Installation guide
Multi Ejector (Spareparts)
Type CTM 1, CTM 2, CTM 6
CTM 1 Series Multi Ejector and Strainer
Service on strainer
Service on connectors
- Remove connectors with O-rings
- Replace O-rings and place new connectors
- Mount new connectors with screws:
– 6 mm screws torque: 10 Nm ± 1 Nm
– 8 mm screws torque: 27.5 Nm ± 2.5 Nm
Tightening sequence