Installation Guide for FCS models including: CGAS-D-IR, CET-RDM, RLY-8, CGAS-D-IR Multi Channel Control System, CGAS-D-IR, Multi Channel Control System, Channel Control System, Control System

A4

PDF preview unavailable. Download the PDF instead.

Controls-Schematic-Refrigeration-System-Central-Panel
BACNET MS/TP TO BAS

R

ADDITIONAL ANALOG OUTPUTS

ADDITIONAL RELAYS

EIGHT OPTIONAL ANALOG OUTPUTS

FOUR RELAYS

REFRIGERANT DETECTION SYSTEM - EQUIPMENT FCS: MULTI CHANNEL CONTROL SYSTEM (UP TO 128 CHANNELS) WITH...
FOUR RELAYS RATED 5A @ 240VAC, LCD DISPLAY, INTERNAL BUZZER WITH SILENCE MANUAL SHUTOFF SWITCH (-SW) TOP MOUNTED STROBE (-L) CGAS-D-IR: SINGLE CHANNEL REFRIGERANT DETECTOR/TRANSMITTER WITH ONE RELAY RATED 5A @ 240VAC, INTERNAL BUZZER
CET-RDM: REMOTE DISPLAY MODULE
RLY-8: REMOTE RELAY MODULE (8 RELAY OUTPUTS PER MODULE)
LNK-AO: REMOTE ANALOG OUTPUT MODULE (4 ANALOG OUTPUTS PER MODULE)
RSH-24V: REMOTE HORN/STROBE
RPS-24VDC: REMOTE POWER SUPPLY (1 FOR EVERY 16 TRANSMITTERS)

SEQUENCE OF OPERATIONS LOW ALARM: DETECTION OF 50PPM R123 OR 250PPM FREON REFRIGERANT SHALL ACTIVATE VENTILATION SYSTEM HIGH ALARM: DETECTION OF 150PPM R123 OR 1000PPM FREON REFRIGERANT SHALL ACTIVATE HORN/STROBE AND SHUTDOWN CHILLERS

SYSTEM NOTES: 1. REFRIGERANT SENSOR LOCATION AT 6-8 INCHES ABOVE FINISHED FLOOR 2. REFRIGERANT SENSOR TO HAVE DETECTION RADIUS OF 31 FEET 3. ALL TRANSMITTERS AND REMOTE MODULES TO BE 4-WIRE DAISY CHAINED FROM CONTROLLER 4. SYSTEM TO COMMUNICATE VIA MODBUS RS485 FOR DATA COMMUNICATION 5. RECOMMENDED WIRE: 4 CONDUCTOR, 4 COLOR, 16 AWG STRANDED, SHIELDED. DO NOT USE SOLID CORE 6. CONTROLLER POWERED BY 90-240VAC


AutoCAD 2025 - English 2025 (25.0s (LMS Tech)) pdfplot17.hdi 17.00.154.00000