ENGO-CONTROLS-LOGO

ENGO CONTROLS E901-RF Programmable Wireless Thermostat

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat-PRO

Product Information

Specifications

  • Product Name: E901RF Wireless Programmable Thermostat
  • Power Supply: 2xAA batteries
  • Working Range: Up to 60m in open space
  • Features:
    • 2 types of time schedules
    • Possibility to choose hysteresis or built-in TPI algorithm
    • Maximum/minimum temperature limitation
    • Two relay types: NO (normally open) or NC (normally closed)
    • HEATING / COOLING function
    • PIN lock
    • Unique transmission codes

Product Usage Instructions

Proper Thermostat Location
The ideal position for thermostat mounting is about 1.5m under floor level, away from heating or cooling sources, and not exposed to sunlight or extreme conditions like drafts.

Wall Mounting

  1. Remove the thermostat cover as shown in the picture.
  2. If there are batteries inside, remove them.

Pairing with the E901RX Receiver
To pair the thermostat with the E901RX receiver, follow the steps outlined in the manual under section 7, including the transmission test in section 7.1.

Cleaning and Maintenance
Refer to section 11 of the manual for instructions on cleaning and maintaining the thermostat for optimal performance.

Technical Information
For detailed technical specifications and information about the product, refer to section 12 of the user manual.

FAQs

  • Q: What should I do if the thermostat is not responding?
    A: Check the batteries and ensure they are properly installed. If the issue persists, refer to the troubleshooting section in the user manual or contact customer support.
  • Q: Can I adjust the temperature limits on the thermostat?
    A: Yes, you can set maximum and minimum temperature limits on the thermostat. Refer to the user manual for instructions on adjusting these settings.

Introduction

Product Compliance
This product complies with the essential requirements and other relevant provisions of Directives 2014/53/EU and 2011/65/EU.

Safety Information

  • Before starting installation work and before using the product, read the entire manual.
  • The information contained in the instructions is essential for proper functioning.
  • To avoid accidents resulting in personal injury and material damage, please follow all safety precautions, specified in this manual.
  • The device should not be used by people with limited mental, sensory or mental abilities, without experience, of insufficient knowledge as well as children.
  • Do not use an unassembled device (eg without a cover).
  • The device may only be opened by a qualified person.
  • Keep electrical devices out of the reach of children and ensure that they do not play with it. Children should not be left unattended. If necessary, disconnect the control system for the entire room.
  • Do not leave the packaging, cabinet, or any loose parts of the device unattended, as they pose a risk to children.

WARNING!

  • Installation must be carried out by a qualified person with appropriate electrical qualifications in accordance with standards and regulations in force in the given country and in the EU.
  • Never try to connect the device other than as described in the manual.
  • Before assembly, repair or maintenance as well as during any connection works it is absolutely necessary to disconnect the mains supply and make sure that the terminals and electric wires are not live.
  • The device may not be exposed to extreme temperatures, strong vibrations or subjected to mechanical shock.
  • The device should not be used in unfavorable environmental conditions or in rooms where there is a concentration of flammable gases, fumes or dust.

WARNING! There may be additional protection requirements for the entire installation that the installer is responsible for maintaining.

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (1)Care for the natural environment is of paramount importance to us. The awareness that we manufacture electronic devices obliges us to dispose of used electronic components and devices safely. Therefore the company has received a registration number issued by the Chief Inspector for Environmental Protection. The crossed-out symbol the trash can on the product means that the product must not be disposed of with ordinary waste containers. Sorting waste for recycling helps to protect the environment. It is the user’s responsibility to surrender used equipment to a designated collection point for recycling waste from electrical and electronic equipment.

Product Overview

E901RF is a weekly, surface-mounted electronic room thermostat, used for wireless control of heating devices (e.g. gas, oil boilers, heat pumps) or cooling devices. It has the function of creating your own schedules. Thanks to the built-in algorithms, it offers much better temperature control accuracy than traditional mechanical thermostats. Please read these instructions carefully before using the device for the first time. The thermostat should use 2xAA, 1.5V alkaline batteries. Rechargeable batteries are not allowed.

