Danfoss iC7 Series Air Cooled System Modules Installation Guide
Series Air Cooled System Modules

Optimize installation footprint, speed and reduce costs more than you dreamed possible, with the revolutionary iC7 series air-cooled system modules.

High power density combined with industry-leading heat-pipe thermal management means you achieve a smaller footprint and reduce space requirements in your electrical room. The slim profile enables you to fit more modules within a fixed-width cabinet.

Shrink your system, with smaller enclosures or fewer enclosure sections, and filters which integrate beneath the module.

Integration and scalability are extremely easy, because each unit is designed and tested in thermal independence. This reduces your engineering, assembly, and testing time.

Thermal excellence saves your operating costs with the unique segregated IP54 cooling channel, and reduced heat load in your installation. With the iC7 series aircooled system modules, you enjoy industry benchmark cooling efficiency, even including the thermal load of optionally integrated filters and chokes. Configure your choice of commonmode and dU/dt filter options in the  integration unit located beneath themodule.

With the integration unit, access is so easy: simply pull out the power unit, with no need to remove the power cable. Power terminals are located at the front for easy access.

HIGHLIGHTS

  • Highly compact power unit design requires less space for installation
  • Increase power by paralleling power units with no need for balancing filters
  • Integration unit with built-in filters reduces integration cost
  • Fast power unit replacement with no need for motor cable removal
  • Front-mounted motor cable terminals
  • Lightweight power units facilitate faster and easier servicing
  • Modular and scalable control concept
  • Efficient heat management with back-channel cooling

Secure-by-design
Your drive is equipped with marketleading hardware-based protection against unauthorized access with a built-in crypto chip on the control unit. Use a microSD card to copy settings, log data, download software and activate additional features – all protected by the crypto chip ensuring end-to-end encrypted data transfer.

Functional safety to match your needs
STO SIL3, Pl e as standard makes certification easier. A flexible offering allows the addition of functional safety via fieldbus.

User interfaces
A new range of user interfaces integrate well-known features and functionality. Integration of features in
MyDrive® tools is supported
Halo indicator
More built-in sensors for enhanced control
The iC7 drive has an increased number of built-in sensors. This enables improved control performance, increased protection of application and drive, and capability to support Industrial IoT solutions.

Superior sensorless control
In open or closed loop, the iC7 drive delivers superior shaft performance even at low speed.
Symbol Motor Control
Symbol Motor Control video

 

Filters and accessories
For a complete installation, a range of integrated and separate filter options are available.
Symbol  iC7 Filters

Engineering support
Danfoss provides an extensive selection of support material and tools to help in engineering, such as

  • Dimensioning tools, such as MyDrive® Select, MyDrive® Harmonics and MyDrive® ecoSmart™
  • EPLAN P8 macros
  • Dimensional and electrical drawings

Symbol MyDrive® Simulation
Symbol MyDrive® Virtual
Symbol MyDrive® Hil

Simulation reduces time to market
Remove the constraints of the physical environment and open up new opportunities using iC7 simulation models which perfectly mirror the converter or drive.

You can predict performance, test scenarios, streamline commissioning, and collaborate across teams and locations in an open environment.

Reliably validate interoperability of systems, using high-fidelity hardwarein-the-loop (HIL) simulation support from Danfoss.

The iC7 platform is founded on model-based design, which ensures the simulation models are always valid: up to date and accurate.

These models comply with the FMI standard and are easy to integrate in your simulation platform
Logo
Supported by MyDrive® tools
You can use MyDrive® tools on the device of your choice, supporting the entire lifecycle of the iC7 drive; from selection and dimensioning, through programming and commissioning, to maintenance and support during operation.

Symbol MyDrive® Insight
Product Instruction
What if sensorless open loop performance could match closed loop?
Product Instruction

Quality in focus
Reliable and predictable operation has been a key driver. With an ISO 9001- certified and IATF 16949-compliant quality system combined with use of 6-Sigma principles, quality and reliability are at absolute marketleading standards.

Reliability is assured by design with features such as minimized airflow through the control board section.

Automated assembly enables close control and monitoring of critical processes. The finished drives are 100% full-load tested ensuring reliability before leaving the factory

Scalable and flexible control
Enjoy a new level of performance thanks to rapid-response control.

The control capability is scalable and equipped with Ethernet-based fieldbus and STO inputs as standard. Add more I/Os as needed, to match your applications. Connect to a computer via an Ethernet port, enabling you to use MyDrive® commissioning or service tools.

