Product Information

Specifications

  • Model: ERC 213
  • Type: Electronic refrigeration control
  • Relays: 3
  • Designed for: Commercial refrigeration applications

User Interface
The ERC 213 features a user-friendly interface with key functions that include scrolling, main switch ON/OFF, factory reset, defrost control, back function, pull-down start/stop, set point change, and menu access.

Display Icons

  • Night mode (Energy saving)
  • Fan running
  • Compressor running (Flashes in pull-down mode)
  • Active alarm
  • Defrost

Dimensions and Mounting

  • Dimensions: 83mm x 61.2mm x 66mm
  • Mounting: Rear mounting with lock clips
  • Electrical connections: Refer to the electrical connections diagram for details on wiring.

Product Usage Instructions

Installation

  1. Mount the ERC 213 using the provided drilling template and secure it with clips.
  2. Ensure correct electrical connections based on the provided diagram.
  3. Connect power connectors according to the specified phase requirements.

Initial Configuration
Upon power up, perform quick configuration within 30 seconds by following the specified steps.

Usage

  1. To scroll up or down, perform short presses of less than 1 second.
  2. To turn the main switch ON/OFF, press and hold for approximately 3 seconds.
  3. To access the factory reset function, press and hold at power up.

The ERC 213 is a smart multipurpose refrigeration controller with temperature and defrost management, available with 3 relays. The controller has been designed to fulfill today’s requirements of commercial refrigeration applications

Technical Highlights

  • Ease of use: Four buttons, easy menu structure, and preinstalled application solutions ensure superior usability
  • Simple installation: High performance 16 A relay enables direct connection of heavy loads, such as 2 hp compressors, without use of intermediate relays. A wide range of compatible types of sensors and screw connection terminals ensure high flexibility in installation.
  • Unit protection: Special software features like compressor protection from fluctuation in the power supply or from high condensing temperature ensure the safe operation of the unit.
  • Energy efficiency: Defrost on demand, day/night mode, and smart evaporator fan management ensure energy efficiency

User Interface

Danfoss-ERC-213-Electronic-Refrigeration-Control-FIG- (1)

Dimensions (mm) and mounting

Danfoss-ERC-213-Electronic-Refrigeration-Control-FIG- (3)

 

Electrical connections

Danfoss-ERC-213-Electronic-Refrigeration-Control-FIG- (3)

Note: 2L and 3L must be connected to the same phase.

  • Power connectors: wire size = 0.5 – 1.5 mm2, max. tightening torque = 0.4 Nm
  • Low voltage signal connectors: wire size = 0.15 – 1.5 mm2, max. tightening torque = 0.2 Nm

Quick configuration at power-up

  1. STEP 1: power on
  2. STEP 2: select the quick configuration menu Within 30 seconds of power on, press “<” BACK for 3 seconds. The main switch “r12” is automatically set to OFF.
  3. STEP 3: select pre-installed application o61 The display automatically shows the application selection parameter “o61”Danfoss-ERC-213-Electronic-Refrigeration-Control-FIG- (4) The digital inputs DI1 and DI2 can be configured for multiple functions (refer to Parameters “o02” and “o37”).
    NC = Not configured
    Press SET to select the pre-installed application. The display shows the default value (eg. “AP0” flashing). Choose the application type by pressing UP/DOWN and press SET to confirm. The controller presets parameter values according to the selected application and does not hide relevant parameters. Tip: you can easily move from AP0 to AP7, and thus select the simplified list of parameters, by pressing the UP key (circular list).
  4. STEP 4: select sensor type “o06 The display automatically shows the sensor selection parameter “o06”. Press SET to select the sensor type. The display shows the default value (eg. “n10” flashing). Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm.
    Note: All sensors must be the same type.
  5. STEP 5: configure DO2 output “o71”
    The display automatically shows the “o71” parameter to configure the “DO2” output. Select the required configuration (DEF or Lig or ALA) as per the application and press SET to confirm. The display returns to normal display mode and the control is started.

Danfoss-ERC-213-Electronic-Refrigeration-Control-FIG- (5)

Quick Configuration via “cFg” Menu

  1. Press the “SET” button for 3 seconds to access the parameter menu (display will show “cFg”).
  2. Enter the “CFg” menu by pressing the “SET” button (display will show first parameter “r12” main switch.
  3. Select “r12” by pressing “SET” button again and set the main switch to “oFF” (r12=0).
  4. Press the back button (<) to come back to the ‘CFg” menu.
  5. Press the DOWN button to scroll through the “cFg” menu parameter list.
  6. Open the “061 application mode” and select the needed application mode (Press SET).
  7. Open the “007 Cooling/Heating” and select the needed function and press”SET” (applicable only for APO and AP5).
  8. Open the “006 Sensor type” and select the temperature sensor type used (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000)- (Press “SET”).
  9. Open the “071 DO2 configuration” and select the function associated to DO2 output and press “SET”.
  10. Open the “002 DI1 Configuration” and select the function associated to digital input 1 (Press “SET”).
  11. Open the “037 DI2 Configuration” and select the function associated to digital input 2 (Press “SET”).
  12. Navigate back to parameter “r12 Main switch” and set it in “ON” position to start control.
  13. Go through other parameters’ default settings and change wherever needed.

