Quick start guide ERC 213


File Info : application/pdf, 4 Pages, 454.37KB

PDF preview unavailable. Download the PDF instead.

AI240786442776en-000301
Quick Start Guide ERC 213

Overview
The ERC 213 is designed to be an easy, universal replacement control. We encourage users to employ one of five predefined applications that meet the needs of most systems. If users need to modify specific parameters, it should be done after installing the predefined application that most closely meets system needs.
For more information, including detailed instructions, error codes, parameters, and more, visit www.danfoss.com/erc or download the Koolcode app from iTunes or Google Play.
For a video guide of the quick set-up, visit http://bit.ly/ERC213 or use the QR code located to the right.

Quick Set-up

STEP Action

Screen Display

STEP 1 Wire control, to include power and sensors

Power up control STEP 2
Energize control

Control turns on, goes through start up, then shows the current temperature reading

Enter Quick Configuration Menu and Select app

Press "<" for more than three seconds within one minute of power up to enter Quick Configuration Menu. o61 appears on screen

STEP 3

Press "set" while o61 is on screen

AP0 flashes on screen

Select appropriate app using App Selection section below by pressing " " or " ", then press "set".

o06 appears on screen

Select Sensor

Press "set" while o06 is on screen

n10 flashes on screen

STEP 4 If using included sensor, leave default value "n10". If using another sensor, select using Sensor Resistance

section on opposing page or cycle through steps 2 ­ 4 changing the sensor type until the temperature reading o06 appears on screen, then control resets

on the main screen is accurate. As above, cycle between options by pressing " " or " " and press "set" to save.

Set Temperature STEP 5 From main screen, quickly press "set" (1 second).
Cycle to intended temperature by pressing " " or " " and press "set" to save.

Current temp. setting appears on screen Screen returns to main screen

App Selection
Select application based on application and wiring configuration (i.e., refrigeration vs. freezing, and number of temperature sensors). The Typical Wiring Configurations diagram on the reverse side of this document may be used to assist with selection. All parameters can be modified using the full menu. Some parameters have min and max set points which may need to be changed for less common configurations.

Control Application Code

Application

Defrost Type*

Defrost Termination

Sensors

AP0 (Default)

No preset application - full menu

2

AP1

Refrigeration Natural

Time

1

AP2

Refrigeration Electric

Time

1

AP3

Freezing

Electric

Time

1

AP4

Refrigeration Electric

Temp.

2

AP5

Freezing

Electric

Temp.

2

AP6

No preset application - simplified menu

2

* Hot gas defrost is an option available in full menu (d01).

Default Temp. [°F]
[r00]

Temp. Range

min./max. Default Dif.

[°F]

[°F] [r01]

[r02/r03]

36

-31 / 22

4

39

36 / 43

4

36

32 / 39

4

-11

-15 / -4

4

36

32 / 39

4

-11

-15 / -4

4

36

-31 ­ 122

4

Defrost Interval
[hrs] [d03]
6 4 6 6 6 6 6

Max. Defrost Time [mins] [d04]

Defrost Termination Temp. [°F]
[d02]

30

43

30

­

15

­

15

­

30

43

30

43

30

43

Key Functions and Display Icons

Key Functions

Press and hold at power up: FACTORY RESET ("FAC" is displayed)

Press for one second: UP Press and hold: ON/OFF
Press for one second: DOWN Press and hold: DEFROST

Press for one second: BACK Press and hold: PULL-DOWN
Display Icons
Night mode (Energy saving)

Press for one second: TEMP. SETPOINT/OK SET Press and hold: MENU
Fan running

Compressor running (Flashes in pull-down mode)

Active alarm

Defrost

°C Unit (°C or °F)

Connection Diagram

DO1 12

DO2 DO3 3L 4N 5 6 7

Programming key ­ EKA 183B (080G9741) GND TX RX +5V 15 16 17 18

GND

GND

8 9 10 11 12 13 14

~ ~ ~~
Power supply (according to the product code number)

Sair

S5 Sc/DI1

DI2

­ Sair Control sensor ­ S5 Defrost (evaporator) sensor ­ SC Condenser sensor ­ DI1 Digital input ­ configurable to the functions listed under
menu code o02 ­ DI2 Digital input ­ configurable to the functions listed under
menu code o37

© Danfoss | DCS (ADAP-KOOL®) | 2018-11

DKRCE.PD.RL0.A3.02 | 1

Quick Start Guide, ERC 213

Sensor Resistance: Using an ohmmeter, you can measure resistance of a sensor to identify sensor type or to troubleshoot a potentially faulty sensor.

