EPH CONTROLS - logoCDTP2 Room Thermostat Hardwired

EPH CONTROLS CDTP2 Hardwired Room Thermostat -

Prior to setting the thermostat, it is neccessary to complete all required settings described in this section.

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon3 Factory default settings

Contacts: Volt
Free
Temperature indicator: °C
Switching dierential: 0.4°C
In built frost protection: 5°C
High and Low temp. limitation: Off
Clock: 24 hours
Keypad lock: Off

Specifications & wiring

Power supply: 2 x AA Alkaline Battery
Power consumption: 8 VA
Temp. control range: 5 … 35°C
Ambient temperature: 0 … 50°C
Contact rating: 8A 230Vac
Dimensions: 84 x 84 x 30mm
Temperature sensor: NTC 10K Ohm @ 25°C
Switching differential: Adjustable from 0.2/0.4/0.6/0.8/1.0˚C
Frost protection: Only operational in stand by mode EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon4

Mounting

The mounting height should be 1.5 meters above the floor level.
The thermostat should be wall mounted in the room where the heating is to be controlled.
The place of installation should be chosen so that the sensor can measure the room temperature as accurately as possible.
Choose the mounting location to prevent direct exposure to sunlight or other heating / cooling sources when mounted. The unit can be fitted to:

  1. Recessed conduit boxes
  2.  Surface mounting boxes
  3. Directly on walls.

Installation

Slacken the fastening screw on the bottom of the thermostat with a philips head screwdriver.
The thermostat is hinged and can be opened 180 degrees.
Mount the unit as described in section 3.
Wire the thermostat according to the wiring diagram.
Close the thermostat and tighten the fastening screw.

Wiring diagram

INTERNAL WIRING DIAGRAM CDTP2

EPH CONTROLS CRTP2 Room Thermostat -

If mains voltage output is required, 230V must be connected to terminal 2.

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon Boiler Plus

Operating Instructions

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon 1 CAUTION!
Before commencing any work on the electrical connections, you must first disconnect the thermostat from the mains. None of the 230V connections must be live until the installation has been completed and the housing is closed. Only qualified electricians or authorised service staff are permitted to open the thermostat. There are parts that may carry mains voltage behind the cover. The thermostat must not be left unsupervised when open. (Prevent non specialists and especially children from gaining access to it.)
Important: Keep this document

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon2

Frost protection

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon3 5°C

Frost protection is built into this thermostat, it is pre fixed at 5°C and is not adjustable.
It will only be activated when the thermostat is in the stand by mode and the room temperature falls below 5°C.

Button / Symbol description

EPH CONTROLS CRTP2 Room Thermostat - fig1

Resetting the thermostat

It is necessary to reset the thermostat prior to initial programming.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon5 RESET button on the side of the thermostat.
‘NO’ will appear on the screen.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 button.
‘YES’ will appear on the screen.
Press the ‘OK’ button to return to normal operation.

Keypad lock and unlock

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon3 OFF

To lock the keypad, press and hold the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons for 5 seconds.
EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon8 will appear on the screen. The keypad is now locked.
To unlock the keypad, press and hold the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons for 5 seconds.
EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon8 will disappear from the screen. The keypad is now unlocked.

Setting the date, time and operating mode

Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon9 Set button once. ‘Set Date Year’ will appear on the screen.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 or EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the year. Press the ‘OK’ button.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 or EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the month. Press the ‘OK’ button.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 or EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the day. Press the ‘OK’ button.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 or EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the hour. Press the ‘OK’ button.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 or EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the minute. Press the ‘OK’ button.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 or EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust from 5/2d to 7d or 24h mode.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon4 button or wait 10 seconds and the thermostat will return to normal operation.

Factory program setting

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon3 5 / 2d

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon3

5/2D
P1 P2 P3 P4 P5 P6
Mon-Fri 06:30 08:00 12:00 14:00 17:30 22:00
21˚C 18˚C 21˚C 18˚C 21˚C 16˚C
Sat-Sun 08:00 10:00 12:00 14:00 17:30 23:00
21˚C 18˚C 21˚C 18˚C 21˚C 16˚C
7D
P1 P2 P3 P4 P5 P6
Mon-Fri 06:30 08:00 12:00 14:00 17:30 22:00
21˚C 18˚C 21˚C 18˚C 21˚C 16˚C
Sat-Sun 08:00 10:00 12:00 14:00 17:30 23:00
21˚C 18˚C 21˚C 18˚C 21˚C 16˚C
 

Everyday

24H
P1 P2 P3 P4 P5 P6
06:30 08:00 12:00 14:00 17:30 22:00
21˚C 18˚C 21˚C 18˚C 21˚C 16˚C

Adjusting the program settings for 5/2d

Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon9 Set button twice.
Programming for Monday to Friday is now selected.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the P1 time. Press the ‘OK’ button.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the P1 temp. Press the ‘OK’ button.
Repeat this process to adjust P2 to P6 times and temperatures.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon9 Set button.
Programming for Saturday to Sunday is now selected.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the P1 time. Press the ‘OK’ button.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the P1 temp. Press the ‘OK’ button.
Repeat this process to adjust P2 to P6 times and temperatures.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon4 button to return to automatic mode.
If 7 D mode is selected, you can program each day of the week with 6 individual times and temperatures.
If 24H mode is selected, you can only program each day of the week with the same 6 times and temperatures.

