggo Sensor Suhu Inframerah ExTemp-3

Isolator utawa Barrier Intrinsik Aman

LCT-485 ora kudu disambungake langsung menyang sensor ExTemp. Sampeyan mung kudu digunakake bebarengan karo isolator Intrinsik Aman utawa penghalang zener.
Isolator utawa penghalang kudu bisa ngliwati sinyal 4-20 mAlog analog kanthi sinyal digital sing ditumpangake kayata Frequency Shift Keying (FSK).

Model sing cocog kalebu:

  • Model isolator MTL5541
  • Model alangi MTL7706+
    Iki diprodhuksi dening Measurement Technology Ltd (www.mtl-inst.com).

Sambungan - Jaringan Modbus RS-485
Kabeh sambungan ing ngisor iki ana ing sisih aman saka isolator Intrinsik Aman utawa alangi.

Antarmuka Jaringan CALEX LCT-485 kanggo Sensor Suhu Inframerah ExTemp-4

Priksa manawa jarak ing antarane saben piranti lan bus jaringan sabisa.
Cathetan
LCT-485 cocog karo standar industri kanggo kompatibilitas elektromagnetik kanthi kabel RS-30 nganti 485 m. Yen jaringan kudu mlaku kanthi jarak sing luwih dawa, panggunaan RS-
485 repeater dianjurake.
Priksa manawa kabeh sambungan wis bener sadurunge nggunakake daya.

OPERASI

Sawise sensor ana ing posisi, isolator utawa alangi Intrinsik Aman sing cocog kudu disambungake lan dikonfigurasi.
Nalika sambungan daya lan kabel sing cocog wis aman, sistem siyap kanggo operasi terus-terusan kanthi ngrampungake langkah-langkah prasaja ing ngisor iki:

  1. Nguripake sumber daya
  2. Nguripake indikator (yen dipasang)
  3. Kirim pesen test kanggo konfirmasi komunikasi karo LCT-485 apik (disaranake maca saka alamat 0xD0, alamat Modbus Slave)
  4. Kirim pesen tes kanggo konfirmasi komunikasi karo sensor ExTemp apik (disaranake maca saka alamat 0x08, Suhu Obyek Disaring)
  5. Maca utawa ngawasi suhu

MODBUS liwat LINE SERIAL (RS-485)

Antarmuka
Baud rate 1200 bps nganti 57600 bps, dideteksi kanthi otomatis
Format (Bit) 8 data, ganjil / malah / ora paritas, 1 utawa 2 mandeg bit
Tundha balesan (ing 9600 baud) Register ExTemp: 1 s maks LCT-485 register:
30 ms (single register)
50 ms (kabeh spasi alamat)

 

Didhukung Fungsi
Waca register (R) 0x03, 0x04
Tulis register tunggal (W) 0x06
Tulis sawetara register (W) 0x10

DAFTAR DAFTAR MODBUS (DAFTAR EXTEMP)

alamat R/W Katrangan Default nilai Min. nilai Maks. nilai
0x00 (0) [LENGKAP]
0x01 (1) R ID Sensor (dawa: 2 tembung): Bit 0..19 - Nomer seri

Bits 20..23 - Lapangan Sensor saka view (0=2:1, 1=15:1, 2=30:1)

Bit 24..27 – Tipe sensor (A= ExTemp) Bit 28..31 – Reserved

0x03 (3) R Suhu obyek sing ora disaring
0x04 (4) R Suhu sensor
0x05 (5) R Suhu ditahan maksimal
0x06 (6) R Suhu ditahan minimal
0x07 (7) R Suhu rata-rata
0x08 (8) R Suhu obyek sing disaring
0x09 (9) [LENGKAP]
0x0A (10) R/W Setelan emisivitas (1 LSB = 0.0001) 9500 2000 10000
0x0B (11) R/W Suhu sing dibayangke 0
0x0C (12) R/W Status sensor:

Bits 0..1 - Reserved

Bit 2 – Tahan pangolahan aktif (1) / mati (0) Bit 3 – Tahan puncak (1) / lembah (0)

Bits 4..6 - Reserved

Bit 7 – Kompensasi energi sing dibayangke aktif (1) / mati (0)

Bits 8..15 - Reserved

3
0x0D (13) R/W Periode rata-rata (1 LSB = 250 ms) 1 0 240
0x0E (14) R/W Periode ditahan (1 LSB = 250 ms) 1 0 4800
0x0F (15) R/W Suhu ing 4mA 0 -200 9000
0x10 (16) R/W Suhu ing 20mA 5000 800 10000
0x11 (17)

kanggo

0xCF (207)

[LENGKAP] -0

DAFTAR DAFTAR MODBUS (DAFTAR LCT-485)

alamat R/W Katrangan Default nilai Min. nilai Maks. nilai
0xD0 (208) R/W Alamat budak modbus* 1 1 247
0xD1 (209) R/W Baud rate* 9600 400 60000
0xD2 (210) R/W Paritas (0 = ora ana, 1 = ganjil, 2 = genap)* 0 0 2
0xD3 (211) R/W Mungkasi bit

(1 = 1 stop bit, 2 = 2 stop bit)*

0 0 1
0xD4 (212) R/W Mode konfigurasi bus otomatis (ABC).

(0 = mati, 1 = aktif, 2 = nggunakake baud rate paling cedhak**)

1 0 2
0xD5 (213) [LENGKAP]
0xD6 (214) R/W Register fungsi

(1=muat maneh, 0x5555=reset pabrik) Dibusak kanthi otomatis

0 0 65535

Yen diganti, nilai anyar mung bakal ditrapake sawise daya diuripake, utawa sawise "1" ditulis menyang Function Register 0xD6 Mode "2": sawise ndeteksi tingkat baud, LCT-485 banjur milih tingkat baud "dikenal" paling cedhak. saka nilai umum ing ngisor iki: 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400,57600 (ndeleng "Mode Konfigurasi Bus Otomatis" ing ngisor iki)

Cathetan

  1. Kabeh suhu ana ing sepuluh derajat C
  2. Kabeh operasi nulis disimpen ing memori non-molah malih
  3. Kanggo informasi luwih lengkap, waca http://www.modbus.org/specs.php
  4. Gunakake alamat 255 kanggo komunikasi karo sensor unit LCT-485 sing disambungake (pastikan mung siji unit LCT-485 sing disambungake)
  5. Gunakake alamat 0 kanggo siaran menyang kabeh unit LCT-485 sing disambungake (ora ana tanggapan)

KONFIGURASI BUS OTOMATIS (ABC) MODE
LCT-485 kanthi otomatis bisa ndeteksi baud rate bener, paritas lan setelan bit mandeg digunakake dening Master Modbus. Mode iki diaktifake kanthi gawan. Kanggo nggunakake mode ABC:

  1. Konfigurasi Modbus Master supaya bola-bali ngirim pesen Waca menyang LCT-485. Priksa manawa wektu entek Modbus Master ora luwih cendhek tinimbang wektu tundha balesan unit LCT-485 (1 detik). Priksa manawa Modbus Master bakal terus nyoba ngirim pesen sawise akeh wektu entek.
  2. LCT-485 bakal ngrungokake pesen saka Master Modbus. Kaping pisanan bakal nggunakake setelan sing dipilih kanggo tingkat baud, bit mandeg lan paritas. Yen ora ana setelan iki sing wis dikonfigurasi, nilai standar bakal digunakake.
  3. Sawise sawetara pesen gagal, yen setelan sing dipilih ora bisa digunakake, LCT-485 bakal kanthi otomatis ngukur lan nyetel baud rate. Banjur bakal nyoba kabeh kombinasi setelan stop bit lan paritas nganti nemokake nilai sing bener.
  4. LCT-485 bakal ndeteksi nalika komunikasi apik karo Modbus Master wis ditetepake, lan mode ABC banjur bakal rampung. Nilai sing dideteksi kanthi otomatis bakal disimpen ing registrasi Modbus LCT-485. mode ABC ora bakal diwiwiti maneh nganti daya wis cycled.
  5. Sampeyan bisa ngganti tingkat baud, paritas lan setelan bit mandeg kanthi nulis menyang ndhaptar Modbus. LCT-485 bakal nggunakake setelan anyar sawise daya wis cycled, utawa sawise "1" ditulis kanggo Fungsi Register 0xD6.