Conveniently extend functionality
Select the optional integration unit to neatly integrate common mode and/ or dU/dt filters beneath the inverter module. The integration units support both traditional and ducted cooling solutions, and connects/disconnects to the power unit without removing motor cables.

 Features and benefits

Feature Benefit
Efficient heat management: heat pipe technology and segregated main cooling channel (back-channel cooling) – Compact size enables you to pack more power into the space available
Paralleling of 3-phase modules with no output filter required – Modular and scalable solutions for high powers– Simplified spare unit handling
Lightweight – Fast integration and serviceability– High vibration robustness
Optional integration unit for output filter integration, enabling back-channel cooling – Compact size enables you to pack more power into the space available– Fast integration
Pull-out of power unit without removing motor or mains cables, included with integration unit – Fast integration and serviceability
AuxBus internal network for temperature monitoring of filters – Exceptional reliability and robustness for increased uptime
Segregated IP54 cooling channel and dedicated PCB area – Extremely reliable in heavy-duty service, for increased uptime

Air-cooled module

  • Inverter module
    IM10
    Product Instruction
  • Inverter module
    with short integration unit IR10
    Product Instruction
  • Inverter module
    with standard integration unit IR10
    Product Instruction
  • Inverter module
    IM11
    Product Instruction
  • Inverter module
    with short integration unit IR11
    Air-cooled module
  • Inverter module
    with standard integration unit IR11
    Product Instruction
  • AFE Module
    with short integration unit
    Air-cooled module
  • AFE module
    with integration unit IR10/IR11
    Product Instruction
  • AFE & LCL filter
    with standard integration unit IR10/IR11
    Product Instruction
  • LCL filter
    LCL 10/11
    Product Instruction

Modular architecture: Setting the standard for modular control

A flexible, modular, control architecture means you can tailor the control functionality exactly to your needs. You can purchase exactly the control options you need, or replace other PLC components, I/O and external safety components.

This modularity gives you not only more flexibility, but more secure integration of drives in the control system and IT architecture. You achieve faster set-up, and smarter monitoring, data gathering and analytics thanks to support for multiple communication network types.

The purchase cost is lower since you only buy the necessary control options, saving excess unused functionality

The drive can reduce your costs further by substituting for a low-end PLC controller/system, thanks to its IEC 61131-based control architecture.

Program execution close to the process opens new possibilities in fast process control thanks to reduced delays. Built-in security protects your IPR and service business.

Features

  • Expandable bus includes I/O, fieldbus, and expanded safety options
  • Up to 10 control options
  • Slot-independent options
  • Integrated microSD card slot
  • Integrated STO SIL3 safety
  • Programmable (IEC 61131- based)
  • Use the same options for iC7 series air-cooled system modules, liquid-cooled system modules and enclosed drives

Technical information

  • Integrated Ethernet port
  • Dual-channel STO SIL3 integrated as standard
  • Modbus TCP as standard and other fieldbus protocols optional
  • Basic I/O: 6 x DI, 2 x DO,  2 x AI +/-10 V/0-20 mA, 1 x AO(0-10/4-20 mA), 2 x NO/NC RO, 1 x NO RO, 1 x Thermistor
  • One optical fiber pair as communication link with power module or star coupler board
  • For more options such as voltage measurement, temperature measurement, relay option, and encoder option, refer to the Functional extensions fact sheet.

Functional extensions 

  • Control mounting plate mechanics
    Product Instruction
  • Control and option boards
    Product Instruction
    Product Instruction