Sensor Type

Code

Resistance [ohm] at Temperature [°F]

0

20

32

75

PTC PTC 1000 NTC 10000 * NTC 5000 * Included in kit

Ptc

690

761

807

980

Pt1

931

974

1000

1093

n10

70317

40411

29481

10459

n5

42664

23110

16325

5251

Common Functions Adjust Temperature Set Point From main screen, quickly press "set" (one second). The current temperature setting will appear on screen. Cycle to intended temperature by pressing "^" or "^" and press "set" to save. The display will return to the main screen.
Adjust Differential From main screen, press "set" for more than three seconds. Cycle to "r--" submenu by pressing " " or " " and press "set." Cycle to "r01" and press "set." Cycle to preferred differential setting, and press "set" to save. "r01" will appear on screen. Press "<" twice to return to main screen. Manual Defrost From main screen, press defrost for more than three seconds to initiate defrost. The DEFROST icon is shown during defrost. Press defrost key for at least three seconds to stop manual defrost.
Factory Reset Press and hold " " and " " simultaneously at power up.
Unlock Keypad After 5 minutes of no activity, the keypad will lock if P76 = yes (by default it is set to no). When the keypad is locked any key press shows "LoC" in the display. Press " " and " " simultaneously for three seconds to unlock the keyboard. "unl" is displayed for three seconds.

Technical Specifications

Power Supply Inputs

080G3411 115V AC 50/60 HZ; 080G3412 230V AC 50/60 Hz
4 total; 2 analog, 1 analog/digital, 1 digital

Sensor Included in Kit NTC 10000

Output

D01 Compressor Relay
115 V (080G3268): 16 FLA/72 LRA 230 V (080G3269): 10 FLA/60 LRA
D02 Defrost Relay and/D03 Fan Relay

8A, 2 FLA, 12 LRA

Operating Conditions 14 ­ 131 °F

Storage Conditions -40 ­ 158 °F

Approvals

UL Recognized/NSF

Typical Wiring Configurations

ERC 213 - APP 1

DI1 DI2

Sair (Control Sensor)

ERC 213 - APP 2-3

DI1 DI2

Sair (Control Sensor)

ERC 213 - APP 4-5
Sair S5 (Control DI1 DI2 (Defrost) Sensor)

115 V AC 230 V AC
DO1

DO2 DO3

115 V AC 230 V AC

DO1 DO2 DO3

115 V AC 230 V AC

DO1 DO2 DO3

Troubleshooting Power Supply Code
A01 A02

Common Alarm/ Error Codes

E27

E29

Description High temperature alarm Low temperature alarm Defrost sensor error
Air temperature sensor error

Remedy (applicable parameter code in parenthesis) Bring down temperature or increase high limit alarm limit (A13) Increase temperature or low temperature alarm limit (A14) Verify that defrost sensor is wired into terminals 10 and 11 Verify that correct sensor type is selected (o06) Verify that control sensor is wired into terminals 9 and 10 ­ 8 is not used Verify that correct sensor type is selected

Problem

Likely Cause

Remedy (applicable parameter number in parenthesis)

Common Problems / Resolution

Compressor does not start

Waiting for compressor delay timer Defrost in progress

Check compressor minimum off time (CO2) Check defrost interval (d03) Check defrost on demand (temp. initiated defrost) (d19)

Defrost does not start Controller in pull down mode

Check pull-down duration (r96)

Wrong temperature Wrong type of sensor selected

Verify that correct sensor type is selected (o06)

is displayed

Sensor installed into incorrect terminals Verify that control sensor is wired into terminals 9 and 10 ­ 8 is not used

Evaporator icing

Defrost interval too long Defrost time too short

Reduce defrost interval (d03) Increase max. defrost time (d04)

Need additional help with programming, parameters, or error codes? Download Danfoss' Koolcode app.

2 | DKRCE.PD.RL0.A3.02

© Danfoss | DCS (ADAP-KOOL®) | 2018-11

Quick Start Guide, ERC 213

Parameter sheet

Parameter Name

Menu Code

Unit

Min. Value

Max. Value

Default Value

Value

Predefined applications

o61

­

­

­

App0

App0

Sensor type

o06

­

­

­

n10

n10

Temperature Setpoint

r00

°C

-100

200

2

2

Differential

r01

K

0.1

20

2

2.7

Min. set point limit

r02

°C

-100

200

-35

-35

Max. set point limit

r03

°C

-100

200

50

50

Display offset

r04

K

-10

10

0

0

Display Unit

r05

­

­

­

°C

°F

Calibration of Sair

r09

K

-20

20

0

0

Night Set back

r13

K

-50

50

0

0

Offset reference displacement

r40

°C

-50

20

0

0

Pull down duration

r96

min..

