IA10 Indicator and Alarm Unit
“
Product Specifications
- Model: IA10 Ver. QS0IA101A EN
- Indicators: AL1/ AL2/ AL3/ AL4/ AL5, FZ, HD, MX, MAN, COMM, Key
Lock - Keys: SHIFT Key, UP Key, SCROLL Key, DOWN Key
Product Usage Instructions
1. Overview & Appearance
Front Panel Indicators:
- AL1/ AL2/ AL3/ AL4/ AL5: Alarm 1~5 Indicator
- FZ: Hold PV1, frozen to value 0
- HD: Hold PV1 to the current value
- MX: Hold PV1 to the maximum value
- MAN: Manual Mode Indicator
- COMM: Communication Indicator
- Key Lock Indicator
2. Display and Keys
During power-up, the upper display will show PROG and the lower
display will show the Firmware version for 6 seconds.
Keys:
- SCROLL KEY or ENTER KEY: Select parameter
- UP KEY: Increase parameter value
- DOWN KEY: Decrease parameter value
- SHIFT KEY: Move to digit of parameter to change value
User Menu:
- Press key for 3 seconds to enter User Mode parameter
- Decimal point selection options available
Calibration Menu:
- Press key for 3 seconds to enter Calibration Mode
parameter - Time constant options available for selection
Frequently Asked Questions (FAQ)
Q: How do I switch to Manual Mode?
A: Press the key for 3 seconds and release it to get MANU in the
lower display and then use the key to enter into Manual Mode
parameter.
Q: How do I revert the display to the home screen?
A: Press two keys synchronously to revert the display to the
home screen.
“`
IA10 Indicator and Alarm Unit Quick Start Guide
Model: IA10 Ver. QS0IA101A EN
1. OVERVIEW & APPEARANCE
Front Panel and Function
Indicators:
AL1/ AL2/ AL3/ AL4/ AL5: Alarm 1~5 Indicator
FZ: Hold PV1, frozen to value 0 HD: Hold PV1 to the current value MX: Hold PV1 to the maximum value MAN: Manual Mode Indicator COMM: Communication Indicator Key: Lock Indicator
Process Value/ Unit: Degree: Process Value Unit, °C or °F PV1: Process Value 1, 5-digit PV2: Process Value 2, 5-digit User Access Keys:
SHIFT Key UP Key, Increasing SCROLL Key, Enter DOWN Key, Decreasing
2. DISPLAY AND KEYS
1) PV & SetPoint (PV1/ PV2)
Reg Addr
Code
Parameter
Range
Def- Data ault Type
During power-up, the upper display will show PROG and the lower display will 2) Manual Mode Menu (MANU)
0) No.dP: No decimal point
show the Firmware version for 6 seconds. There are 4 Keys
available in the display board for the user to operate as explained below.
SCROLL KEY or ENTER KEY:
This key is used to select a parameter to
be viewed or adjusted.
UP KEY:
This key is used to increase the value of the selected
parameter.
3) Setup Menu (SET) 4) Calibration Mode Menu (CALI)
3.1 USER MENU
Press the key for 3 seconds and release it to get User in the lower display and then use the key to enter into User Mode parameter.
3
DP1
Decimal point selection 1
1) 1-dP: 1 decimal digit 2) 2-dP: 2 decimal digits 3) 3-dP: 3 decimal digits
4) 4-dP: 4 decimal digits
22/23
IN1LO
Input1 low scale value (H-L)
IN1LO IN1HI (°F) Low: -19999, High: 99999
24/25
IN1HI
Input1 high scale IN1LO IN1HI value (H-L) (°F) Low: -19999, High: 99999
1 R/W
0.0 R/W 200.0 R/W
DOWN KEY:
This key is used to decrease the value of the selected
parameter. SHIFT KEY:
This key is used to move to the digit of the selected
parameter and change the value by using up or down key to increase or
3.2 MANUAL MODE MENU (MANU)
Press the key for 3 seconds and release it to get MANU in the lower display and then use the key to enter into Manual Mode parameter.
0) No.dP: No decimal point
44
DP2
Decimal point selection 2
1) 1-dP: 1 decimal digit 2) 2-dP: 2 decimal digits 3) 3-dP: 3 decimal digits
4) 4-dP: 4 decimal digits
1 R/W
decrease the value. RESET KEY: +
Two keys pressed synchronously are used to revert
the display to the home screen, the process values screen
3 MENU FLOW CHART
3.3 Setup Menu (SET)
Press the key for 3 seconds and release it to get SET menu in the lower display and then use the key to get SET (Base/ ALM/ RETR/ COMM/ EI) parameters in the second lower display. Use the key to enter into Base/ ALM/
106/ 107
IN2LO
Input2 low scale value (H-L)
IN2LO IN2HI (°F) Low: -19999, High: 99999
108/ 109
IN2HI
Input2 high scale value (H-L)
IN2LO IN2HI (°F) Low: -19999, High: 99999
0) NONE: no calculation
1) Addi: PV1 + PV2
0.0 R/W 200.0 R/W
The Menu has been divided into 5 groups. They are as follows:
RETR/ COMM/ EI parameters. Press the keys + to go back to the home.