In the set:

  • thermostat transmitter
  • thermostat receiver

Product features:

  • has 2 types of time schedules
  • possibility to choose hysteresis or a built-in TPI algorithm
  • maximum/minimum temperature limitation
  • two relay types (selectable in thermostat settings): NO (normally open) or NC (normally closed)
  • has the HEATING / COOLING function
  • PIN lock
  • has unique transmission codes
  • working range up to 60m in open space
  • automatically renews the operating signal

Package content

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (2)

  1. E901RF thermostat
  2. E901RX receiver
  3. Quick Guide
  4. Thermostat bracket
  5. Power supply wire and control wire
  6. 2xAA batteries
  7. Mounting screws

Proper thermostat location

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (3)

Please note: The ideal position to thermostat mounting is about 1,5m under floor level far from heating or cooling sources. Thermostat can’t be exposed to sunlight or any extreme conditions like for example draft.
Because of fire and explosion risk there is not allowed to use thermostat in atmosphere of explosive gases and flammable liquids (eg coal dust). In case if any of listed dangers occur you have to use additional protection measures – anti-dust and explosive gases (tight cover) or prevent their formation. Furthermore, thermostat can’t be used in condensation of water vapor conditions and be exposed to water action.

Wall mounting

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (4) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (5)

Free-standing thermostat
With the bracket attached to the E901RF set, you can use the thermostat anywhere in the house and put it on a table, desk, etc. To use the bracket properly, see the steps below:

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (6) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (7)

Receiver

The thermostat communicates wirelessly with the receiver. The receiver should be supplied with 230VAC, the maximum switching load of the receiver is 16A. Avoid installing the device in places directly exposed to water, moisture and air condensation. The receiver can operate in two different modes – AUTO (automatic) and MANUAL (manual). To select a specific mode, use the switches on the front of the receiver.ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (8)

Receiver’s switch description

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (9)

REMEMBER!: Thermostat (transmitter) will communicate with receiver only when both are paired together and receiver’s switches are set to ON and AUTO position.

Receiver LED indicators
The status of the receiver is indicated by two LEDs. These are LEDs with the following colors:

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (10)

A detailed explanation of the meaning of the LEDs can be found in the table below:

  DESCRIPTION
 

The green LED lights up

 

The receiver is connected to the 230V power supply.

The green LED flashes The receiver is in the pairing mode (then you must activate the “SYNC” parameter in the thermostat).
The green LED is off The receiver is disconnected from the 230V power supply or the left switch is in the OFF position.
The orange LED lights up In automatic mode, the receiver received a heating / cooling signal from the thermostat.

The receiver was started in manual mode (left switch is set to ON and right switch is set to MANUAL)

The orange LED flashes The receiver was paired but lost communication with the thermostat due to out of range or low battery in the thermostat. The receiver starts flashing after 40 minutes of time when it does not receive a signal from the ther- mostat.
The orange LED is off In automatic mode, the receiver didnt get a heating / cooling signal from the thermostat.

The receiver is OFF in manual mode (left switch is set to OFF and right switch is set to MANUAL).

Connection description

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (11) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (12)ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (13)

Before you start (first power on)

The thermostat is powered by two 1.5V AA alkaline batteries. Insert the batteries into the compartment under the front housing, paying attention to their polarity. The thermostat will start up showing the current software version and then go to the main screen.