Key specifications

Mains connection AFE
Mains voltage Uin – 3 x 380-500 V AC (-15%…+10%); 465-740 V DC
Mains frequency – 45-66 Hz
Supply network – TN-S, TN-C, IT and TT
Power factor – cosφ = 1: (fundamental)
Short circuit current – Maximum short circuit current must be < 100 kA
Total harmonics distortion THDi – < 5%
Overvoltage category – Class III according to IEC/EN 61800-5-1
Connections to mains – Once every 120 s
Motor connection (INU)
Output voltage – 0-Uin 3-phase
Output frequency – 0-599 Hz (Limited performance with output filters above 70 Hz)
Switching frequency – 1.5-10 kHz. Default switching frequency 3 kHz DPWM
Motor control principles –  U/f control–  Voltage Vector Control (VVC+)–  Flux Vector Control (FVC+)
Motor and generator types supported –  Induction/asynchronous motor–  Permanent magnet motor–  Salient permanent magnet motor–  Synchronous reluctance assisted permanent magnet motor
Cable length – Up to 150 m [492 feet] with symmetrical 3-phase screened motor cable
EMC (IEC61800-3)
Immunity – Fulfils IEC/EN61800-3 (2018), 2nd environment
Emissions – IEC/EN61800-3 (2018), category C4, default for the IP00/UL Open Type drive– IEC/EN61800-3 (2018), category C3, if the drive is installed according to the instructions of the manufacturer
Environmental conditions
Protection rating drive modules – IP00/UL Open Type
Ambient operating temperature – -15 °C to 0 °C (5 °F to 32 °F) (no frost) The highest current rating of AM11 and IM11 must be derated 20% in freezing conditions.–  0 °C to 40 °C (32 °F to 104 °F) (at IN) with derating up to +15 °C (131 °F)
Storage/transportation temperature – -40 °C to +70 °C (32 °F to 158 °F)
Relative humidity – 5 to 96% RH, no dripping water or condensation allowed
Pollution degree – PD2
Altitude –  0–4000 m (0–13100 ft) above sea level: in case network is not corner-grounded (Voltage class 5).– Above 1000 m (3300 ft): derating of maximum ambient operating temperature by 1 °C per each 100 m is required.
Vibration (IEC60068-2-6) –  Displacement amplitude 0.5 mm (peak) at 5–22 Hz)–  Maximum acceleration amplitude 1 G at 22–150 Hz
Shock (IEC60068-2-27) – Max 15G, 11 ms (in package)
Environmental operating conditions (IEC 60721-3-3 – Climatic conditions: Class 3K5–  Chemically active substances: IEC 60721-3-3 Edition 3.0/ISO 3223 Second Edition, class C4–  Biological conditions: Class 3B1–  Mechanical conditons: Class 3M3–  Mechanically active substances: Class 3S2–  Special climatic conditions (heat radiation): Class 3Z1

Inverter module (INU)

Product Instruction
Inverter module (INU)
The inverter module is a bidirectional DC-fed power inverter for the supply and control of AC motors and generators

The inverter (INU) module is intended for the regulation of motor speed in response to system feedback or to remote commands from external controllers. A drive system consists of the system modules, the motor, and equipment driven by the motor. The INU module is also intended for system and motor status surveillance.

Benefits of the Inverter module

  • Designed for maximum machine performance and flexibility
  • Versatility for drive applications requiring a wide range of drive features for different motor types for either closed loop or open loop control methods
  • Optional system module with integration unit including high performance dU/dt filters and/or common-mode filters for space saving and easy cabinet integration

Ratings

  • 385-4870 A IL , +10% overload 1 min/5 min
  • 380-500 V AC Motor Voltage
  • Output frequency: 0-599 Hz
  • Switching frequency: 1,5-10 kHz. Nominal 3 kHz

Highlights

  • Most compact INU module on the market thanks to integration of filters
  • IP54/Type 12 segregated main cooling channel supporting backchannel cooling solutions
  • Designed for enclosure integration and quick serviceability
  • Integration of common-mode and dU/dt filters in the integration unit
  • Slide-in philosophy for power unit installation means you can remove the power unit without disconnecting the motor cable

Motor control

  • Highly dynamic performance: Highest possible machine accuracy due to superior shaft performance, also for sensorless operation
  • Superior low-speed performance also in sensorless operation
  • The motor always runs at maximum possible torque for the given current – ensuring highest possible motor efficiency: Maximum Torque Per Ampere (MTPA)
  • Fast commissioning using Automatic Motor Adaption (AMA) at standstill maximizes energy efficiency with any motor
  • More integrated sensors for better performance
  • Flexible choice of control features optimized to your application, thanks to integrated application software

Inverter module 1]