synchronously anytime
45 MATH Value calculation 2) Subt: PV1 – PV2 3) Mult: PV1 x PV2 4) Divi: PV1 ÷ PV2
0 R/W
3.4 CALIBRATION MENU (CALI)
0) 0: 0 second time constant
Press the key for 3 seconds and release it to get CALI in the lower display
1) 0.2: 0.2 second time constant 2) 0.5: 0.5 second time constant
and then use the key to enter into Calibration Mode parameter. Note: The flow chart shows a complete list of all parameters. For actual application, the
6
FILT
Filter damping time constant of
PV
3) 1: 1 second time constant 4) 2: 2 second time constant 5) 5: 5 second time constant 6) 10: 10 second time constant
2 R/W
number of available parameters will vary depending on the setup and will be less
7) 20: 20 second time constant
than that shown in the flow chart.
8) 30: 30 second time constant 9) 60: 60 second time constant
4. PARAMETERS DESCRIPTION
7
LCUT
Input low-cut OFF(-1) or value (°F) 0~36000
-1 R/W
Reg Addr
Code
Parameter
Range
Def- Data Scale Scale ault Type Low High
46 SQRT
Square root function
0) oFF: Square root disable 1) oN: Square root enable
0 R/W
User Manual, ALSP
81 PASS
Parameter Password
Low: 0, High: 9999
0 R/W
0
65535
47
DSP1
Upper display
0) INPT1: Display input1 (PV1) 1) MATH: Display math calculation
0) NoNE: No display
0
R/W
26/27 A1SP Alarm 1 Setpoint (°F)Low: -19999, High: 99999
0.0 R/W -19999 99999
1) INPT2: Display input2 (PV2)
28/29 A2SP Alarm 2 Setpoint (°F)Low: -19999, High: 99999
0.0 R/W -19999 99999 48 DSP2 Lower display 2) MATH: Display value calculation 4 R/W
30/31 A3SP Alarm 3 Setpoint (°F)Low: -19999, High: 99999
0.0 R/W -19999 99999
3) IN1P: Display input1 percentage
32/33 A4SP Alarm 4 Setpoint (°F)Low: -19999, High: 99999
0.0 R/W -19999 99999
4) A1SP: Display alarm1 setpoint
104/ 105
A5SP
Alarm 5 Setpoint (H-L)
(°F)Low: -19999, High: 99999
Manual Mode
55
AOSW
Retransmission output control
0) OFF: RE1, RE2 output 1) ON: AO1, AO2 output 2) EIx: EIx control
56
AO1
Retransmission output1 %
Low: 0.00 High: 100.00
57
AO2
Retransmission output2 %
Low: 0.00 High: 100.00
139
AO3
Retransmission output3 %
Low: 0.00 High: 100.00
167
FILE
Restore to the factory default
0) Default
Setup Menu/ BASE
103
LOCK
Parameters lock
0) oFF: Lock off 1) oN: Lock all parameters on
0) J_tC: J typeThermocouple
1) K_tC: K typeThermocouple
2) T_tC: T type Thermocouple
3) E_tC: E type Thermocouple
4) B_tC: B type Thermocouple
5) R_tC: R type Thermocouple
6) S_tC: S type Thermocouple
7) N_tC: N type Thermocouple
8) L_tC: L type Thermocouple
9) U_tC: U type Thermocouple
42
INPT1
Input sensor selection 1
10) P_tC: P type Thermocouple 11) C_tC: C type Thermocouple
Input1 offset 0.0 R/W -19999 99999 84 OFTL1 value for low Low: -1999 High: 1999
point calibration
1 R/W
0
65535
110/ 111
CALO 1
Input1 signal value during low point calibration
Low: -19999 High: CAHi1-1
0.0 R/W 0.0 R/W 0.0 R/W
0
65535
85
OFTH 1
Input1 offset value for high point calibration
Low: -1999
High: 1999
0 0
65535 65535
112 /113
CAHI1
Input1 signal value during high point calibration
Low: CALO1+1 High: 99999
0 R
Input2 offset 0 65535 86 OFTL2 value for low Low: -1999 High: 1999
point calibration
0 R/W
0
65535
114/ 115
CALO 2
Input2 signal value during low point calibration
Low: -19999 High: CAHi2-1
87
OFTH 2
Input2 offset value for high point calibration
Low: -1999
High: 1999
116/ 117
CAHI2
Input2 signal value during high point calibration
