Elitech-logo

Elitech STC-9100 Double Sensor Temperature Thermostat

Elitech STC-9100 Double Sensor Temperature Thermostat-fig1STC-9100 defrosting temperature controller controls three loads: the refrigeration device, the defrosting unit, and the External Alarm.

Wiring Diagram

Elitech STC-9100 Double Sensor Temperature Thermostat-fig2

Set the temperature

Please learn that the room temperature was supposed to keep at the range from “F1” to “F1 + F2”
Elitech STC-9100 Double Sensor Temperature Thermostat-fig3Elitech STC-9100 Double Sensor Temperature Thermostat-fig4

You can set them in both the user interface and the Admin Interface. Below is the 2nd method.

  • Step 1: Enter the Admin Interface: hold the [SET] key and the [ Elitech STC-9100 Double Sensor Temperature Thermostat-fig5] key at the same time for 10s; you will see the code “F1” (“Elitech STC-9100 Double Sensor Temperature Thermostat-fig8“).
  • Step 2: Press the [SET] key to check current value, and press the Elitech STC-9100 Double Sensor Temperature Thermostat-fig7 key or the Elitech STC-9100 Double Sensor Temperature Thermostat-fig5 key to change the F1 value;
  • Step 3: Press the [SET] key to save the new data, and back to the menu list, you will see the code “F1” (“Elitech STC-9100 Double Sensor Temperature Thermostat-fig8“) again.
  • Step 4: Switch to the “F2” (“HY”) code by press the key.
    Repeat the above 2-4 steps to update all the code you want to.Repeat the above 2-4 steps to update all the code you
    want to.

At last: Just leave the unit alone; it will auto quit from setting mode back to normal status in 10s.

  1.  F1 Elitech STC-9100 Double Sensor Temperature Thermostat-fig8: SP (Temperature Set-Point)
  2. F2 (HY): Temperature Hysteresis / Return Difference
  3. F3 (U5): Upper limit for SP
  4.  F4 (L5): Lower limit for SP
  5. F5 (AC): Delay Time for the Compressor and Delay time for defrosting if it was Hot Gas mode Elitech STC-9100 Double Sensor Temperature Thermostat-fig10
    If you found the “F1” Elitech STC-9100 Double Sensor Temperature Thermostat-fig8 value cannot be modified to the value you need, please adjust the F3 and F4 (the US and the L5), which are the limitation for F1 Elitech STC-9100 Double Sensor Temperature Thermostat-fig8

Configure the Defrosting

This unit controls the defrosting by Time and Temperature.

  • Temperature Condition: the evaporation sensor temperature is lower than the preset “defrosting Stop temperature” F8 (dte), which is a significant value to prevent over defrost.
  • Time Condition 1: the real-time passes the preset interval time F6 (i d f), a regular parameter for almost all defrosting thermostats.
  • Time Condition 2: If the “defrosting method” you take is the hot gas from the compressor reverse rotary when
    Elitech STC-9100 Double Sensor Temperature Thermostat-fig11 it will count the compressor’s last stops moment plus F5 (ac), which is a protective value to avoid the compressor frequently startup and stops.

The operates method is just like page 1 shows;

  • Elitech STC-9100 Double Sensor Temperature Thermostat-fig12 Defrosting Cycle / Interval Time
  • Elitech STC-9100 Double Sensor Temperature Thermostat-fig13 Defrosting Lasting/Running Time
  • Elitech STC-9100 Double Sensor Temperature Thermostat-fig14Defrosting Stop Temperature
  • Elitech STC-9100 Double Sensor Temperature Thermostat-fig15Defrosting Water Dripping Time
  • Elitech STC-9100 Double Sensor Temperature Thermostat-fig16 Defrosting Mode:
    • Elitech STC-9100 Double Sensor Temperature Thermostat-fig17 Electric-Heating.
    • Elitech STC-9100 Double Sensor Temperature Thermostat-fig21Hot Gas from the compressor.
  • Elitech STC-9100 Double Sensor Temperature Thermostat-fig19Count mode of defrost cycle:
    • Elitech STC-9100 Double Sensor Temperature Thermostat-fig20Cumulative time from the controller power on.
    • Elitech STC-9100 Double Sensor Temperature Thermostat-fig21Cumulative time of the compressor working.
  • Elitech STC-9100 Double Sensor Temperature Thermostat-fig22Display mode when defrosting:
    • Elitech STC-9100 Double Sensor Temperature Thermostat-fig23 Shows the room sensor temperature display.
    • Elitech STC-9100 Double Sensor Temperature Thermostat-fig24Shows the evaporator sensor temp. (continue showing 10 minutes once defrosting over)

Set the External Alarm?

Elitech STC-9100 Double Sensor Temperature Thermostat-fig25

And then check below items

Elitech STC-9100 Double Sensor Temperature Thermostat-fig26

This is not a step-by-step user manual; It just shows the key points. The new user should read the Full-Content Version User Manual

Elitech STC-9100 Double Sensor Temperature Thermostat-fig27

Haswill Electronics
STC-9100 Temperature Control & Monitor System Copyright Haswill-Haswell All Rights Reserved