400 V AC, 465-650 V DC

Model code

AC current Typical motor power 400 V AC DCcurrrent Frame
IN IL ( 1/5) IH ( 1/5) Imax (3s) PL PH IN-DC IP00
[A] [A] [A] [A] [kW] [kW] [A]
iC7-60SAIN05-385AE00 394 385 320 544 200 160 410 IM/IR10
iC7-60SAIN05-480AE00 490 480 399 679 250 200 510 IM/IR10
iC7-60SAIN05-590AE00 603 590 490 833 315 250 641 IM/IR10
iC7-60SAIN05-658AE00 672 658 547 930 355 250 721 IM/IR11
iC7-60SAIN05-730AE00 746 730 606 1031 400 315 813 IM/IR11
iC7-60SAIN05-820AE00 838 820 681 1158 450 355 913 IM/IR11
iC7-60SAIN05-880AE00 899 880 731 1243 500 400 1015 IM/IR11
iC7-60SAIN05-1000E00 1021 1000 830 1411 560 450 1138 2xIM/IR10
iC7-60SAIN05-1100E00 1123 1100 913 1553 630 500 1280 2xIM/IR10
iC7-60SAIN05-1260E00 1287 1260 1050 1785 710 560 1441 2xIM/IR11
iC7-60SAIN05-1450E00 1481 1450 1210 2057 800 630 1625 2xIM/IR11
iC7-60SAIN05-1710E00 1746 1710 1420 2414 900 710 1826 2xIM/IR11
iC7-60SAIN05-1760E00 1797 1760 1470 2499 1000 800 2030 3xIM/IR11
iC7-60SAIN05-1960E00 2001 1960 1630 2771 1100 900 2234 3xIM/IR11
iC7-60SAIN05-2150E00 2195 2150 1790 3043 1200 1000 2436 3xIM/IR11
iC7-60SAIN05-2340E00 2389 2340 1950 3315 1300 1000 2639 3xIM/IR11
iC7-60SAIN05-2510E00 2563 2510 2090 3553 1400 1100 2841 3xIM/IR11
iC7-60SAIN05-2640E00 2695 2640 2200 3740 1500 1200 3045 4xIM/IR11
iC7-60SAIN05-2880E00 2940 2880 2400 4080 1600 1300 3247 4xIM/IR11
iC7-60SAIN05-3060E00 3124 3060 2540 4318 1700 1400 3450 4xIM/IR11
iC7-60SAIN05-3280E00 3349 3280 2730 4641 1800 1500 3652 4xIM/IR11
iC7-60SAIN05-3420E00 3492 3420 2840 4828 1900 1500 3856 5xIM/IR11
iC7-60SAIN05-3600E00 3675 3600 2990 5083 2000 1600 4058 5xIM/IR11
iC7-60SAIN05-4060E00 4145 4060 3370 5729 2200 1800 4465 5xIM/IR11
iC7-60SAIN05-4320E00 4410 4320 3590 6103 2400 1900 4871 6xIM/IR11
iC7-60SAIN05-4870E00 4972 4870 4050 6885 2700 2200 5478 6xIM/IR11

460 V AC, 650-740 V DC

  Model code AC current Typical motor power 460 V AC DCcurrrent Frame
IN IL ( 1/5) IH ( 1/5) Imax (3s) PL PH IN-DC IP00
[A] [A] [A] [A] [Hp] [Hp] [A]
iC7-60SAIN05-385AE00 394 385 320 544 300 250 380 IM/IR10
iC7-60SAIN05-480AE00 490 480 399 679 350 300 443 IM/IR10
iC7-60SAIN05-590AE00 543 531 441 750 450 350 570 IM/IR10
iC7-60SAIN05-658AE00 603 590 490 833 500 350 632 IM/IR11
iC7-60SAIN05-730AE00 672 658 547 930 550 450 695 IM/IR11
iC7-60SAIN05-820AE00 746 730 606 1031 600 500 758 IM/IR11
iC7-60SAIN05-880AE00 838 820 681 1158 700 550 883 IM/IR11
iC7-60SAIN05-1000E00 940 920 764 1299 750 550 948 2xIM/IR10
iC7-60SAIN05-1100E00 1052 1030 855 1454 850 650 1073 2xIM/IR10
iC7-60SAIN05-1260E00 1174 1150 960 1632 950 750 1200 2xIM/IR11
iC7-60SAIN05-1450E00 1328 1300 1080 1836 1100 850 1389 2xIM/IR11
iC7-60SAIN05-1710E00 1603 1570 1310 2227 1300 1100 1641 2xIM/IR11
iC7-60SAIN05-1760E00 1807 1770 1470 2499 1500 1200 1892 3xIM/IR11
iC7-60SAIN05-1960E00 1940 1900 1580 2686 1600 1300 2021 3xIM/IR11
iC7-60SAIN05-2150E00 2083 2040 1700 2890 1700 1300 2146 3xIM/IR11
iC7-60SAIN05-2340E00 2195 2150 1790 3043 1800 1500 2272 3xIM/IR11
iC7-60SAIN05-2510E00 2389 2340 1950 3315 1900 1600 2397 3xIM/IR11
iC7-60SAIN05-2640E00 2532 2480 2060 3502 2100 1700 2650 4xIM/IR11
iC7-60SAIN05-2880E00 2685 2630 2190 3723 2200 1800 2775 4xIM/IR11
iC7-60SAIN05-3060E00 2828 2770 2300 3910 2300 1800 2902 4xIM/IR11
iC7-60SAIN05-3280E00 3114 3050 2540 4318 2500 2100 3155 4xIM/IR11
iC7-60SAIN05-3420E00 3277 3210 2670 4539 2700 2200 3406 5xIM/IR11
iC7-60SAIN05-3600E00 3573 3500 2910 4947 2900 2300 3658 5xIM/IR11
iC7-60SAIN05-4060E00 3859 3780 3140 5338 3200 2500 4036 5xIM/IR11
iC7-60SAIN05-4320E00 4176 4090 3400 5780 3400 2700 4289 6xIM/IR11
iC7-60SAIN05-4870E00 4625 4530 3760 6392 3700 2900 4667 6xIM/IR11