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (60) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (59)

LCD icon descriptionENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (15)

  1. Program timeline indicator
  2. AM/PM
  3. Clock
  4. Day of the week indicator
  5. Settings icon
  6. Key lock function
  7. Send a signal (pairing)* only E901RF
  8. Holiday Mode
  9. Low battery indicator
  10. Frost Protection Mode
  11. Comfort Mode
  12. Economic Mode
  13. Cooling status
  14. Heating status
  15. Temperature unit
  16. Room/setpoint temperature
  17. Temporary override
  18. Program number

Button description

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (16)

Time settings

Day/time settings are set using the D, H and M buttons. Please see steps below how to set time/day:ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (17)

Operation

Manual mode
There are two temperature setpoint levels at our disposal. In manual mode chosen setpoint temperature level is maintained permanently until user changes operation mode or set a different temperature for each level.

  • ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (18)Comfort Mode – in this mode, the thermostat is to maintain a constant day temperature. When the temperature is set manually, e.g. 23°C, the thermostat maintains it until user switches to another operating mode or set a different temperature, e.g. 21°C.
  • ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (19)Economic Mode – in this mode, the thermostat is to maintain the reduced (night) temperature. When the temperature is set manually, e.g. 17°C, the thermostat maintains it until user switches to another mode or set a different temperature, e.g. 19°C.

Comfort mode
In the comfort temperature mode, the thermostat is to maintain a constant day temperature. The comfort temperature level is indicated by sun icon. To set the comfort temperature, see the steps below:ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (20) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (21)

Economic mode
In the economic temperature mode, the thermostat is to maintain a reduced (night) temperature. This is to ensure a more economical operation of the heating system when, for example, you are away from home. The economic temperature level is indicated by the moon icon. To set the economic (night) temperature, see the steps below:ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (22) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (23)

AUTO mode – two schedule types

  • ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (24)AUTO Mode – In the automatic mode, the thermostat maintains the set temperature according to the schedule selected by the user. You can choose from 2 types of schedule to manage the temperature during the week.
  1. First type scheduleENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (25)
    First type schedule mode is represented by timeline – 24 hours of a day. Empty „boxes” means hours where Economic (Moon) setpoint temperature will be maintained, black „boxes” means hours where Comfort (Sun) setpoint temperature will be maintained.
    There are three different configurations in a schedule type 1:
    • Two different programs (timelines), separate program for working days (Monday to Friday) and separate program for weekends (Saturday to Sunday)
    • Individual programs (timelines) for each day of the week
    • Same program (timeline) for the whole week
  2. Second type schedule
    Schedule type 2 enables the programming of 6 time intervals per day, with precision up to 10 minutes. Each of the 6 time intervals allows you to set a different temperature (schedule type 1 is limited to switching between two setpoint temperatures (SUN/MOON) at full hours time periods).
    When creating a schedule type 2, you must define time and temperature setpoint (thermostat will start to maintain given setpoint temperature from given time setting). There are three different schedule configurations:
    • Two different programs, separate program for working days (Monday to Friday) and separate program for weekends (Saturday to Sunday)
    • Individual programs for each day of the week
    • Same program for the whole week
      Schedule of the second type exampleENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (26)
  3. Switching between schedules (AUTO Mode) type 1 and 2ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (27)

First type schedule programming

  1. Default program settings (1-3)
    Within first type schedule mode there are 9 programs available. Programs 0 to 3 are factory-defined programs that cannot be changed. In this chapter you will find detailed information on the built-in factory programs (1-3) in the E901. These are pre-programmed time settings for the comfort and economy temperature that can be assigned to a selected day. To set up the program, see the steps below. The black squares on the timeline indicate the operating time for the comfort temperature mode, while the absence of them – for the economy temperature mode. Under the chart of each program, there is time (hour) when each mode is active. By default, program 1 is set for each day of the week.ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (28) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (29)
  2. Choosing and programming user programs (4-9)
    In order to program your own schedule its necessary to choose user program (4-9), because only user programs are editable. Then we must draw our own timeline using Sun/Moon buttons. Thermostat will be switching between two setpoint temperatures (Comfort and Economy) which are represented by Sun and Moon icons. Switching time is represented by timeline. See steps below how to programm your own schedule:
    Example: below, program 4 will be defined for the MON – FR period with a comfort temperature from 8:00 to 16:00 and
    economic from 0:00 to 8:00 and 16:00 to 0:00. Programming starts from 0:00.ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (30) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (31)ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (32)
    Please note! Programs 0, 1, 2, 3 are factory set and cannot be edited.
    Programs 4 to 9 are user-defined (editable). One program (e.g. program 4) can be assigned to several days of the week. If this program is edited, the change affects all days to which given program is assigned to.
  3. Frost Protection program setting
    Frost protection mode (program 0) protects heating system against freezing. It is recommended to set this program if you are planning a long winter trip or if you do not heat up for a long time. The thermostat will maintain a constant temperature of 7˚C, thus reducing energy consumption to a minimum.ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (33) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (34)
    PLEASE NOTE! In the frost protection mode, the temperature setpoint can’t be changed and it is maintained constantly at 7°C.
  4. Temporary override mode
    When thermostat is running schedule (automatic mode) we can temporarily override it by new setpoint temperature:ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (35) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (36)

