User Guide for Danfoss models including: AI240786442776en-000301, ERC 213 Electronic Refrigeration Control, ERC 213, Electronic Refrigeration Control, Refrigeration Control
File Info : application/pdf, 4 Pages, 454.37KB
DocumentDocumentQuick Start Guide ERC 213 Overview The ERC 213 is designed to be an easy, universal replacement control. We encourage users to employ one of five predefined applications that meet the needs of most systems. If users need to modify specific parameters, it should be done after installing the predefined application that most closely meets system needs. For more information, including detailed instructions, error codes, parameters, and more, visit www.danfoss.com/erc or download the Koolcode app from iTunes or Google Play. For a video guide of the quick set-up, visit http://bit.ly/ERC213 or use the QR code located to the right. Quick Set-up STEP Action Screen Display STEP 1 Wire control, to include power and sensors Power up control STEP 2 Energize control Control turns on, goes through start up, then shows the current temperature reading Enter Quick Configuration Menu and Select app Press "<" for more than three seconds within one minute of power up to enter Quick Configuration Menu. o61 appears on screen STEP 3 Press "set" while o61 is on screen AP0 flashes on screen Select appropriate app using App Selection section below by pressing " " or " ", then press "set". o06 appears on screen Select Sensor Press "set" while o06 is on screen n10 flashes on screen STEP 4 If using included sensor, leave default value "n10". If using another sensor, select using Sensor Resistance section on opposing page or cycle through steps 2 4 changing the sensor type until the temperature reading o06 appears on screen, then control resets on the main screen is accurate. As above, cycle between options by pressing " " or " " and press "set" to save. Set Temperature STEP 5 From main screen, quickly press "set" (1 second). Cycle to intended temperature by pressing " " or " " and press "set" to save. Current temp. setting appears on screen Screen returns to main screen App Selection Select application based on application and wiring configuration (i.e., refrigeration vs. freezing, and number of temperature sensors). The Typical Wiring Configurations diagram on the reverse side of this document may be used to assist with selection. All parameters can be modified using the full menu. Some parameters have min and max set points which may need to be changed for less common configurations. Control Application Code Application Defrost Type* Defrost Termination Sensors AP0 (Default) No preset application - full menu 2 AP1 Refrigeration Natural Time 1 AP2 Refrigeration Electric Time 1 AP3 Freezing Electric Time 1 AP4 Refrigeration Electric Temp. 2 AP5 Freezing Electric Temp. 2 AP6 No preset application - simplified menu 2 * Hot gas defrost is an option available in full menu (d01). Default Temp. [°F] [r00] Temp. Range min./max. Default Dif. [°F] [°F] [r01] [r02/r03] 36 -31 / 22 4 39 36 / 43 4 36 32 / 39 4 -11 -15 / -4 4 36 32 / 39 4 -11 -15 / -4 4 36 -31 122 4 Defrost Interval [hrs] [d03] 6 4 6 6 6 6 6 Max. Defrost Time [mins] [d04] Defrost Termination Temp. [°F] [d02] 30 43 30 15 15 30 43 30 43 30 43 Key Functions and Display Icons Key Functions Press and hold at power up: FACTORY RESET ("FAC" is displayed) Press for one second: UP Press and hold: ON/OFF Press for one second: DOWN Press and hold: DEFROST Press for one second: BACK Press and hold: PULL-DOWN Display Icons Night mode (Energy saving) Press for one second: TEMP. SETPOINT/OK SET Press and hold: MENU Fan running Compressor running (Flashes in pull-down mode) Active alarm Defrost °C Unit (°C or °F) Connection Diagram