Trend IQ5 Controller Installation Instructions

Document Number: TG201482 Issue 1

Date: 17-Oct-2023

Important: Retain these instructions

These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.

CONTENTS

  1. Box Contents
  2. Storing
  3. Installation
  4. Field Maintenance
  5. Removing Controller from Din Rail
  6. Disposal
  7. China Hazardous Substances Table

For more information, visit: https://partners.trendcontrols.com

1 BOX CONTENTS

2 STORING

Operating Temperature: -40°C (-40°F) to +70°C (+158°F)

Humidity: 5% RH to 90% RH

Note: For temperatures below 0°C (32°F) special care must be taken that there is no condensation on or within the unit.

3 INSTALLATION

Labels used on IQ5

It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).

Any connected devices must be insulated from mains by reinforced insulation.

WARNING: Removal of cover exposes dangerous voltages. ⚡

WARNING: To reduce the risk of electrical shock or fire do not interconnect the output of different Class 2 circuits.

Dimensions

2 Mounting Requirements

Protection: IP20, NEMA1

Altitude: ≤4000 m (13124 ft)

Pollution degree: 2 (Only non-conducting pollution occurs)

Operating Temperature: -25°C (-13°F) to +60°C (+140°F)

Note: For temperatures below 0°C (32°F) special care must be taken that there is no condensation on or within the unit.

The IQ5 should be installed in an enclosure or outside normal reach (e.g. in a plenum).

The unit is UL rated as UL60730-1 Automatic electrical controls for household and similar use.

Mounting:

3 Mount Unit

Set the rear mounting clips to the correct position and slide the unit onto the DIN rail.

4 Connect Ethernet Network(s)

Connect the IQ5 Controller to the Ethernet LAN or WAN using a standard Ethernet cable (Cat 5e twisted pair), maximum 100 m (109 yds).

IQ5 Controller Network Example:

5 Unclip the Terminal Covers

Unclip the terminal covers to access the ports for Power, RS-485, and the IQ3/4 IO expansion bus.

6 Make Connections - Overview

Plug-in connectors with screw terminals:

Optional connectors with push-fit terminals

Note: It is recommended that wire ends are terminated using suitable ferrules, especially when using stranded wire with push-fit terminals.

Connection Type and Corresponding Step:

Connection Type Go to step...
Power 7
RS-485 Ports 8
T1L Bus 9
IQ3/4 IO Bus 10

7 Connect Power

This equipment must be earthed (grounded). ?

Supply rating: 24 Vac ±20%, 50/60 Hz, 34VA (1.42A); 24 Vdc ±20%, 12.5W (0.52A).

If IO modules are to be powered from the controller's T1L bus, the above rating must be increased. Refer to the IQ5-IO Modules Data Sheet (TA201481) for details.

Power supply cable must have a maximum operating temperature of 80°C or greater.

For UL rating, use 18 AWG or larger wire rated at least 90°C (194°F).

The primary supply must include a fuse or circuit breaker appropriate for the transformer.

The 24 V supply must include a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unit.

Do not position the equipment so that the disconnecting device is difficult to operate.

DO NOT SWITCH ON POWER

8 Connect RS-485 Networks (if required)

For use with Modbus, M-Bus, and/or XNC functionality. One port can also be used for an MSTP LAN of IQECOS.

Note: An appropriate converter will be required to enable connection to an RS-232 M-Bus network or connection to an RS-485 4-wire network.

Where Modbus, M-Bus or XNC functionality is required, this must be enabled by installing an INT licence. Where an MSTP LAN is required, an NC licence must be installed.

Termination: The bus must be terminated at each end with a resistor matched to the cable characteristic impedance (i.e. ±1%, ¼ Watt, range 100 to 130 Ω). If the IQ5 is at one end of a 120 Ω cable, switch ON its built-in terminator, otherwise switch it OFF. Termination must be applied at the far end(s) of the cable.

Bias: The IQ5 does not need the bus to be biased as it has a fault tolerant transceiver and applies a small bias. Other devices on the bus may require biasing.

Termination Table:

Protocol Device Count Cable Type Max Length* (metres/feet)
Modbus 32** 120 Ω twisted pair 900 (2953)
M-Bus 60 120 Ω twisted pair 1000 (3280)
MSTP 30 120 Ω twisted pair 1200 (4000)
XNC 32 depends on chosen application

* dependent on cable specification and baud rate.
** up to 32 unit loads.

The GND/0V terminal MUST be connected on all devices. It is not recommended to use the screen as the OV connection.

Cable screening is recommended for reliable operation in electrically noisy environments. The cable screen should be connected to earth at one point.

Earthing (Grounding) & Isolation Requirements:

9 Install and Connect IQ5-IO Modules (T1L Bus) (if required)

Depending on the controller licence, up to 300 I/O channels are supported.

Remove I/O cover plate from IQ5 and retain for use on the last IQ5-IO module.

Cable Length:

For full IO module installation details and power requirements, please refer to: IQ5-IO Installation Instructions - Mounting (TA201484).

10 Install and Connect IQ4/IO or XCITE/IO Modules (IQ3/4 IO Bus) (if required)

The IQ3/4 IO bus provides compatibility with I/O modules from the IQ4/IO and XCITE/IO ranges. Up to 192 I/O channels are supported on this bus.

Note: To use this bus it must be enabled by installing a CAN licence. See IQ5 Data Sheet (TA201480) for further details.

Note: No power is available via this connector. A separate 24 Vdc power supply must be provided. For all installations, if the bus voltage at an I/O module drops below 19.2 V at full load, install another power supply at that module.