MODE PEMULIHAN
Yen setelan paritas, stop bit lan baud rate ilang utawa ora dingerteni, lan mode ABC "0" (Off), komunikasi bisa dipulihake kaya ing ngisor iki:
Konfigurasi Modbus Master supaya bola-bali ngirim pesen Waca nggunakake 9600 baud, ora paritas, 1 stop bit. Sawise pirang-pirang pesen, LCT-485 bakal bali menyang setelan kasebut nganti daya diuripake. Iki bakal ngidini setelan asli sing bener diwaca saka LCT-485. Setelan pemulihan iki ora disimpen, lan ora nimpa setelan sing wis ana.

PENTING

  • LCT-485 ora cocok digunakake ing wilayah sing mbebayani. MUNGKIN kudu disambungake ing wilayah sing aman, lan dilindhungi dening isolator utawa penghalang Intrinsik Aman sing cocog.
  • Aja ngoperasikake unit iki ing cedhak medan elektromagnetik sing kuwat (contone ing sekitar generator utawa pemanas induksi). Gangguan elektromagnetik bisa nyebabake kesalahan pangukuran.
  • Kabel kudu disambungake mung menyang terminal sing cocog.
  • Aja mbukak omah LCT-485. Iki bakal ngrusak unit lan mbatalake garansi.

MAINTENANCE
Perwakilan layanan pelanggan kasedhiya kanggo pitulung aplikasi, kalibrasi, ndandani, lan solusi kanggo masalah khusus. Hubungi Departemen Layanan sadurunge bali peralatan. Ing sawetara kasus, masalah bisa ditanggulangi liwat telpon. Yen piranti ora nindakake minangka ngirim, nyoba kanggo cocog gejala ing ngisor iki kanggo masalah. Yen tabel ora mbantu, hubungi kita kanggo saran luwih.

mecahaken masalah

Gejala Kemungkinan Penyebab Solusi
Ora ana komunikasi Ora ana daya kanggo piranti Priksa sumber daya lan kabel
Alamat Modbus Slave sing salah Priksa alamat Modbus Slave ing label ing sisih unit. Priksa manawa alamat Modbus Slave wis diganti.

Kanggo maca Alamat Budak liwat Modbus:

Kanthi mung siji unit LCT-485 sing disambungake menyang Modbus Master, maca saka register 0xD0 nggunakake alamat Slave 255 (iki bakal ngasilake respon saka alamat Slave)

Ora ana (utawa intermiten) komunikasi Konflik alamat Modbus Budak Priksa manawa saben unit ing jaringan duwe alamat Modbus Slave sing unik
Tata letak jaringan RS-485 salah Priksa manawa saben piranti RS-485 dipasang kanthi kabel sing paling cendhak menyang bus jaringan utama
Ora ana resistor terminasi Priksa manawa ana resistor terminasi 120 Ω sing disambungake ing antarane garis RS-485 + lan - ing Master Modbus, lan liyane ing mburi bis ing piranti paling adoh.

JAMINAN
Calex njamin saben instrumen sing diprodhuksi bebas saka cacat ing materi lan pengerjaan ing panggunaan lan layanan normal sajrone rong taun wiwit tanggal tuku. Jaminan iki mung ditrapake kanggo panuku asli miturut Katentuan lan Ketentuan Penjualan Calex.