Second type schedule programming
There are three different configurations in a schedule type 1:

  • Two different programs (timelines), separate program for working days (Monday to Friday) and separate program for weekends (Saturday to Sunday)
  • Individual programs (timelines) for each day of the week
  • Same program (timeline) for the whole week

Exemplary schedule setting for working days and weekend:ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (37) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (38)

  1. Temporary override mode
    When thermostat is running schedule mode we can temporarily override it by setting new work mode or setpoint temperature:ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (39)

Party mode
In the party mode, the user can override schedule with comfort setpoint temperature by defined number of hours. To do this, follow the steps below:ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (40)

The maximum duration of party mode is 9 hours. The temperature setpoint does not change during this mode. When party mode is enabled, pressing SUN, MOON or AUTO button twice (or 3 times if backlight is OFF) will disable it and thermostat will go back to the appropriate mode.

To cancel active party mode (example):

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (41)

Holiday mode
Holiday mode is a special program temperature setpoint which thermostat will maintain for specified days. During holiday mode thermostat is maintaining frost protection setpoint temperature. To set holiday mode, follow the steps below:

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (42) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (43)

TO STOP HOLIDAY MODE:

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (44)

Key lock function

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (45)

The user has the option to set a PIN code, which he will have to enter each time he wants to unlock the buttons of the thermostat. To set a PIN code, go to parameter P12 (please refer to the „Installer settings” section).

Pairing with the E901RX receiver

PLEASE NOTE!The  E901RF thermostat is already paired with the receiver!
In order to pair the devices correctly, you must first prepare the receiver for synchronization!

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (46) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (47) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (48)

WARNING! If the green diode on the receiver has not stopped blinking after 10 minutes, repeat the pairing process taking into account the distance between devices, obstacles and interference.

Transmission test
It is important to place the receiver and transmitter in places where nothing is interfering with the radio signal. The range of communication between the transmitter and the receiver in an open area is up to 60m. Radio transmission is influenced by many factors that can shorten the working distance, such as thick walls, drywall covered with aluminum foil, metal objects such as cabinets, general radio interference, etc. However, the range is sufficient for most domestic applications. It is recommended that the radio transmission between devices has to be tested before mounting the thermostat to the wall. The test can be performed by changing the set temperature, i.e. by activating or deactivating the heating.

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (49) ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (50)ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (51)

Please note: If the orange LED does not turn on / off as indicated by the transmitter flame icon, try moving the transmitter closer to the receiver and repeat all steps from the beginning.
If it still doesn’t work, try the pairing process again.

