TP02G-AS1 HMI Text Panel
“
Specifications
- Screen Type: STN-LCD
- Display Color: Monochromatic
- Backlight: Yes
- Resolution: 160 x 32 dots
- Display Range: (W) x (H) = 72 x 22 mm
- Contrast Adjustment: 15 levels
- Language/Font Support:
- ASCII: Alphanumeric (including European characters)
- Taiwan: Big 5 codes (Traditional Chinese Fonts)
- China: GB2324-80 codes (Simplified Chinese Fonts)
Product Usage Instructions
Installation
Please insert the TP02 series into the opening hole of the panel
and tighten the screws. For a firm mounting, use the mounting fixed
support accessory included with the TP02 series. Insert the fixed
support at the back and tighten the screws. The recommended
thickness range for installation is 0.5mm to 9.0mm.
Panel Function Explanation
The TP02G-AS1 is an OPEN-TYPE device designed to be installed in
a control cabinet free of airborne dust, humidity, electric shock,
and vibration. To prevent unauthorized access or accidents, ensure
the control cabinet has safeguards in place. Avoid connecting AC
power to any I/O terminals to prevent damage. The device features
various LED indicators for status and communication.
Back Panel
The back panel features an RS-232 extension port with specific
terminal requirements: 5 PIN terminal/Wire gauge: 12-24 AWG/Torque:
4.5 lb.-inch.
FAQ
Q: What should I do if the LED indicators show abnormal
behavior?
A: If the LED indicators blink quickly along with an alarm
sound, there is an abnormal situation. Refer to the user manual for
troubleshooting steps or contact customer support for
assistance.
Q: Can I adjust the contrast of the display screen?
A: Yes, the TP02G-AS1 allows for contrast adjustment with 15
levels of adjustment. Refer to the user manual for instructions on
how to adjust the contrast based on your preferences.
“`
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
TP02G-AS1
TP-0143030-01 2022-09-06
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Warning
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
ENGLISH
EN TP02G-AS1 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating TP02G-AS1, or to prevent an accident from damaging TP02G-AS1, the control cabinet in which TP02G-AS1 is installed should be equipped with a safeguard. For example, the control cabinet in which TP02G-AS1 is installed can be unlocked with a special tool or key.
EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before TP02G-AS1 is powered up. After TP02G-AS1 is disconnected, Do NOT touch any terminals in a
minute. Make sure that the ground terminal on TP02G-AS1 is correctly grounded in order to prevent electromagnetic interference. FR TP02G-AS1 est un module OUVERT. Il doit être installé que dans une enceinte protectrice (boitier, armoire, etc.) saine, dépourvue de poussière, d’humidité, de vibrations et hors d’atteinte des chocs électriques. La protection doit éviter que les personnes non habilitées à la maintenance puissent accéder à l’appareil (par exemple, une clé ou un outil doivent être nécessaire pour ouvrir a protection). FR Ne pas appliquer la tension secteur sur les bornes d’entrées/Sorties, ou l’appareil TP02G-AS1 pourra être endommagé. Merci de vérifier encore une fois le câblage avant la mise sous tension du TP02G-AS1. Lors de la déconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vérifier que la terre est bien
reliée au connecteur de terre afin d’éviter toute interférence électromagnétique.
Introduction
Product Outline
Displaying Area
Alarm LED Indicator RS-232 LED Indicator RS-485 LED Indicator
Escape / Exit Key
Function Keys Arrow Keys
Enter Key
Panel Function Explanation
Panel component
Explanation
Alarm LED indicator (RED) RS-232 LED indicator (yellow) RS-485 LED indicator (green) Displaying area Escape/Exit key Enter key
Arrow keys
Function keys
Status 1: When power is on, LED will blink slowly for three times. Status 2: When there is an abnormal situation, LED will blink quickly along with an alarm sound.
LED will blink when transmits program and communicates via RS-232.
LED will blink when communicates via RS-485.
Liquid Crystal Module display area. It is used to display current program status. It is used to cancel an incorrect input, or to exit a programming step. It is used to input a value or accept a programming command. UP/Pg Up: It is used to increase the value or move up one page. Pg Dn/DOWN: It is used to decrease the value or move down one page. Left: This key is left direction key and it can be used to select the position of the value. Right: This key is right direction key and it can be used to select the position of the value. F0/0: It is used as a constant 0, or the user can define it as function F0. F1/1: It is used as a constant 1, or the user can define it as function F1. F2/2: It is used as a constant 2, or the user can define it as function F2. F3/3: It is used as a constant 3, or the user can define it as function F3. F4/4: It is used as a constant 4, or the user can define it as function F4. F5/5: It is used as a constant 5, or the user can define it as function F5. F6/6: It is used as a constant 6, or the user can define it as function F6. F7/7: It is used as a constant 7, or the user can define it as function F7. F8/8: It is used as a constant 8, or the user can define it as function F8. F9/9: It is used as a constant 9, or the user can define it as function F9.