Maximum I/O bus length depending on cable type:

Controller and IO Module Configuration Maximum I/O bus length (excluding rigid interconnectors) Maximum No. of Modules
Belden 3084A Belden 7895A
IQ5 controller with IQ4/IO modules only total bus length up to 100 m (109 yards) or total bus length up to 300 m (328 yards) if IQ4/IO modules are within 100m (109 yards) of a power supply total bus length up to 300 m (328 yards) 30
IQ5 controller with IQ4/IO modules and/or XCITE/IO modules total bus length up to 30 m (33 yards) Note: Maximum 10 m (11 yards) for certain system configurations - for details check the XCITE/IO Modules Data Sheet (TA201352) and XCITE/IO Installation Instructions - Mounting (TG200627). 15

For related installation instructions, refer to:
IQ4/IO Installation Instructions - Mounting (TG201342)
XCITE/IO Installation Instructions - Mounting (TG200627)

11 Refit Terminal Covers

Refit the terminal covers.

Note: Spare covers are available to order (e.g. IQ5-TCVR-140-10).

12 Fit IO Terminal Cover

Fit the IO terminal cover.

Note: Spare covers are available to order (e.g. IQ5-IO-END-10).

13 Close Panel / Enclosure

Close the panel or enclosure.

14 Configure IQ5 Controller and I/O Modules

For configuration details, refer to the following documents:

4 FIELD MAINTENANCE

The IQ5 require no routine maintenance.

WARNING: Contains no serviceable parts. Do not attempt to open the unit. Failure to comply may cause damage to the unit. ⚠️

5 REMOVING CONTROLLER FROM DIN RAIL

  1. Isolate Power (including IO supplies): Ensure all power is disconnected. ⚡
  2. Remove Terminal Covers
  3. Unplug Wired I/O Connectors
  4. Unclip Module from DIN Rail

Warning: Hazardous voltages may be present on I/O terminals. Isolate before touching. ⚠️

6 DISPOSAL

WEEE Directive: At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.

7 CHINA HAZARDOUS SUBSTANCES TABLE

This table is prepared in accordance with the provisions of SJ/T 11364.

部件名称 (Component Name) 有害物质 (Hazardous Substances)
铅(Pb) (Lead (Pb)) 汞(Hg) (Mercury (Hg)) 镉(Cd) (Cadmium (Cd)) 六价铬(Cr6+) (Chromium VI Compounds (Cr6+)) 多溴联苯(PBB) (Polybrominated Biphenyls (PBB)) 多溴二苯醚 (PBDE) (Polybrominated Diphenyl Ethers (PBDE))
电缆 (Cables) X Ο X Ο Ο Ο
印刷线路板总成 (PCB Assembly) X Ο X Ο Ο Ο
连接器 (Connectors) X Ο X Ο Ο Ο
塑料外壳 (Enclosures (Plastic)) Ο Ο Ο Ο Ο Ο
金属外壳 (Enclosures (Metal)) X Ο Ο Ο Ο Ο

Ο Indicates that said hazardous substance contained in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572.

X Indicates that said hazardous substance contained in all of the homogeneous materials for this part is above the limit requirement of GB/T 26572.

All other components, not listed in the table, do not contain restricted substances above the threshold level.

Models: IQ5-IO, IQ5 Controller, IQ5, Controller

File Info : application/pdf, 12 Pages, 1.31MB

PDF preview unavailable. Download the PDF instead.

HBA-BMS-IQ5-Installation-Guide-EN-Manual-and-Guides ?download=false

References

Adobe PDF Library 17.0

Related Documents

Preview Trend IQ5-IO Modules: Comprehensive I/O Expansion for Building Control
Explore the features, specifications, and installation guidelines for the Trend IQ5-IO Modules, a range of versatile input/output modules designed to expand the capabilities of the IQ5 controller. Learn about universal inputs/outputs, digital inputs, digital/relay outputs, BLE connectivity, and hand-off-auto functionality.
Preview IQ5, IQ5-IO Controller & I/O Modules Installation Instructions
This document provides detailed installation and configuration instructions for Trend IQ5 and IQ5-IO Controller & I/O Modules. It covers initial setup, network configuration, addressing, feature licensing, and troubleshooting.
Preview IQ5-IO I/O Modules Installation and Mounting Guide
Comprehensive guide for the installation and mounting of TREND IQ5-IO I/O modules, covering content, storage, installation steps, wiring, and maintenance.
Preview Trend IQ4/IO I/O Expansion Modules Data Sheet
Data sheet for Trend IQ4/IO I/O Expansion Modules, detailing their features, specifications, physical characteristics, and installation guidelines.
Preview Trend IQ4/IO.. I/O Expansion Modules Data Sheet
Data sheet for Trend IQ4/IO.. I/O Expansion Modules, detailing their features, specifications, compatibility, and installation for industrial automation systems. These DIN rail mountable modules offer digital, universal, and analogue I/O capabilities.
Preview TREND IQ4/IO I/O Expansion Modules Installation and Mounting Guide
Comprehensive installation and mounting instructions for TREND IQ4/IO I/O Expansion Modules. Covers box contents, storing, installation procedures, wiring, and disposal.
Preview TREND IQ422 DDC-Station Datasheet
Datasheet for the TREND IQ422 DDC-Station, detailing its electrical specifications, hardware features, communication protocols, and installation guidelines.
Preview Trend RV-WMB Wallbus Room Display Data Sheet
This data sheet provides comprehensive information on the Trend RV-WMB Wallbus Room Display, including its features, functionality, hardware specifications, and configuration options for use with Trend IQ4 and IQeco controllers.