0

960

0

0

Pull down temp limit

r97

°C

-100

200

0

0

Alarm delay - Normal conditions

A03

min.

0

240

30

30

Alarm delay - pulldown / startup / def

A12

min.

0

240

60

60

High temp alarm

A13

°C

-100

200

8

8

Low temp alarm

A14

°C

-100

200

-30

-30

DI1 delay

A27

min.

0

240

30

30

DI2 delay

A28

min.

0

240

30

30

Condenser High temp alarm

A37

°C

0

200

80

80

Condenser High block limit

A54

°C

0

200

85

85

Voltage protection

A72

­

­

­

No

No

Min. cut-in voltage

A73

V

0

270

0

0

Min. cut-out voltage

A74

V

0

270

0

0

Max. voltage

A75

V

0

270

270

270

Defrost Method

d01

­

­

­

Electric

Electric

Defrost stop temperature

d02

°C

0

50

6

6.5

Defrost Interval

d03

hour

0

240

8

6

Max. defrost Time

d04

min.

0

480

30

30

Defrost delay at power up

d05

min.

0

240

0

0

Drip delay

d06

min.

0

60

0

0

Fan delay after defrost

d07

min.

0

60

0

0

Fan start temp after defrost

d08

°C

-50

0

-5

-5

Fan ON during defrost

d09

­

­

­

On

On

Defrost stop sensor

d10

­

­

­

None

None

Comp accumulated runtime

d18

hour

0

96

0

0

Defrost on demand

d19

K

0

20

20

20

Defrost delay after pulldown

d30

min.

0

960

0

0

Fan at compressor cutout

F01

­

­

­

FFC

FAo

Fan stop evaporator temp

F04

°C

-50

50

50

50

Fan ON time

F07

min.

0

15

2

2

Fan OFF time

F08

min.

0

15

2

2

© Danfoss | DCS (ADAP-KOOL®) | 2018-11

DKRCE.PD.RL0.A3.02 | 3

Quick Start Guide, ERC 213

Parameter Name

Menu Code

Unit

Compressor min. ON time

C01

min.

Compressor min. OFF time

C02

min.

Comp OFF delay at open door

C04

min.

Zero crossing

C70

­

Delay of outputs at startup

o01

sec

DI1 configuration

o02

­

Serial address

o03

­

Password

o05

­

Display Resolution

o15

­

Relay 1 counter

o23

­

Relay 2 counter

o24

­

Relay 3 counter

o25

­

DI2 configuration

o37

­

Display during defrost

o91

­

DO2 Config

o71

­

DI1 polarity

P73

­

DI2 polarity

P74

­

Invert alarm relay

P75

­

Keyboard lock

P76

­

Main switch

r12

­

Controller status

u00

­

Air temperature (Sair)

u01

°C

Present regulation reference

u02

Evaporator temperature (S5)

u09

°C

DI1 status

u10

­

Night mode

u13

­

DI2 status

u37

­

Condenser temperature (Sc)

U09

­

Compressor relay status

u58

­

Fan relay status

u59

­

Defrost relay status

u60

­

Firmware version

u80

­

Database version

­

­

Order No Low

­

­

Air temperature sensor(Sair) error

E29

­

Defrost sensor (S5) error

E27

­

Condensor sensor(Sc) error

E30

­

High temperature alarm

A01

­

Low temperature alarm

A02

­

High voltage alarm

A99

­

Low voltage alarm

AA1

­

High condenser temperature alarm

A61

0

Door alarm

A04

0

DI external alarm

A15

0

Min. Value 0 0 0 ­ 0 ­ 0 0 ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­

Max. Value 30 30 15 ­ 600 ­ 247 999 ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­

Default Value 0 2 0 yes 5 Off 0 0 0.1 ­ ­ ­ Off -ddef no no
Normal No Off S25 ­ ­ ­ Off Off Off
Off Off Off ­ ­ ­ Off Off Off Off Off Off Off Off Off Off

Value 0 2 0 yes 5 Off 0 0 1 0 0 0 Off -ddef no no
Normal No On S20 321 0 0 Off Off Off 0 Off On Off 4.16 4.02 3502 On Off Off Off Off Off Off Off Off Off