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Back Panel Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
RS-232
Extension port
Dimension
5 PIN terminal/Wire gauge: 12-24 AWG/Torque: 4.5 lb.-inch
Front panel (unit: mm [inch])
Right side diagram (unit: mm [inch])
Vertical view (unit: mm)
Mounting dimension (unit: mm [inch])
85 [3.35]
135~136.5[5.31~5.37] Thickness Range 0.5~9mm
Installation
Please insert TP02 series to the opening hole of panel and tighten the screws. However, if a firm mounting TP02 series to the panel is needed, please use the mounting fixed support accessory which is packed together with TP02 series, then insert the fixed support in the back and tighten the screws.
If the fixed support is not installed well, Delta will not guarantee the waterproof function. The screw torque should be 4-5(kg-cm). DO NOT exceed this specification when tightening the screws; otherwise TP02 series may be damaged. Please leave sufficient space (more than 50mm) around the unit for heat dissipation. Notes: Only the front panel is guaranteed by ingress protection rating. The control panel itself must comply with the testing conditions required by the applied ingress protection rating.
Thickness: 0.5~9.0mm
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Specifications
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Function Specifications
Item
TP02G-AS1
Screen type
STN-LCD
Display color
Monochromatic
Backlight
The back-light automatic turn off time is 1 ~ 99 minutes (0 = DO NOT turn off) (The back-light life is about 50 thousand hours at 25°C)
Resolution
160 x 32 dots
5×8 dots, 25 characters×8 rows 8×8 dots, 16 characters×8 rows 8×12 dots, 16 characters×5 rows 8×16 dots, 16 characters×4 rows
Display range
(W) x (H) = 72 x 22 (unit: mm)
Display screen
Contrast adjustment Language/font
15 levels of adjustment ASCII: Alphanumeric (including European characters) Taiwan: (Big 5 codes) Traditional Chinese Fonts China: (GB2324-80 codes) Simplified Chinese Fonts
Font size
ASCII: 5 × 8, 8 × 8, 8 × 12, 8 × 16
Alarm LED indicator (RED)
1. Power on indication (blink for three times) 2. Communication error alarm 3. Special indication by user programming
RS-232 LED indicator (yellow)
It will blink when transmitting program and communicating by using RS-232.
RS-485 LED Indicator (green)
It will blink when communicating by using RS-485.
Program memory
256KB flash memory
RAM of system
32K Byte
Serial communication port RS-232 (COM1)
Unsynchronized transmission method: RS-232 Data length: 7 or 8 bits, Stop bits: 1 or 2 bits Parity: none/odd/even, Transmission speed: 4,800 bps ~115,200 bps RS-232: 9 PIN D-SUB male
External interface
Extension communication port RS-485 (COM2)
Unsynchronized transmission method: RS-485 Data length: 7 or 8 bits, Stop bits: 1 or 2 bits Parity: None/Odd/Even, Transmission speed: 4,800 bps ~115,200 bps RS-485: 5 PIN removal terminal
Extension interface 1. Update firmware version 2. The slot for program copy card
5 PIN removal terminal
Include 24V DC input and RS-485 communication input
Electrical Specifications
Specifications
TP02G-AS1
Communication interface
COM1: RS-232 COM2: RS-485
Waterproof class of front panel IP66 / NEMA4X / UL Type4X (Indoor use only)
Operating temperature for hardware
0 ~ 50°C; 20 ~ 90%RH (non-condensing)
Storage temperature for hardware
-20 ~ 60°C
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Specifications
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
TP02G-AS1
Vibration
5Hzf9Hz = Continuous: 1.75mm / Occasional: 3.5mm 9Hzf150Hz = Continuous: 0.5g / Occasional: 1.0g
Shock
15g peak, 11ms duration, half-sine, three shocks in each direction per axis, on 3 mutually perpendicular axes (total of 18 shocks)
Radiated emission
CISPR11, Class A
Electrostatic discharge immunity EN61000-4-2
Radiated immunity
EN61000-4-3
Electrical fast transient
EN61000-4-4
Altitude
0 ~ 2000 meters
Weight/dimensions
0.24kg; 147 × 97 × 35.5mm (Width(W) × Height(H) × Deep(D))
Cooling method
Natural air cooling
Password Function
1. If the user forgot the password, the password can be cleared by using the following code: 8888. This universal code will clear the password and all TP02 series internal programs. The TP02 series will be reset to the factory settings by using this code also. Please pay close attention when using it.
2. The password can be the alphabet from A to Z or the number from 0 to 9. But it must use the function keys F0 ~ F9 to input the password characters. Please refer to the following table. F0: scrolls in a loop as follows 0ABCDEF0. F1: scrolls in a loop as follows 1GHIJK1. F2: scrolls in a loop as follows 2LMNOP2. F3: scrolls in a loop as follows 3QRSTU V3. F4: scrolls in a loop as follows 4WXYZ4. F5: It just can be used to be constant 5. F6: It just can be used to be constant 6. F7: It just can be used to be constant 7. F8: It just can be used to be constant 8. F9: It just can be used to be constant 9.
Hardware Operation
When the user wants to startup TP02 series, a 24V DC power is needed. After applying 24V DC power to TP02 series, it will enter into the startup display and then enter the user-designed program. Pressing Esc key and holding on for 5 seconds can return to system menu. There are five selections in the system menu and are described below.
