Danfoss LogoENGINEERING TOMORROW
Radiator Thermostat RAS-C² Combi Pack / Radiator Pack
BI-DIRECTIONAL VALVE WITH FLOW-SELECTABLE FEATURE
INSTRUCTION

Installation of valve

The valve is a bi-directional valve * and can be installed horizontally or vertically in either the flow or return pipe.
A built in flow direction selection feature can be used to eliminate the risk of water hammer.

Troubleshooting

In the unlikely event of water hammer being encountered turn the setting ring (see diagram 4) to the other setting. Alternatively if commissioning the whole system, establish the flow direction through each valve using the diagrams below. If the flow direction needs to be changed there is no need to remove the valve, simply turn the setting ring.

  1. Close all radiator valves by turning the valve cover cap clockwise. Leave system to cool.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 1
  2. Start boiler/heating.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 2
  3. Open one valve and determine flow direction. Which pipe heats first?Danfoss RAS-C2 Combi Radiator Thermostat - Figure 3Keymark reference:
    This package contains sensor 013G6040, valve 013G6281 (15mm) or valve 013G6283 (8/10 mm)Danfoss RAS-C2 Combi Radiator Thermostat - Figure 4
  4. Remove cap and turn setting ring according to the drawings – the setting ring is turned by hand only.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 5Danfoss RAS-C2 Combi Radiator Thermostat - Figure 7
  5. Repeat step 3 and 4 until all valves have been set correctly. Sensor may now be fitted or the valve cap temporarily refitted.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 6

* Maximum pressure drop should not exceed 0.45 bar

RAS-C/RAS-D with push-fit

Mounting

  1. Ensure the pipe is pushed to the pipe stop in the elbow.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 8
  2. IMPORTANT: Both nuts have to be tightened It is good practice to check the fitting before use: pull the pipe back to check it is secure.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 9

Dismounting
IMPORTANT:
Ensure system is depressurised before removing fitting.
Push in collet squarely against face of fitting.
With the collet held in this position, the pipe can be pulled out. The fitting can then be re-used.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 10Collet cover and collet clip
Collet covers or collet clips provide added security against unintended pipe disconnection.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 19

Cutting the pipes

  1. Cut the pipe square ensuring that it is free from score marks and burs. For plastic pipe we recommend the use of a plastic pipe cutter, do not use a hacksaw
  2. For plastic pipes, it is essential that a pipe insert is used. This must be of the same make as the pipe. It is important to ensure that all internal burs are removed from the pipe end prior to fitting the insert. Do not use any lubricant.
Specification
Copper pipe According to BS2871 Part 1 / BS EN1057. Max. temp92°C, Max. pressure 3 bar
Plastic pipes: According to BS7291. Max. temp. 92°C.  Max. pressure 3bar

Lockshield valve (type RLV-D) is only included in codes 013G6007Danfoss RAS-C2 Combi Radiator Thermostat - Figure 12

Fitting the Sensor

Installation Guide

  1. Remove cap from valve and turn sensor to Danfoss RAS-C2 Combi Radiator Thermostat - Icon 1
  2. Make sure union nut is turned loosely up towards the sensor body until it is only slightly free of the lower part of the sensor body.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 13
  3. Press the sensor firmly onto the valve.
    Sensor horizontal:
    ensuring that the scale pointer is at top.
    Sensor vertical: ensuring that the scale pointer is at the front.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 14
  4. Whilst holding the sensor firmly on the valve secure connection by turning union nut clock-wise by hand.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 15
  5. Whilst still holding the sensor firmly on the valve, tighten the grey union nut to 5Nm, using parrot nose pliers.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 16
  6. Set desired room temperature.Danfoss RAS-C2 Combi Radiator Thermostat - Figure 17

Removing the Sensor
Turn the sensor to max. position . Turn union nut anticlockwise to release lockingmechanism (4). The sensor can now be separated from the valve.

User Guide

Setting the desired room temperatures
The desired room temperature is set by turning the head. The temperatures obtained are approximately:Danfoss RAS-C2 Combi Radiator Thermostat - Figure 18

Do not cover the thermostat
The thermostat opens and closes as determined by the temperature around it. Therefore the sensor must never be hidden behind thick curtains, furniture, etc. Alternatively a thermostat with remote sensor should be used.
Positive SHUT-OFF feature:
The head can be turned past the Danfoss RAS-C2 Combi Radiator Thermostat - Icon 2 setting (a slight resistance will be felt) to setting “0” at which point the water flow is shut off completely. After also shutting the lockshield valve the radiator may be drained and removed for maintenance and decoration purposes.

Danfoss Logo© Danfoss Climate Solutions | 01/2024
AN325831496588en-GB0401 (013R9677)

Documents / Resources

Danfoss RAS-C2 Combi Radiator Thermostat [pdf] Installation Guide
RAS-C2, RA-FS, 013G6040, 013G6281, 013G6283, RAS-C2 Combi Radiator Thermostat, Combi Radiator Thermostat, Radiator Thermostat, Thermostat
Danfoss RAS-C2 Combi Radiator Thermostat [pdf] Instructions
013R9447, 013G6285, 013G6286, RAS-C2 Combi Radiator Thermostat, RAS-C2 Combi, Radiator Thermostat, Thermostat

References

Leave a comment

Your email address will not be published. Required fields are marked *