1] Preliminary values subject to validation
IL: Low overload – 110% overload – 1 min every 5 min
IH: High overload – 150% overload – 1 min every 5 min

500 V AC, 650-740 V DC

  Model code AC current Typical motor power 500 V AC DCcurrrent Frame
IN IL ( 1/5) IH ( 1/5) Imax (3s) PL PH IN-DC IP00
[A] [A] [A] [A] [kW] [kW] [A]
iC7-60SAIN05-385AE00 394 385 320 544 250 200 408 IM/IR10
iC7-60SAIN05-480AE00 490 480 399 679 315 250 513 IM/IR10
iC7-60SAIN05-590AE00 543 531 441 750 355 250 577 IM/IR10
iC7-60SAIN05-658AE00 603 590 490 833 400 315 651 IM/IR11
iC7-60SAIN05-730AE00 672 658 547 930 450 355 731 IM/IR11
iC7-60SAIN05-820AE00 746 730 606 1031 500 400 812 IM/IR11
iC7-60SAIN05-880AE00 838 820 681 1158 560 450 910 IM/IR11
iC7-60SAIN05-1000E00 940 920 764 1299 630 500 1024 2xIM/IR10
iC7-60SAIN05-1100E00 1052 1030 855 1454 710 560 1153 2xIM/IR10
iC7-60SAIN05-1260E00 1174 1150 960 1632 800 630 1300 2xIM/IR11
iC7-60SAIN05-1450E00 1328 1300 1080 1836 900 710 1461 2xIM/IR11
iC7-60SAIN05-1710E00 1603 1570 1310 2227 1100 900 1787 2xIM/IR11
iC7-60SAIN05-1760E00 1807 1770 1470 2499 1200 1000 1949 3xIM/IR11
iC7-60SAIN05-1960E00 1940 1900 1580 2686 1300 1100 2112 3xIM/IR11
iC7-60SAIN05-2150E00 2083 2040 1700 2890 1400 1100 2273 3xIM/IR11
iC7-60SAIN05-2340E00 2195 2150 1790 3043 1500 1200 2436 3xIM/IR11
iC7-60SAIN05-2510E00 2389 2340 1950 3315 1600 1300 2598 3xIM/IR11
iC7-60SAIN05-2640E00 2532 2480 2060 3502 1700 1400 2760 4xIM/IR11
iC7-60SAIN05-2880E00 2685 2630 2190 3723 1800 1500 2922 4xIM/IR11
iC7-60SAIN05-3060E00 2828 2770 2300 3910 1900 1500 3085 4xIM/IR11
iC7-60SAIN05-3280E00 3114 3050 2540 4318 2000 1700 3246 4xIM/IR11
iC7-60SAIN05-3420E00 3277 3210 2670 4539 2200 1800 3572 5xIM/IR11
iC7-60SAIN05-3600E00 3573 3500 2910 4947 2400 1900 3897 5xIM/IR11
iC7-60SAIN05-4060E00 3859 3780 3140 5338 2600 2100 4221 5xIM/IR11
iC7-60SAIN05-4320E00 4176 4090 3400 5780 2800 2300 4546 6xIM/IR11
iC7-60SAIN05-4870E00 4625 4530 3760 6392 3100 2600 5033 6xIM/IR11

1] Preliminary values subject to validation
IL: Low overload – 110% overload – 1 min every 5 min
IH: High overload – 150% overload – 1 min every 5 min

AFE modules

AFE module
The AFE unit is a bi-directional low harmonic supply unit for motor drive applications. Active front end is typically used as a supply to a common  DC bus drive line-ups or high powersingle drives when low harmonics or regeneration of power back to the grid is needed/valued.