Technical specifications

Features Description
Purpose of control Operating temperature sensing control suitable for incorporation into commercial air- conditioning and refrigeration applications
Construction of control Incorporated control
Power supply 115 V AC / 230 V AC 50/60 Hz, galvanic isolated low voltage regulated power supply
Rated power Less than 0.7 W
Inputs Sensor inputs, Digital inputs, Programming key Connected to SELV limited energy <15 W
Allowed sensors types NTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C – EKS 211)

NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C – EKS 221)

PTC 990 Ohm at 25 °C, (EKS 111)

Pt1000, (AKS 11, AKS 12, AKS 21)

Sensors included in Kit Solution NTC 10000 Ohm at 25 °C, cable length: 1.5 m
Accuracy Measuring range:

-40 – 105 °C (-40 – 221 °F)

Controller accuracy:

±1 K below -35 °C, ±0.5 K between -35 – 25 °C

±1 K above 25 °C

Type of action 1B (relay)
Output DO1 – Relay 1:

16 A, 16 (16) A, EN 60730

10 FLA/60 LRA at 230 V, UL60730

16 FLA/72 LRA at 115 V, UL60730

DO2 – Relay 2:

8 A, 2 FLA/12 LRA, UL60730

8 A, 2 (2 A), EN60730

Features Description
  DO3 – Relay 3:

3 A, 2 FLA / 12 LRA, UL60730-1

3 A, 2 (2 A), EN60730-1

Display LED display, 3 digits, decimal point and multi-function icons, °C + °F scale
Operating conditions -10 – +55 °C (14 – 131 °F), 90% Rh
Storage conditions -40 – +70 °C (-40 – +158 °F), 90% Rh
Protection Front: IP65 (Gasket integrated) Rear: IP00
Environmental Pollution degree II, non-condensing
Overvoltage category II – 230 V supply version – (CE, UL recognized) III – 115 V supply version – (UL recognized)
Resistance to heat and re UL94-V0

Temperature for ball pressure test statement According to Annex G (EN 60730-1)

EMC category Emission: IEC/EN 61000 6-3

Immunity: IEC/EN 61000 6-2

Approvals UL recognition (US & Canada) (UL 60730-1) CQC

CE (LVD & EMC Directive) EAC

NSF ROHS2.0

HACCP temperature monitoring in compliance with EN13485 Class I, when used with AKS 12 sensor

Parameter List

Function Code Min Max AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7
Con guration cFg  
Main switch ( -1=Service 0=OFF, 1=ON,) r12 -1 1 1 1 1 1 1 1 1 1
Pride ned applications o612 AP0 AP7 AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7
Cooling/Heating (rE=Cooling, Ht= Heating) o072 rE Ht rE rE1 rE1 rE1 rE1 rE1 rE Ht1
Sensor type (n5=NTC 5K, n10=NTC10K, ptc=PTC, pt1=PT1000) o062 n5 ptc n10 n10 n10 n10 n10 n10 n10 n10
DO2 con g (dEF=Defrost; ALA=alarm; Lig=Light) o712 dEF Lig dEF ALA1 dEF1 dEF1 dEF1 dEF1 dEF ALA
Reference r-  
Setpoint (unit: °C) r00 -100 200 2 4 2 -20 2 -24 2 50
Dierential (unit: K) r01 0.1 20 2 2 2 2 2 2 2 4
Maximum set point limitation (unit: °C) r02 -100 200 50 6 4 -18 4 -20 50 70
Minimum set point limitation (unit: °C) r03 -100 200 -35 2 0 -24 0 -26 -35 30
Display o set (unit: K) r04 -10 10 0 0 0 0 0 0 0 0
Display Unit (°C/ °F) r05 -C -F -C -C -C -C -C -C -C -C
Calibration of Sair (unit: K) r09 -20 20 0 0 0 0 0 0 0 0
Main switch ( -1=Service 0=OFF, 1=ON,) r12 -1 1 1 1 1 1 1 1 1 1
Night Set back (unit: K) r13 -50 50 0 0 0 0 0 0 0 0
Reference displacement

