il y a 5 jours — 8x Voltage or current output,. Resolution of the transmitter 14 bits. Range output. 0 V to 10 V; 0 mA to 20 mA; 4 mA to 20 mA. Isolation. Max 1000 V DC.

SFAR-S-8AO Installation instruction

Innon Support (http://support.innon.com)


File Info : application/pdf, 3 Pages, 423.69KB

PDF preview unavailable. Download the PDF instead.

SFAR-S-8AO Installation instruction
SFAR-S-8AO
JUMPER SETTING

Power supply
Supply output
Analog output
Range output Isolation Interface Baudrate Ingress protection Temperature Relative humidity Connectors Dimension Mounting Housing material

SPECIFICATION

Voltage

10-38 V DC; 10-28 V AC

Power consumption 1,25 W @ 24 V DC 1,5 VA @ 24 V AC

DC: 20-30 V 4,5 W; AC: 20-28 V 5 VA

8x Voltage or current output,

Resolution of the transmitter 14 bits

0 V to 10 V; 0 mA to 20 mA; 4 mA to 20 mA

Max 1000 V DC

RS485, up to 128 devices on the bus

From 2400 to 115200 bps

IP40 ­ for indoor installation

Operating -10°C - +50°C; Storage - 40°C - +85°C

5 to 95% RH (without condensation)

Max 2.5 mm2

119,1 mm x 101 mm x 22,6 mm

DIN rail mounting (DIN EN 50022)

Plastic, self-extinguishing PC/ABS

TOP PANEL

ANALOG OUTPUTS

COMMUNICATION

POWER SUPPLY

WARNING

TERMINALS OF THE DEVICE

·Note, an incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has been correctly wired before turning the power ON. · Before wiring, or removing/mounting the product, be sure to turn the power OFF. Failure to do so might cause electric shock. · Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock. · Do not disassemble the product. Doing so might cause electric shock or faulty operation. · Use the product within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere etc.). Failure to do so might cause fire or faulty operation. · Firmly tighten the wires to the terminal. Insufficient tightening of the wires to the terminal might cause fire

iSMA CONTROLLI S.p.A. ­ Via Carlo Levi 52, 16010 Sant'Olcese (GE) - Italy | support@ismacontrolli.com

www.ismacontrolli.com

Installation Instruction| 1st Issue rev. 3 | 01/2022

page 1

Registered access

Modbus Dec Hex Register Name

Access

30001

0

0x00 Version/Type

Read

30002

1

0x01 Switches

Read

40003

2

0x02 Baud rate

Read & Write

40004

3

0x03 Stop Bits & Data Bits Read & Write

40005

4

0x04 Parity

Read & Write

40006

5

0x05 Response Delay

Read & Write

40007

6

0x06 Modbus Mode

Read & Write

40009

8

0x08 Watchdog

Read & Write

40033

32

0x20

Received packets LSR (Least Significant Reg.)

Read & Write

40034
40035 40036 40037 40038 30051 40053 40054 40055 40056 40057 40058 40059 40060

33

0x21

Received packets MSR (Most Significant Reg.)

Read & Write

34 0x22 Incorrect packets LSR Read & Write

35 0x23 Incorrect packets MSR Read & Write

36 0x24 Sent packets LSR

Read & Write

37 0x25 Sent packets MSR

Read & Write

50 0x32 Outputs

Read

52 0x34 Analog output 1

Read & Write

53 0x35 Analog Output 2

Read & Write

54 0x36 Analog Output 3

Read & Write

55 0x37 Analog Output 4

Read & Write

56 0x38 Analog Output 5

Read & Write

57 0x39 Analog Output 6

Read & Write

58 0x3A Analog Output 7

Read & Write

59 0x3B Analog Output 8

Read & Write

Description Version and Type of the device Switches state RS485 baud rate No of Stop bits & Data Bits Parity bit Response delay in ms Modbus Mode (ASCII or RTU) Watchdog
No of received packets
No of received packets with error
No of sent packets
Bit is set if value  0
Value of Analog Output: in mV for voltage output (max 10240) in A for current output 0 ­ 20 mA (max 20480) in  for current output 4-20 mA (max 1000)

Modbus Dec Hex Register Name

Access

40061 40062 40063 40064 40065 40066 40067 40068 40069 40070 40071 40072 40073 40074 40075 40076

60 0x3C Default output 1 value Read & Write

61 0x3D Default output 2 value Read & Write

62 0x3E Default output 3 value Read & Write

63 0x3F Default output 4 value Read & Write

64 0x40 Default output 5 value Read & Write

65 0x41 Default output 6 value Read & Write

66 0x42 Default output 7 value Read & Write

67 0x43 Default output 8 value Read & Write

68 0x44 Output 1 setting

Read & Write

69 0x45 Output 2 setting

Read & Write

70 0x46 Output 3 setting

Read & Write

71 0x47 Output 4 setting

Read & Write

72 0x48 Output 5 setting

Read & Write

73 0x49 Output 6 setting

Read & Write

74 0x4A Output 7 setting

Read & Write

75 0x4B Output 8 setting

Read & Write

Description
Default value of output set when power is on or when watchdog reset occurs
Setting of output mode: 0 ­ output disabled 1 ­ voltage output 2 ­ current output 0-20 mA 3 ­ current output 4-20 mA Caution! For the change to take effect, you must also set the jumper inside the module.

iSMA CONTROLLI S.p.A. ­ Via Carlo Levi 52, 16010 Sant'Olcese (GE) - Italy | support@ismacontrolli.com

www.ismacontrolli.com

Installation Instruction| 1st Issue rev. 3 | 01/2022

page 2

INSTALLATION GUIDELINE
Please read the instruction before use or operating the device. In case of any questions after reading this document, please contact the iSMA CONTROLLI Support Team (support@ismacontrolli.com).
· Before wiring or removing/mounting the product, make sure to turn the power off. Failure to do so might cause an electric shock. · Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on. · Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock. · Do not disassemble the product. Doing so might cause an electric shock or faulty operation. · Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure to do so might cause a fire or faulty operation. · Firmly tighten the wires to the terminal. Failure to do so might cause a fire. · Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product. · Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals. · It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads. · Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges. · Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single power source causes a risk of introducing disturbances from the loads to the control devices. · If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, which are dangerous for devices. · Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external communication. It is recommended to use galvanic separators. · To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads. · Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena. · Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.
Electrical installation of this product must be done in accordance with national wiring codes and conform to local regulations.

iSMA CONTROLLI S.p.A. ­ Via Carlo Levi 52, 16010 Sant'Olcese (GE) - Italy | support@ismacontrolli.com

www.ismacontrolli.com

Installation Guideline| 1st Issue rev. 1 | 05/2022