The main functionality of the AFE is to maintain stable DC-link voltage reference. The AFE transfers power between the grid and the DC bus both ways depending on the load of the DC bus.

Benefits of the AFE

  • Regenerative energy is fed back to the grid, improving the payback time of the investment. Regeneration at full power is available at any time.
  • The AFE can boost the DC-link voltage within the voltage window of the converter hardware. Its advantage is that the DC-voltage available for motor inverters is not limited even under non-ideal grid conditions
  • Power quality is excellent since the grid current is sinusoidal with very low harmonics (<5% THDi) and power factor is unity (cos φ = 1). This means that there is no need to oversize incoming supply transformers, as for traditional diode rectifiers, which reduces investment costs and space.

Ratings

  • 317-4900 A IL , +10% overload 1 min/5 min
  • 380-500 V AC / 465-740 V DC (05)
  • 45-66 Hz Grid frequency
  • THDi <5%
  • Fundamental power factor cos φ = 1, adjustable reactive current set point

Highlights

  • Most compact AFE on the market
  • Meets the most stringent harmonics requirements thanks to high DC and AC power quality
  • Robust and reliable in varying ambient conditions
  • IP54/Type 12 segregated main cooling channel supporting backchannel cooling solutions
  • Designed for enclosure integration and quick serviceability
  • Direct connection between LCL filter and AFE input terminals
  • Slide-in philosophy for easy power unit and LCL filter installation and removal

DC-bus and grid control

  • Fast primary control ensures stable DC voltage even under non-ideal grid conditions for accurate motor control.
  • AFE is able to boost DC voltage to guarantee full motor voltage even when the supply voltage is below nominal.
  • Low harmonic operation meets even the stringest power quality requirements for drive systems.
  • Reactive reference can be used to compensate other low power factor equipment in the network.
  • Unrivalled paralleling options with no need for drive-to-drive communication
  • Power can be shared between parallel units automatically with DC-link voltage droop control.

 Active front-end modules (AFE)

AFE 400 V AC, 465-650 V DC

  Model code AC ratings DC ratings Frame
SN IN ( 1/5) IL ( 1/5) IH ( 1/5) IN-DC PL PH IP00  AM/AR10
[KVA]220 [A]324 [A]317 [A]263 [A] [kW]216 [kW]
iC7-60SA3A05-317AE00 371 179
iC7-60SA3A05-400AE00 278 409 400 327 469 272 223 AM/AR10
iC7-60SA3A05-514AE00 357 525 514 426 602 349 290 AM/AR10
iC7-60SA3A05-580AE00 402 593 580 464 677 394 316 AM/AR11
iC7-60SA3A05-650AE00 451 664 650 525 760 442 357 AM/AR11
iC7-60SA3A05-730AE00 506 746 730 591 852 496 402 AM/AR11
iC7-60SA3A05-816AE00 566 833 816 678 953 555 461 AM/AR11
iC7-60SA3A05-920AE00 638 940 920 735 1075 625 500 2xAM/AR10
iC7-60SA3A05-1030E00 714 1052 1030 850 1203 700 578 2xAM/AR10
iC7-60SA3A05-1210E00 839 1236 1210 980 1413 822 666 2xAM/AR11
iC7-60SA3A05-1410E00 977 1440 1410 1140 1647 958 775 2xAM/AR11
iC7-60SA3A05-1630E00 1130 1664 1630 1360 1903 1107 924 2xAM/AR11
iC7-60SA3A05-1860E00 1289 1899 1860 1575 2172 1263 1070 3xAM/AR11
iC7-60SA3A05-2120E00 1469 2165 2120 1838 2475 1440 1248 3xAM/AR11
iC7-60SA3A05-2450E00 1698 2501 2450 2030 2861 1664 1379 3xAM/AR11
iC7-60SA3A05-2800E00 1940 2859 2800 2231 3268 1902 1515 4xAM/AR11
iC7-60SA3A05-3270E00 2266 3338 3270 2710 3817 2221 1840 4xAM/AR11
iC7-60SA3A05-3650E00 2529 3726 3650 2888 4260 2479 1961 5xAM/AR11
iC7-60SA3A05-4080E00 2827 4165 4080 3390 4761 2771 2302 5xAM/AR11
iC7-60SA3A05-4500E00 3118 4594 4500 3544 5251 3056 2407 6xAM/AR11
iC7-60SA3A05-4900E00 3395 5002 4900 4070 5719 3327 2764 6xAM/AR11

