iSMACONTROLLI SFAR-S-8AO Modbus I-O

SFAR-S-8AO Modbus I-O Module

SPECIFICATION

Power supply Voltage 10-38 V DC; 10-28 V AC
Power consumption 2,4 W @ 24 V DC 3 V A @ 24 V AC
Temperature inputs 6x Resistive or thermocouple configurable, resolution 0,1°C
Digital outputs 2xTransistor output max 55 V DC, max 500 mA
Galvanic isolation Max 1500 Vrms
Interface RS485, up to 128 devices on the bus
Baudrate From 2400 to 115200 bps
Ingress protection IP40 – for indoor installation
Temperature Operating -10°C – +50°C; Storage -40°C – +85°C
Relative humidity 5 to 95% RH (without condensation)
Connectors Max 2.5 mm2
Dimension 119,1 mm x 101 mm x 22,6 mm
Mounting DIN rail mounting (DIN EN 50022)
Housing material Plastic, self-extinguishing PC/ABS

JUMPER SETTING

Jumper Setting

TOP PANEL

Top Panel

ANALOG OUTPUTS

Analog Outputs
Analog Outputs

COMMUNICATION

Communication

POWER SUPPLY

Power Supply
Power Supply

WARNING

  • Note, an incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has been correctly wired before turning the power ON.
  • Before wiring, or removing/mounting the product, be sure to turn the power OFF. Failure to do so might cause electric shock.
  • Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
  • Do not disassemble the product. Doing so might cause electric shock or faulty operation.
  • Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere etc.). Failure to do so might cause fire or faulty operation.
  • Firmly tighten the wires to the terminal. Insufficient tightening of the wires to the terminal might cause fire

TERMINALS OF THE DEVICE

Power Supply

Registered access

Modbus

Dec Hex Register Name Access

Description

30001 0 0x00 Version/Type Read

Version and Type of the device

30002

1 0x01 Switches Read Switches state
40003 2 0x02 Baud rate Read & Write

RS485 baud rate

40004

3 0x03 Stop Bits & Data Bits Read & Write No of Stop bits & Data Bits
40005 4 0x04 Parity Read & Write

Parity bit

40006

5 0x05 Response Delay Read & Write Response delay in ms
40007 6 0x06 Modbus Mode Read & Write

Modbus Mode (ASCII or RTU)

40009

8 0x08 Watchdog Read & Write Watchdog
40033

32

0x20

Received packets LSR (Least Significant Reg.)

Read & Write

No of received packets

40034

33 0x21 Received packets MSR (Most Significant Reg.)

 

Read & Write

40035

34 0x22 Incorrect packets LSR Read & Write No of received packets with error
40036 35 0x23 Incorrect packets MSR

Read & Write

40037

36 0x24 Sent packets LSR Read & Write No of sent packets
40038 37 0x25 Sent packets MSR

Read & Write

30051

50 0x32 Outputs Read Bit is set if value ≠ 0
40053 52 0x34 Analog output 1

Read & Write

Value of Analog Output: in mV for voltage output (max 10240) in μA for current output 0 – 20 mA (max 20480) in ‰ for current output
4-20 mA (max 1000)

40054

53 0x35 Analog Output 2 Read & Write
40055 54 0x36 Analog Output 3

Read & Write

40056

55 0x37 Analog Output 4 Read & Write
40057 56 0x38 Analog Output 5

Read & Write

40058

57 0x39 Analog Output 6 Read & Write
40059 58 0x3A Analog Output 7

Read & Write

40060

59 0x3B Analog Output 8 Read & Write
40061 60 0x3C Default output 1 value

Read & Write

Default value of output set when power is on or when watchdog reset occurs

40062

61 0x3D Default output 2 value Read & Write
40063 62 0x3E Default output 3 value

Read & Write

40064

63 0x3F Default output 4 value Read & Write
40065 64 0x40 Default output 5 value

Read & Write

40066

65 0x41 Default output 6 value Read & Write
40067 66 0x42 Default output 7 value

Read & Write

40068

67 0x43 Default output 8 value Read & Write
40069 68 0x44 Output 1 setting

Read & Write

Setting of output mode: 0 – output disabled

  1. voltage outpu
  2. current output 0-20 m
  3. current output 4-20 mA

Caution! For the change to take effect, you must also set the jumper inside the module.

40070

69 0x45 Output 2 setting Read & Write

40071

70 0x46 Output 3 setting

Read & Write

40072 71 0x47 Output 4 setting

Read & Write

40073

72 0x48 Output 5 setting Read & Write
40074 73 0x49 Output 6 setting

Read & Write

40075

74 0x4A Output 7 setting Read & Write
40076 75 0x4B Output 8 setting

Read & Write

INSTALLATION GUIDELINE

Symbol Please read the instruction before use or operating the device. In case of any questions after reading this document, please contact the iSMA CONTROLLI Support Team
(support@ismacontrolli.com).

  • Symbol Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock.
  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.
  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.
  • Do not disassemble the product. Doing so might cause an electric shock or faulty operation
  • Symbol Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation.
  • Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.
  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.
  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.
  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.
  • Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices.
  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, which are dangerous for devices.
  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external communication. It is recommended to use galvanic separators.
  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.
  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.
  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Symbol Electrical installation of this product must be done in accordance with national wiring codes and conform to local regulations.

CUSTOMER SUPPORT

iSMA CONTROLLI S.p.A. – Via Carlo Levi 52, 16010 Sant’Olcese (GE) – Italy | support@ismacontrolli.com
www.ismacontrolli.com
Installation Guideline| 1
st Issue rev. 1 | 05/2022