Installer settings

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (52)

INSTALLER PARAMETERS:

Pxx Function Value Description Default value
P01 Heating/Cooling mode selection ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (53) Cooling ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (54)
ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (54) Heating
P02 Control method temperature 1 SPAN ±0,25°C 1
2 SPAN ±0,5°C
3 TPI for Underfloor Heating
4 TPI for Radiators
5 TPI for Electrical Heating
P03 Display temperature resolution 0,5°C This parameter specifies the accuracy of the displayed (measured) temperature. 0,5°C
0,1°C
P04 Offset temperature -3.5°C to + 3.5°C If the thermostat indicates wrong temperature, you can correct it by ± 3.5°C 0°C
P05 Relay type NO Normally Open type of relay NO
NC Normally Closed type of relay
P06 Clock format 24h 24 hour 24h
12h 12 hour
P07 Temperature Scale °C Celsius °C
°F Fahrenheit
P08 Minimum setpoint 5°C – 34,5°C Minimum heating / cooling temperature that can be set 5°C
P09 Maximum setpoint 5,5°C – 35°C Maximum heating / cooling temperature that can be set 35°C
Pxx Function Value Description Default value
P10 Key sound NO Off YES
YES On
P11 PIN Code NO Disabled NO
PIN Enabled
P12 Require a PIN to unlock the keys every time NO Function disabled NO
YES Function enabled
CLR Clear settings factory reset NO No action NO
YES Factory Reset
*Only for E901RF thermostat
SYNC Pairing function with RXRT510 receiver (SYNC) NO Pairing disabled NO
YES Pairing enabled

User settings reset

There is a small hole to the right of the OK button. This is the reset button. Pressing the reset button will restore the default values in the user settings (i.e. time, schedule).ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (55)

Please note: Do not use a pencil to press the reset button as the graphite build-up on the stylus can short-circuit and damage the thermostat. In environments with very strong electrostatic discharge (+/- 8KV), the product may not function as under normal conditions. So the device may need to be reset.

Clear settings – factory reset

To perform factory reset (which will remove all user/installer settings), use the CLR parameter from installer parameters menu. After confirming the parameter, the thermostat will restore the default settings.

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (56)

Cleaning and Maintenance
The E901RF thermostat requires no special maintenance. Periodically, the outer casing can be wiped clean using a dry cloth (please DO NOT use solvents, polishes, detergents or abrasive cleaners, as these can damage the thermostat). There are no user serviceable parts within the unit; any servicing or repairs could only be carried out by ENGO Controls or their appointed agents.

Technical Information

Transmitter’s power supply 2 x AA batteries
Receiver’s power supply 230V AC 50 Hz
Rating max 16 (5) A
Output signal NO/COM relay
Temperature range 5 – 35°C
Display temperature accuracy 0.1°C or 0.5°C
Control algorithm TPI or Hysteresis: ±0.25°C and ±0.5°C
Communication Wireless, 868Mhz
Dimension [mm] transmitter: 150 x 84 x 22

receiver: 96 x 96 x 27

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (57)

Warranty

ENGO Controls warrants this product to be free from any defects in material or workmanship and to perform as specified for a period of five years from the date of installation. ENGO Controls reserves the sole responsibility for breach of this warranty by repairing or replacing the defective product. This product includes software that matches the distributor’s identification at the time of sale. The manufacturer/distributor provides a guarantee covering all functions and specifics of the product in accordance with this marking. The distributor’s warranty does not cover the correct operation of the functions and features available as a result of a product software update.

ENGO-CONTROLS-E901-RF-Programmable-Wireless-Thermostat- (58)

Producer:
ENGO CONTROLS Sp z o.o. Sp. k. 43-262 Kobielice
4 Rolna St.
Poland
www.engocontrols.com

Documents / Resources

ENGO CONTROLS E901-RF Programmable Wireless Thermostat [pdf] Instruction Manual
E901-RF, E901RF, E901-RF Programmable Wireless Thermostat, E901-RF, Programmable Wireless Thermostat, Wireless Thermostat, Thermostat
ENGO CONTROLS E901-RF Programmable Wireless Thermostat [pdf] User Guide
E901-RF, E901-RF Programmable Wireless Thermostat, Programmable Wireless Thermostat, Wireless Thermostat, Thermostat

References

Leave a comment

Your email address will not be published. Required fields are marked *