IL : Low overload – 110% overload – 1 min every 5 min
IH : High overload – 150% overload – 1 min every 5 min

AFE 480 V AC, 650-740 V DC

  Model code AC ratings DC ratings Frame
SN IL ( 1/5) IL ( 1/5) IH ( 1/5) IN-DC PL PH IP00
[KVA] [A] [A] [A] [A] [kW] [kW]
iC7-60SA3A05-317AE00 257 316 309 256 361 252 209 AM/AR10
iC7-60SA3A05-400AE00 316 388 380 298 445 310 243 AM/AR10
iC7-60SA3A05-514AE00 385 473 463 385 542 378 314 AM/AR10
iC7-60SA3A05-580AE00 433 531 520 424 608 424 346 AM/AR11
iC7-60SA3A05-650AE00 487 598 585 470 684 477 383 AM/AR11
iC7-60SA3A05-730AE00 541 664 650 511 759 530 417 AM/AR11
iC7-60SA3A05-816AE00 608 747 731 607 853 596 495 AM/AR11
iC7-60SA3A05-920AE00 686 843 825 639 964 673 521 2xAM/AR10
iC7-60SA3A05-1030E00 774 950 930 770 1086 758 628 2xAM/AR10
iC7-60SA3A05-1150E00 898 1103 1080 880 1262 880 717 2xAM/AR11
iC7-60SA3A05-1280E00 1040 1276 1250 1030 1460 1019 840 2xAM/AR11
iC7-60SA3A05-1630E00 1214 1491 1460 1210 1705 1190 986 2xAM/AR11
iC7-60SA3A05-1860E00 1389 1705 1670 1363 1949 1361 1111 3xAM/AR11
iC7-60SA3A05-2120E00 1588 1950 1910 1533 2230 1557 1250 3xAM/AR11
iC7-60SA3A05-2450E00 1821 2236 2190 1820 2557 1785 1483 3xAM/AR11
iC7-60SA3A05-2800E00 2087 2563 2510 1874 2930 2046 1527 4xAM/AR11
iC7-60SA3A05-3270E00 2428 2981 2920 2430 3408 2380 1980 4xAM/AR11
iC7-60SA3A05-3650E00 2736 3359 3290 2726 3840 2681 2222 5xAM/AR11
iC7-60SA3A05-4080E00 3035 3726 3650 3030 4260 2974 2469 5xAM/AR11
iC7-60SA3A05-4500E00 3334 4094 4010 3152 4681 3268 2569 6xAM/AR11
iC7-60SA3A05-4900E00 3650 4482 4390 3640 5124 3577 2966 6xAM/AR11

1] Preliminary values subject to validation
IL: Low overload – 110% overload – 1 min every 5 min
IH: High overload – 150% overload – 1 min every 5 min