Temporary override (Manual)

Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the temperature setpoint.
‘Manual’ will appear on the screen.
Press ‘OK’ or after 10 seconds the thermostat will operate in this temporary override.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon4 button to return to automatic mode.

Permanent override (Hold)

Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon9 Hold button. ‘Hold’ will appear on the screen.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 buttons to adjust the temperature setpoint.
Press ‘OK’ or after 10 seconds the thermostat will operate in this permanent override.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon4 button to return to automatic mode.

Adjusting the switching differential

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon3 0.4˚C

Press the ‘OK’ and ‘Hold’ buttons for 5 seconds.
‘0.4˚C’ will appear on the screen.
Press the up or down buttons to adjust from 0.2, 0.4, 0.6, 0.8 or 1C.
Press the EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon4 button to return to normal operation.

Replacing the batteries

Slacken the fastening screw on the bottom of the thermostat with a philips head screwdriver.
The thermostat is hinged and can be opened 180 degrees.
Replace the batteries with 2 x AA Alkaline batteries.
Close the thermostat and tighten the fastening screw.

EPH CONTROLS CRTP2 Room Thermostat - fig2

Installer menu

To access the installer menu, you must hold OK and EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon4 for 5 seconds.
When in the installer menu, press EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon6 or  EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon7 and OK to navigate and select.

  • Normal Mode (Nor)
    When the thermostat is in Normal mode, the thermostat will try to reach the target temperature after the program changes.
    Example: Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:30am and the room temperature will start to increase then.
    To return to main menu, press OK to select Nor
  • Optimum Start Mode (OS) Boiler Plus

When the thermostat is in Optimum Start mode, the thermostat will try to reach the target temperature by the start time of the next switching time.
This is done by setting the Ti (time interval) on the thermostat in this menu to 10, 15 or 20. This will allow the thermostat 10 mins, 15 mins or 20 mins to increase the room temperature by 1°C.
Ti can be set when OS is selected in the installer menu. EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon3 20˚C
To return to main menu, press OK to select required Ti
To achieve the target temperature when the program starts, the thermostat will read:

  1. The Room Temperature (RT)
  2. The Setpoint Temperature (ST)
  3. The Target Temperature Difference (TTD) is the difference between the setpoint temperature and the room temperature .

The time (in minutes) that it will take to overcome (TTD) is called Optimum Start Time (OST) and its maximum value is 3 hours = 180 mins. This is subtracted from the start time.
As the temperature increases the thermostat will recalculate the OST if the temperature is increasing too quickly.

EPH CONTROLS CDTP2 Hardwired Room Thermostat - Button1

EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon10 Example when Ti = 20
Program 1 on the thermostat is 21°C for
06:30am and the room temperature is 18°C.
The thermostat will start the heating at 05:30am to reach 21°C for 06:30am @ Ti=20.
EPH CONTROLS CDTP2 Hardwired Room Thermostat - icon11 Example when Ti = 10
Program 1 on the thermostat is 21°C for
06:30am and the room temperature is 18°C.
The thermostat will start the heating at 06:00am to reach 21°C for 06:30am @ Ti=10.

EPH CONTROLS CDTP2 Hardwired Room Thermostat - Button2

EPH CONTROLS - logo

EPH Controls Ireland
technical@ephcontrols.com www.ephcontrols.com
EPH Controls UK
technical@ephcontrols.com www.ephcontrols.co.uk
20221006_CDTP2_Opins_PK

Documents / Resources

EPH CONTROLS CRTP2 Room Thermostat [pdf] Instruction Manual
CRTP2, CRTP2 Room Thermostat, Room Thermostat, Thermostat
EPH Controls CRTP2 Room Thermostat [pdf] Instruction Manual
CRTP2 Room Thermostat, CRTP2, Room Thermostat, Thermostat
EPH CONTROLS CRTP2 Room Thermostat [pdf] Instruction Manual
CRTP2 Room Thermostat, CRTP2, Room Thermostat, Thermostat
EPH CONTROLS CRTP2 Room Thermostat [pdf] Installation Guide
CRTP2 Room Thermostat, CRTP2, Room Thermostat, Thermostat