o set temperature (unit: °C)

r40 -50 20 0 0 0 0 0 0 0
Pull down duration (unit: min) r96 0 960 0 0 0 0 0 0
Pull down limit temperature (unit: °C) r97 -100 200 0 0 0 0 0 0
  1. This option is a default setting in the controller and cannot be changed.
  2. This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0.
Function Code Min Max AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7
Alarm A-  
Delay for temp alarm during normal conditions (unit: min) A03 0 240 30 45 30 30 30 30 30 10
Delay for temp alarm during pull-down/startup/defrost (unit: min) A12 0 240 60 90 60 60 60 60 60
High temp. alarm limit (unit: °C) A13 -100 200 8 10 8 -15 8 -15 8 80
Low temp. alarm limit (unit: °C) A14 -100 200 -30 0 -2 -30 -2 -30 -30 20
DI1 delay (Time delay for selected DI1 function) (unit: min) A27 0 240 30 30 30 30 30 30 30 30
DI2 delay (Time delay for selected DI2 function) (unit: min) A28 0 240 30 30 30 30 30 30 30 30
Condenser High alarm limit (unit: °C) A37 0 200 80 80 80 80 80 80
Condenser High block limit (unit: °C) A54 0 200 85 85 85 85 85 85
Voltage protection enable A72 no YES no no no no no no no no
Minimum cut-in voltage (unit: V) A73 0 270 0 0 0 0 0 0 0 0
Minimum cut-out voltage (unit: V) A74 0 270 0 0 0 0 0 0 0 0
Maximum voltage (unit: V) A75 0 270 270 270 270 270 270 270 270 270
Defrost d-  
Defrost Method (no=None, nAt=Natural, EL = Electric; gAS=Hot gas) d01 no gAS EL nAt EL EL EL EL EL
Defrost stop temperature (unit: °C) d02 0 50 6 6 6 6

This option is a default setting in the controller and cannot be changed.

Function Code Min Max AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7
Defrost Interval (unit: hour) d03 0 240 8 6 8 12 8 12 8
Max defrost Time (unit: min) d04 0 480 30 45 15 15 30 30 30
Defrost delay at power up (unit: min) d05 0 240 0 0 0 0 0 0 NA
Drip delay (unit: min) d06 0 60 0 0 0 0 0 0 21
Fan delay after defrosting (unit: min) d07 0 60 0 0 0 0 0 0 51
Fan start temperature after defrosting (unit: °C) d08 -50 50 -5 501 501 501 -5 -5
Fan during defrosting d09 OFF on on on OFF OFF OFF OFF OFF
Defrost stop sensor non=None (Time), Air = Sair temp. sensor, dEF= S5 Defrost sensor d10 non dEF non non1 non1 non1 dEF1 dEF1 non
Accumulated Compressor runtime to start defrost (0=OFF) (unit: hour) d18 0 96 0 0 0 0 0 0
Defrost on demand (20=OFF) (unit: K) d19 0 20 20 201 201 201 20 20
Defrost delay after pull-down cycle (unit: min) d30 0 960 0 0 0 0 0 0
Fan control F-  
Fan at compressor cutout (FAo=Fan always ON; FFC=Fan follow compressor; FPL= Fan Pulsating) F01 Fao FPL FAo FAo FAo FAo FAo FAo FAo FAo
Fan stop evap. Temperature (unit: °C) F04 -50 50 50 50 50 50
Fan ON Cycle (unit: min) F07 0 180 2 2 2 2 2 2 21 2
Fan OFF cycle (unit: min) F08 0 180 2 2 2 2 2 2 21 2

This option is a default setting in the controller and cannot be changed.

Function Code Min Max AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7
Compressor c-  
Compressor / Heater minimum ON time (unit: min) C01 0 30 0 0 0 0 0 0 0 0
Compressor /Heater minimum OFF time (unit: min) C02 0 30 2 2 2 2 2 2 2 2
Compressor OFF delay at open door (unit: sec) C04 0 900 900 900 900 900 900 900 601 900
Zero crossing selection (YES / no) C70 no YES YES YES YES YES YES YES YES1 YES
Others o-  
Delay of outputs at startup (unit: sec) o01 0 600 10 10 10 10 10 10 101 10
DI1 con guration o02 nC Sc nC nC nC nC nC nC nC nC
Serial address (unit: No) o03 0 247 0 0 0 0 0 0 0
Password (unit: No) o05 0 999 0 0 0 0 0 0 0 0
Sensor type (n5=NTC 5K, n10=NTC10K, ptc=PTC, pt1=PT1000) o062 n5 ptc n10 n10 n10 n10 n10 n10 n10 n10
Cooling/Heating (rE=Cooling, Ht= Heating) o072 rE Ht rE rE1 rE1 rE1 rE1 rE1 rE Ht1
Display Resolution o15 0.1 1.0 0.1 0.1 0.1 0.1 0.1 0.1 0.11 0.1
DI2 con guration o37 nC Pud nC nC nC nC nC nC nC nC
Light Control on= Always on, dAn = Day/Night,