Selections Download program Upload program
Copy program
TP02 settings
Explanation
Use the connection cable (UC-PRG020-12A (2M)) to connect the TP02 serial communication port RS-232 to a PC. Then use the TPEditor/DIAScreen software to download an application program to TP02.
Use the connection cable (UC-PRG020-12A (2M)) to connect the TP02 serial communication port RS-232 to a PC. Then use the TPEditor/DIAScreen software to upload an application program from TP02.
Transfer a program between two TP02 units. 1: transmit programs; 2: receive programs. When transmit programs and data between two TP02 units. Set one TP02 to “Receive Program” mode and the other TP02 to “Transmit Program” mode. Please use twisted pair wires to connect the two units via the RS-485 ports.
There are 8 items that used to modify TP02 system settings: 1. Communication protocol: Setting the address of TP02, the control port of PLC, and the communication
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Selections
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Explanation
string for either RS-232 or RS-485. 2. Contrast: Adjust the contrast of LCM display screen. 3. Back-light: adjust the automatic turn off time of LCM. Setting range is 00 ~ 99 minutes. If set to 00, the
LCM Back-light will not turn off. 4. Buzzer: Used to set the buzzer sound, normal mode or quiet mode. 5. Language setting: Used to set the displayed language. English, Traditional Chinese, Simplified
Chinese or user defined language. 6. Password setting: Used to set, enable, and disable the password function. If the password function is
enabled, it will require the user to input a password before entering any system menu. The factory password is 1234. 7. Startup display: Used to select the TP02 startup display. User can select “user defined” to use the file that designed by TPEditor/ DIAScreen and download to TP02. 8. Comm. indicator: The user can determine if the RS-232 and RS-485 LEDs will blink or not during communication.
PLC connection
There are two methods to connect to PLC: 1. Using TP02 serial communication port (COM1) RS-232: set 8-pin DIP switch to RS-485 mode and
connect the cable (UC-MS010-02A(1M)/UC-MS020-01A(2M)/UC-MS030-01A(3M)) to program communication I/O RS-232C of PLC. 2. Using extension communication port (COM2) RS-485: set 8-pin DIP switch to RS-485 mode and connect 5-pin removal terminal of extension communication port to RS-485 of PLC with twisted pair.
Execution
Execute the internal program that download from TPEditor/ DIAScreen or transmitted from other TP02 units. When program is in execution, the user can return to system menu by pressing Escape/Exit (Esc) key for 5 seconds.
Communication Connection
UC-PRG020- 12A(2M)
PC
UC-PRG030-10A( 3M)
D VP PLC
U C- MS010-02A(1M) U C- MS020-01A(2M) U C- MS030-01A(3M)
U C- MS030-03A(3M)
COM1(RS-232)
A H500 PLC
DDBB99male tofeDmBal9eDB9 cable ( (Standardc)able)
AS300 PLC
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to
Connect a PC to
info@automatedpt.com
TP02G via connection
able
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
UC-PRG020-12A (2M) / UC-PRG030-10A(3M)
1. UC-PRG020-12A (2M)
4 1
USB 1 : +5V (RE D) 2 : D- (WHI TE) 3 : D+(G RE E N) 4 : GND( B LA CK)
2. UC-PRG030-10A (3M)
DB9 FemDaBle9Connector
2: Rx 9
5
3: Tx
5: GN D
7: CTS 8: RTS
6
1
DB9 Female CoDnBn9ector
9
5 3 Tx
2 Rx
5 GND
6
1
DDBB9Female Connector
5 2 Rx
9
3 Tx
5 GND
1
6
Connect a DVP-PLC to TP02G via cable UC-MS010-02A(1M)/UC-MS020-01A(2M)/UC-MS030-01A(3M)
UC – MS 0 1 0- 0 2 A (1 M)
8 -8P-PI NINMMIaNleI -MDINI NI-DIN
8 5 2 Rx 4
7
4
Tx G ND
5 8
5V 1, 2
UC -M S 0 2 0- 0 1 A (2 M) / U C -M S 0 3 0- 0 1 A (3 M) 6 3 1
DDBB99Female Connector
3 Tx 9 5
2 Rx
5 GND
7 8
61
1
4
6
Connect a AH-PLC to TP02G via cable UC-MS030-03A(3M)
DB9 MalDe CBo9nnector
5
9
2 Rx
3 Tx
5 GND
1
6
DFDeBBm9a9le
Connector
9
5
3 Tx
2 Rx
5 GND 6
1
Connect a AS-PLC to TP02G via DB9 (MALE) to DB9 (FEMALE) standard cable
DB9 MaleDCBon9nector
5
9
3 Rx
2 Tx
5 GND
1
6
DDCoBBn9n9Feecmtoar le
9
5
3 Tx
2 Rx
5 GND 6
1
Send Quote Requests to info@automatedpt.com Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Documents / Resources
![]() |
DELTA TP02G-AS1 HMI Text Panel [pdf] Instruction Manual TP02G-AS1, TP-0143030-01, TP02G-AS1 HMI Text Panel, TP02G-AS1, HMI Text Panel, Text Panel |