DO1 12 DO2 DO3 3L 4N 5 6 7 Programming key EKA 183B (080G9741) GND TX RX +5V 15 16 17 18 GND GND 8 9 10 11 12 13 14 ~ ~ ~~ Power supply (according to the product code number) Sair S5 Sc/DI1 DI2 Sair Control sensor S5 Defrost (evaporator) sensor SC Condenser sensor DI1 Digital input configurable to the functions listed under menu code o02 DI2 Digital input configurable to the functions listed under menu code o37 © Danfoss | DCS (ADAP-KOOL®) | 2018-11 DKRCE.PD.RL0.A3.02 | 1 Quick Start Guide, ERC 213 Sensor Resistance: Using an ohmmeter, you can measure resistance of a sensor to identify sensor type or to troubleshoot a potentially faulty sensor. Sensor Type Code Resistance [ohm] at Temperature [°F] 0 20 32 75 PTC PTC 1000 NTC 10000 * NTC 5000 * Included in kit Ptc 690 761 807 980 Pt1 931 974 1000 1093 n10 70317 40411 29481 10459 n5 42664 23110 16325 5251 Common Functions Adjust Temperature Set Point From main screen, quickly press "set" (one second). The current temperature setting will appear on screen. Cycle to intended temperature by pressing "^" or "^" and press "set" to save. The display will return to the main screen. Adjust Differential From main screen, press "set" for more than three seconds. Cycle to "r--" submenu by pressing " " or " " and press "set." Cycle to "r01" and press "set." Cycle to preferred differential setting, and press "set" to save. "r01" will appear on screen. Press "<" twice to return to main screen. Manual Defrost From main screen, press defrost for more than three seconds to initiate defrost. The DEFROST icon is shown during defrost. Press defrost key for at least three seconds to stop manual defrost. Factory Reset Press and hold " " and " " simultaneously at power up. Unlock Keypad After 5 minutes of no activity, the keypad will lock if P76 = yes (by default it is set to no). When the keypad is locked any key press shows "LoC" in the display. Press " " and " " simultaneously for three seconds to unlock the keyboard. "unl" is displayed for three seconds. Technical Specifications Power Supply Inputs 080G3411 115V AC 50/60 HZ; 080G3412 230V AC 50/60 Hz 4 total; 2 analog, 1 analog/digital, 1 digital Sensor Included in Kit NTC 10000 Output D01 Compressor Relay 115 V (080G3268): 16 FLA/72 LRA 230 V (080G3269): 10 FLA/60 LRA D02 Defrost Relay and/D03 Fan Relay 8A, 2 FLA, 12 LRA Operating Conditions 14 131 °F Storage Conditions -40 158 °F Approvals UL Recognized/NSF Typical Wiring Configurations ERC 213 - APP 1 DI1 DI2 Sair (Control Sensor) ERC 213 - APP 2-3 DI1 DI2 Sair (Control Sensor) ERC 213 - APP 4-5 Sair S5 (Control DI1 DI2 (Defrost) Sensor) 115 V AC 230 V AC DO1 DO2 DO3 115 V AC 230 V AC DO1 DO2 DO3 115 V AC 230 V AC DO1 DO2 DO3 Troubleshooting Power Supply Code A01 A02 Common Alarm/ Error Codes E27 E29 Description High temperature alarm Low temperature alarm Defrost sensor error Air temperature sensor error Remedy (applicable parameter code in parenthesis) Bring down temperature or increase high limit alarm limit (A13) Increase temperature or low temperature alarm limit (A14) Verify that defrost sensor is wired into terminals 10 and 11 Verify that correct sensor type is selected (o06) Verify that control sensor is wired into terminals 9 and 10 8 is not used Verify that correct sensor type is selected Problem Likely Cause Remedy (applicable parameter number in parenthesis) Common Problems / Resolution Compressor does not start Waiting for compressor delay timer Defrost in progress Check compressor minimum off time (CO2) Check defrost interval (d03) Check defrost on demand (temp. initiated defrost) (d19) Defrost does not start Controller in pull down mode Check pull-down duration (r96) Wrong temperature Wrong type of sensor selected Verify that