AFE, 500 V AC, 650-740 V DC

  Model code AC ratings DC ratings Frame
SN IL ( 1/5) IL ( 1/5) IH ( 1/5) IN-DC PL PH IP00  AM/AR10
[KVA]268 [A]316 [A]309 [A]256 [A] [kW]263 [kW]
iC7-60SA3A05-317AE00 361 218
iC7-60SA3A05-400AE00 330 388 380 298 445 323 253 AM/AR10
iC7-60SA3A05-514AE00 401 473 463 385 542 393 327 AM/AR10
iC7-60SA3A05-580AE00 451 531 520 424 608 442 360 AM/AR11
iC7-60SA3A05-650AE00 507 598 585 470 683 497 399 AM/AR11
iC7-60SA3A05-730AE00 563 664 650 511 760 552 434 AM/AR11
iC7-60SA3A05-816AE00 634 747 731 607 854 621 516 AM/AR11
iC7-60SA3A05-920AE00 715 843 825 639 963 701 543 2xAM/AR10
iC7-60SA3A05-1030E00 806 950 930 770 1086 790 654 2xAM/AR10
iC7-60SA3A05-1150E00 936 1103 1080 880 1261 917 747 2xAM/AR11
iC7-60SA3A05-1280E00 1083 1276 1250 1030 1459 1061 875 2xAM/AR11
iC7-60SA3A05-1630E00 1265 1491 1460 1210 1704 1240 1027 2xAM/AR11
iC7-60SA3A05-1860E00 1447 1705 1670 1363 1949 1418 1157 3xAM/AR11
iC7-60SA3A05-2120E00 1655 1950 1910 1533 2229 1622 1302 3xAM/AR11
iC7-60SA3A05-2450E00 1897 2236 2190 1820 2557 1859 1545 3xAM/AR11
iC7-60SA3A05-2800E00 2174 2563 2510 1874 2930 2131 1591 4xAM/AR11
iC7-60SA3A05-3270E00 2529 2981 2920 2430 3408 2479 2063 4xAM/AR11
iC7-60SA3A05-3650E00 2850 3359 3290 2726 3840 2793 2314 5xAM/AR11
iC7-60SA3A05-4080E00 3161 3726 3650 3030 4260 3098 2572 5xAM/AR11
iC7-60SA3A05-4500E00 3473 4094 4010 3152 4681 3404 2676 6xAM/AR11
iC7-60SA3A05-4900E00 3802 4482 4390 3640 5124 3726 3090 6xAM/AR11

1] Preliminary values subject to validation
IL: Low overload – 110% overload – 1 min every 5 min
IH: High overload – 150% overload – 1 min every 5 min

Dimensions and weight 1]: INU and AFE modules, LCL filters

Module type Inverter AFE LCL filters
Frame IM10170 IM11 AM10170 AM11 LCL10/LCL11260
[mm] Width 210 210
Height 990 990 990 990 1530
Depth 502 502 502 502 553
[kg] Weight 65 75 65 75
[in] Width 6.7 8.3 6,7 8.3 10.2
Height 39 39 39 39 60.2
Depth 19.8 19.8 19.8 19.8 21.8
[lb] Weight 143 165 143 165

1] Preliminary values subject to validation
For more information refer to the iC7-60 Air-cooled System Modules Operating Guide

Dimensions and weight 2]: INU, AFE and NFE modules with short integration unit

Module type Inverter with integration unit AFE with integration unit NFE with integration unit
Frame IR10235 IR11 AR10235 AR11 NR11235
[mm] Width 235 235
Height 1302 1302 921 921 921
Depth 553 553 553 553 553
[kg] Weight 90 100 72 82
[in] Width 9.3 9.3 9.3 9.3 9.3
Height 51.3 51.3 36.3 36.3 36.3
Depth 21.8 21.8 21.8 21.8 21.8
[lb] Weight 198 221 159 181

2] Preliminary values subject to validation
Weight values are for module with empty integration unit, excluding filter weight . For more information refer to the iC7-60 Air-cooled System Modules Operating Guide

Module with no integration unit
Product Instruction
Module with short integration unit
Product Instruction

Dimensions and weight 2]:
INU, AFE and NFE modules with standard integration unit

Module type Inverter with integration unit AFE with integration unit NFE with integration unit
Frame IR10 IR11 AR10 AR11 NR11
[mm] Width 235 235 235 235 235
Height 1530 1530 1530 1530 1530
Depth 553 553 553 553 553
[kg] Weight 92 102 78 88
[in] Width 9.3 9.3 9.3 9.3 9.3
Height                         60.2 60.2 60.2 60.2 60.2
Depth                          21.8 21.8 21.8 21.8 21.8
[lb] Weight 202.8 224.9 172 194

2] Preliminary values subject to validation
Weight values are for module with empty integration unit, excluding filter weight . For more information refer to the iC7-60 Air-cooled System Modules Operating Guide

Module with standard integration unit
Product Instruction

Imagine versatile and highly secure power conversion and motor control. Intensely powerful and compact converters and drives built to optimize a vast range of systems while giving you the flexibility to distribute intelligence the way you want. Paving the way for a new dimension, where open, connected and intelligent systems are the new reality

Open up a new dimension with iC7 series
iC7-Automation | iC7-Marine | iC7-Hybrid
Contact us

AM424649926039en-000201 | © Copyright Danfoss Drives | 2023.09

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.