doo=Based on door action

o38 on doo on on on on on on on on
Prede ned applications o612 AP0 AP7 AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7
Save settings as factory WARNING: The earlier factory settings are overwritten o67 no YES no no no no no no no
  1. This option is a default setting in the controller and cannot be changed.
  2. This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0.
Function Code Min Max AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7
DO2 con g (dEF=Defrost; ALA=alarm; Lig=Light) o712 dEF Lig dEF ALA1 dEF1 dEF1 dEF1 dEF1 dEF ALA
Display during defrost Air=actual air temperature, FrE=freezed temperature,

-d-=”-d-” is displayed

o91 Air -d- -d- -d- -d- -d- -d- -d- -d-1

Note: DI1 & DI2 configuration list as follows –

  • nC= Not configured; Sdc = Status display output, doo = Door alarm with resumption,
  • doA = Door alarm without resumption, SCH = Main switch, nig = Day/ Night mode,
  • rFd = Reference displacement, EAL = External alarm, dEF = Defrost,
  • Pud = Pull down; Sc = Condensor Sensor
  1. This option is a default setting in the controller and cannot be changed.
  2. This parameter can only be set when regulation is stopped, i.e. “r12” is set to 0.
Function Code Min Max AP0 AP1 AP2 AP3 AP4 AP5 AP6 AP7
Polarity P-  
DI1 input polarity (nc / no) no = normally open,

nc = normally closed

P73 no nc no no no no no no no no
DI2 input polarity (nc / no) no = normally open,

nc = normally closed

P74 no nc no no no no no no no no
Invert alarm relay (0= normal,

1= invert relay action)

P75 0 1 0 0 0 0 0 0 0
Key board lock (no / yes) (0=no, 1=yes) P76 no YES no no no no no no no
Code Alarms Description
E29 Sair sensor error Air temperature sensor error
E27 Def sensor error S5 Evaporator sensor is defective or the electrical connection is lost
E30 Sc sensor error Sc Condenser sensor is defect or electrical connection is lost
A01 High temp alarm Air temperature in cabinet is too high
A02 Low temp alarm Air temperature in cabinet is too low
A99 High Volt alarm Supply voltage is too high (compressor protection)
AA1 Low Volt alarm Supply voltage is too low (compressor protection)
A61 Condenser alarm Condenser temp. too high – check air ow
A80 Cond. block alarm Condenser temp. too high – manual reset of alarm required1)
A04 Door alarm Door has been open for too long
A15 DI Alarm External alarm from DI input
A45 Standby Alarm Control has been stopped by “r12 Main switch”

The condenser block alarm can be reset by setting r12 Main switch OFF and ON again or by powering down the controller.

Safety Standards
Check if the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: Use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent the formation of condensation.

Disposal of the Product
The appliance (or the product) must be disposed in accordance with the local waste disposal legislation.

EU design registration
002566703-0001

DanfossA/S

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogs descriptions, advertisements, etc. and whether made available in writing, orally, electronically, on line or via download, shall be considered informative and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogs, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to the form, fit or function of the product.

All trademarks in this material are property of Danfoss A/5 or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/5. All rights reserved.

FAQ

Q: How many relays does the ERC 213 have? 
A: The ERC 213 is equipped with 3 relays for versatile control options.

Q: What is the night mode icon for?
A: The night mode icon indicates an energy-saving mode for efficient operation during specific hours.

Documents / Resources

Danfoss ERC 213 Electronic Refrigeration Control [pdf] Installation Guide
080R9313, ERC 213 Electronic Refrigeration Control, ERC 213, Electronic Refrigeration Control, Refrigeration Control, Control
Danfoss ERC 213 Electronic Refrigeration Control [pdf] Installation Guide
ERC 213 Electronic Refrigeration Control, ERC 213, Electronic Refrigeration Control, Refrigeration Control, Control
Danfoss ERC 213 Electronic Refrigeration Control [pdf] User Guide
AI240786442776en-000301, ERC 213 Electronic Refrigeration Control, ERC 213, Electronic Refrigeration Control, Refrigeration Control

References

Leave a comment

Your email address will not be published. Required fields are marked *