correct sensor type is selected (o06) is displayed Sensor installed into incorrect terminals Verify that control sensor is wired into terminals 9 and 10 8 is not used Evaporator icing Defrost interval too long Defrost time too short Reduce defrost interval (d03) Increase max. defrost time (d04) Need additional help with programming, parameters, or error codes? Download Danfoss' Koolcode app. 2 | DKRCE.PD.RL0.A3.02 © Danfoss | DCS (ADAP-KOOL®) | 2018-11 Quick Start Guide, ERC 213 Parameter sheet Parameter Name Menu Code Unit Min. Value Max. Value Default Value Value Predefined applications o61 App0 App0 Sensor type o06 n10 n10 Temperature Setpoint r00 °C -100 200 2 2 Differential r01 K 0.1 20 2 2.7 Min. set point limit r02 °C -100 200 -35 -35 Max. set point limit r03 °C -100 200 50 50 Display offset r04 K -10 10 0 0 Display Unit r05 °C °F Calibration of Sair r09 K -20 20 0 0 Night Set back r13 K -50 50 0 0 Offset reference displacement r40 °C -50 20 0 0 Pull down duration r96 min.. 0 960 0 0 Pull down temp limit r97 °C -100 200 0 0 Alarm delay - Normal conditions A03 min. 0 240 30 30 Alarm delay - pulldown / startup / def A12 min. 0 240 60 60 High temp alarm A13 °C -100 200 8 8 Low temp alarm A14 °C -100 200 -30 -30 DI1 delay A27 min. 0 240 30 30 DI2 delay A28 min. 0 240 30 30 Condenser High temp alarm A37 °C 0 200 80 80 Condenser High block limit A54 °C 0 200 85 85 Voltage protection A72 No No Min. cut-in voltage A73 V 0 270 0 0 Min. cut-out voltage A74 V 0 270 0 0 Max. voltage A75 V 0 270 270 270 Defrost Method d01 Electric Electric Defrost stop temperature d02 °C 0 50 6 6.5 Defrost Interval d03 hour 0 240 8 6 Max. defrost Time d04 min. 0 480 30 30 Defrost delay at power up d05 min. 0 240 0 0 Drip delay d06 min. 0 60 0 0 Fan delay after defrost d07 min. 0 60 0 0 Fan start temp after defrost d08 °C -50 0 -5 -5 Fan ON during defrost d09 On On Defrost stop sensor d10 None None Comp accumulated runtime d18 hour 0 96 0 0 Defrost on demand d19 K 0 20 20 20 Defrost delay after pulldown d30 min. 0 960 0 0 Fan at compressor cutout F01 FFC FAo Fan stop evaporator temp F04 °C -50 50 50 50 Fan ON time F07 min. 0 15 2 2 Fan OFF time F08 min. 0 15 2 2 © Danfoss | DCS (ADAP-KOOL®) | 2018-11 DKRCE.PD.RL0.A3.02 | 3 Quick Start Guide, ERC 213 Parameter Name Menu Code Unit Compressor min. ON time C01 min. Compressor min. OFF time C02 min. Comp OFF delay at open door C04 min. Zero crossing C70 Delay of outputs at startup o01 sec DI1 configuration o02 Serial address o03 Password o05 Display Resolution o15 Relay 1 counter o23 Relay 2 counter o24 Relay 3 counter o25 DI2 configuration o37 Display during defrost o91 DO2 Config o71 DI1 polarity P73 DI2 polarity P74 Invert alarm relay P75 Keyboard lock P76 Main switch r12 Controller status u00 Air temperature (Sair) u01 °C Present regulation reference u02 Evaporator temperature (S5) u09 °C DI1 status u10 Night mode u13 DI2 status u37 Condenser temperature (Sc) U09 Compressor relay status u58 Fan relay status u59 Defrost relay status u60 Firmware version u80 Database version Order No Low Air temperature sensor(Sair) error E29 Defrost sensor (S5) error E27 Condensor sensor(Sc) error E30 High temperature alarm A01 Low temperature alarm A02 High voltage alarm A99 Low voltage alarm AA1 High condenser temperature alarm A61 0 Door alarm A04 0 DI external alarm A15 0 Min. Value 0 0 0 0 0 0 Max. Value 30 30 15 600 247 999 Default Value 0 2 0 yes 5 Off 0 0 0.1 Off -ddef no no Normal No Off S25 Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Value 0 2 0 yes 5 Off 0 0 1 0 0 0 Off -ddef no no Normal No On S20 321 0 0 Off Off Off 0 Off On Off 4.16 4.02 3502 On Off Off Off Off Off Off Off Off Off 4 | DKRCE.PD.RL0.A3.02 © Danfoss | DCS (ADAP-KOOL®) | 2018-11