CP electronics EBDRC-PRM Ceiling Mounted PIR Presence Detectors
EBDRC-PRM
PRM switching, adjustable head, ceiling PIR presence
Warning: This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.
Dimensions (mm)
74mm cut out
Detection pattern
Wiring
Key
- Neutral
- Live
- Switched output
- 10A circuit protection if required
- Load
- Momentary push-to-make switch, 230V (for absence detection)
- Switching channel is L-Out
Installation
This device is designed to be flush ceiling-mounted. See page 12 for additional mounting options.
- Do not site the unit where direct sunlight & artificial light might enter the sensor.
- Do not site the sensor within 1m of any forced air heating or ventilation.
- Do not fix the sensor to an unstable or vibrating surface.
- Occupancy is best detected when the ambient temperature is different to that of the human body, thus, use within -20 to 35ºC ambient temperature.
- Create cut out
Cut a 74mm diameter hole in the ceiling. - Wire stripping
Strip the wires as shown opposite. Presence detector does not require earth conductor. - Wire in plugs & connect to detector
Wire in plug/s, using wiring diagram on page 3 as a guide. Connect the plug/s to the detector. - Clamp cable
Continue tightening the screws until the clamp bar snaps out and is tightly engaged against the cable/s. The cable clamp must clamp the outer sheath only. - Install detector
Bend the springs up and push detector through hole in ceiling. When fully inserted the springs snap back to hold the device in place.
Caution: To avoid injury, take care when bending springs.
Head position & locking
- Remove metal locking clip from rear of unit.
- Set sensor head position to 90º for maximum detection range. Push clip into position shown in the adjacent diagram to lock head. To remove clip, lever out with a small screwdriver.
Caution: Sensor head position < 90deg may result in varying detection range & sensitivity. - Mount the detector centrally above the doorways for optimum detection as shown in the above image.
- Mount the detector as close to the doorway as possible for precise movement detection and high sensitivity.
Default Settings
- Time out: 20 minutes.
- LUX on level: 999
- LUX off level: 999
- Sensitivity on: 9
- Sensitivity off: 9
- Detection: Presence
Adjustments can be made using the optional UHS5 or UNLCDHS handsets.
Testing
Presence Detection
- Power up the sensor. The load should come on immediately.
- Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
- Enter the room or make some movement and check that the load switches on.
Absence Detection
- Power up the sensor. Switch the load on.
- Vacate the room and wait for the load to switch off (this should under than 20 minutes).
- Enter the room, the load will remain off until you switch it on again.
Technical Data
Parts List
CP Electronics
Brent Crescent, London NW10 7XR t.
Phone: +44 (0)333 900 0671
Email: enquiry@cpelectronics.co.uk
Website: www.cpelectronics.co.uk
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
Documents / Resources
![]() |
CP electronics EBDRC-PRM Ceiling Mounted PIR Presence Detectors [pdf] Instruction Manual EBDRC-PRM Ceiling Mounted PIR Presence Detectors, EBDRC-PRM, Ceiling Mounted PIR Presence Detectors, Mounted PIR Presence Detectors, PIR Presence Detectors, Presence Detectors, Detectors |