OVERVIEW

FCS-CGAS-D-IR-Multi-Channel-Control-System-fig-1

REFRIGERANT DETECTION SYSTEM – EQUIPMENT

  • FCS: MULTI CHANNEL CONTROL SYSTEM (UP TO 128 CHANNELS) WITH…
  • FOUR RELAYS RATED 5A @ 240VAC, LCD DISPLAY, INTERNAL BUZZER WITH SILENCE
  • MANUAL SHUTOFF SWITCH (-SW)
  • TOP MOUNTED STROBE (-L)
  • CGAS-D-IR: SINGLE CHANNEL REFRIGERANT DETECTOR/TRANSMITTER WITH ONE RELAY RATED 5A @ 240VAC, INTERNAL BUZZER
  • CET-RDM: REMOTE DISPLAY MODULE
  • RLY-8: REMOTE RELAY MODULE (8 RELAY OUTPUTS PER MODULE)
  • LNK-AO: REMOTE ANALOG OUTPUT MODULE (4 ANALOG OUTPUTS PER MODULE)
  • RSH-24V: REMOTE HORN/STROBE
  • RPS-24VDC: REMOTE POWER SUPPLY (1 FOR EVERY 16 TRANSMITTERS)

SEQUENCE OF OPERATIONS

  • LOW ALARM: DETECTION OF 50PPM R123 OR 250PPM FREON REFRIGERANT SHALL ACTIVATE VENTILATION SYSTEM
  • HIGH ALARM: DETECTION OF 150PPM R123 OR 1000PPM FREON REFRIGERANT SHALL ACTIVATE HORN/STROBE AND SHUTDOWN CHILLERS

SYSTEM NOTES

  1. REFRIGERANT SENSOR LOCATION AT 6-8 INCHES ABOVE FINISHED FLOOR
  2. REFRIGERANT SENSOR TO HAVE DETECTION RADIUS OF 31 FEET
  3.  ALL TRANSMITTERS AND REMOTE MODULES TO BE 4-WIRE DAISY CHAINED FROM CONTROLLER
  4. SYSTEM TO COMMUNICATE VIA MODBUS RS485 FOR DATA COMMUNICATION
  5. RECOMMENDED WIRE: 4 CONDUCTOR, 4 COLOR, 16 AWG STRANDED, SHIELDED. DO NOT USE SOLID CORE
  6. CONTROLLER POWERED BY 90-240VAC

Specifications

  • BACNET MS/TP to BAS
  • Additional Analog Outputs
  • Additional Relays
  • Eight Optional Analog Outputs
  • Four Relays
  • Refrigerant Detection System – Equipment FCS: Multi-Channel Control System (up to 128 channels)
  • Four Relays rated 5A @ 240VAC
  • LCD Display
  • Internal Buzzer with Silence Manual Shutoff Switch (-SW)
  • Top Mounted Strobe (-L)
  • CGAS-D-IR: Single Channel Refrigerant Detector/Transmitter with one relay rated 5A @ 240VAC
  • Internal Buzzer
  • CET-RDM: Remote Display Module
  • RLY-8: Remote Relay Module (8 relay outputs per module)
  • LNK-AO: Remote Analog Output Module (4 analog outputs per module)
  • RSH-24V: Remote Horn/Strobe
  • RPS-24VDC: Remote Power Supply (1 for every 16 transmitters)

Product Usage Instructions

Sequence of Operations

  • Low Alarm: Detection of 50PPM R123 or 250PPM Freon refrigerant shall activate the ventilation system.
  • High Alarm: Detection of 150PPM R123 or 1000PPM Freon refrigerant shall activate the horn/strobe and shutdown chillers.

System Notes

  1. Refrigerant sensor location at 6-8 inches above the finished floor.
  2. Refrigerant sensor to have a detection radius of 31 feet.
  3. All transmitters and remote modules to be 4-wire daisy-chained from the controller.
  4. System to communicate via Modbus RS485 for data communication.
  5. Recommended wire: 4 conductors, 4 colors, 16 AWG stranded, shielded. Do not use solid core.
  6. Controller powered by 90-240VAC.

FAQs

Q: How do I reset the system after an alarm?
A: To reset the system after an alarm, locate the control panel and press the reset button. Ensure that the cause of the alarm has been addressed before resetting.

Q: Can I extend the detection range of the refrigerant sensor?
A: No, the detection range of the refrigerant sensor is fixed and cannot be extended beyond its specified radius of 31 feet.

Q: What is the recommended maintenance schedule for the system?
A: It is recommended to perform regular maintenance checks on the system every six months to ensure proper functioning and calibration of the sensors and modules.