Low: CALO2+1 High: 99999
19
CODE
Security code for parameter protection
Low: 0 High: 9999
15 R/W
0
65535
94
OFS1
Optional function 1 selection
0) NoNE: No selected 1) R485: RS-485
0.0 R/W 0.0 R/W 0.0 R/W 100.0 R/W 0.0 R/W 0.0 R/W 0.0 R/W 100.0 R/W 0 R/W 0 R/W
12) D_tC: D type Thermocouple
0) NoNE: No selected
13) Pt.dN: PT100 DIN curve 14) Pt.JS: PT 100 JIS curve 15) 4-20: 4-20 mA linear current 16) 0-20:0-20 mA linear current
95
OFS2
Optional function 2 selection
1) RE2: Retransmission2 output 2) ALM5: Alarm5 3) ALM5.RE2:
Alarm5, Retransmission2
0 R/W
17) 0-5V: 0-5V linear voltage
SET/ ALM
18) 1-5V: 1-5V linear voltage
0) NONE: No alarm function
19) 0-10: 0-10V linear voltage
1) PV1Hi: PV1 high alarm
20) 0-1V: 0-1V linear voltage
2) PV1Lo: PV1 low alarm
21) 0-50: 0-50mV linear voltage
0) 4-20: 4-20 mA linear current 1) 0-20:0-20 mA linear current
96
A1FN
Alarm 1 function for alarm output
3) PV1LH: PV1 high latching alarm 4) PV1LL: PV1 low latching alarm 5) PV2Hi: PV2 high alarm
0
R/W
43
INPT2
Input sensor selection 2
2) 0-5V: 0-5V linear voltage 3) 1-5V: 1-5V linear voltage
0 R/W 0 65535
6) PV2Lo: PV2 low alarm 7) PV2LH: PV2 high latching alarm
4) 0-10: 0-10V linear voltage
8) PV2LL: PV2 low latching alarm
5) 2-10: 2-10mV linear voltage
2
UNIT1
Input 1 unit selection
0) oC: °C unit 1) oF: °F unit 2) Pu: Process value unit
0 R/W
15
A1HY
Hysteresis control of alarm 1
(°F) Low: 0.1, High: 90.0 (°C) Low: 0.1, High: 90.0
0 65535
9
A1DL
Alarm 1 delay time
Low: 0, High: 999 sec
0.1 R/W 0 R/W
97
A2FN
Alarm 2 function for alarm output
0)~8) Same as A2FN
0 R/W
Scale Scale Low High
0 65535 -19999 99999 -19999 99999
0 65535 -19999 99999 -19999 99999
0 65535
0 65535
-1 45536 0 65535 0 65535 0 65535 -19999 45536 -19999 99999 -19999 45536 -19999 99999 -19999 45536 -19999 99999 -19999 45536 -19999 99999 0 65535 0 65535 0 65535
0 65535
0 65535 0 65535 0 65535
Reg Addr
Code
Parameter
Range
16
A2HY
Hysteresis control of alarm 2
(°F) Low: 0.1, High: 90.0 (°C) Low: 0.1, High: 90.0
10
A2DL
Alarm 2 delay time
Low: 0, High: 999 sec
98
A3FN
Alarm 3 function for alarm output
0)~8) Same as A1FN 9) DCPS: 20 VDC Output Supply 10) RE3: Retransmission3
17
A3HY
Hysteresis control of alarm 3
(°F) Low: 0.1, High: 90.0 (°C) Low: 0.1, High: 90.0
11
A3DL
Alarm 3 delay time
Low: 0, High: 999 sec
99
A4FN
Alarm 4 function for alarm output
0)~8) Same as A1FN 9) DCPS: 20 VDC Output Supply 10) RE1: Retransmission1
18
A4HY
Hysteresis control of alarm 4
(°F) Low: 0.1, High: 90.0 (°C) Low: 0.1, High: 90.0
12
A4DL
Alarm 4 delay time
Low: 0, High: 999 sec
100
A5FN
Alarm 5 function for alarm output
0)~8) Same as A1FN
101
A5HY
Hysteresis control of alarm 5
(°F) Low: 0.1, High: 90.0 (°C) Low: 0.1, High: 90.0
102
A5DL
Alarm 5 delay time
Low: 0, High: 999 sec
Delay rang of
13 SB alarm detection Low: 0, High: 9999
activation (High)
Delay time of
14 SDT alarm detection Low: 0, High: 999 sec
activation
SET/ RETR
88
RE1
Retransmission 1 selection
0) INPUT1: Input1 (PV1) 1) INPUT2: Input2 (PV2) 2) Math: Math result
0) 4-20: 4-20 mA
1) 0-20: 0-20 mA
89
RES1
Retransmission 1 type
2) 0-5V: 0-5V 3) 1-5V: 1-5V
4) 0-10V: 0-10V
5) 2-10: 2-10V
34/35
ANL1
Output 1 retransmission low value (H-L)
ANL1ANH1 Low: -19999, High: 99999
36/37
ANH1
Output 1 retransmission high value (H-L)
ANL1ANH1 Low: -19999, High: 99999
20
OTZ1
Output 1 zero adjustment
Low: -1.000 High 1.000
21
OTS1
Output 1 span Low: -1.000 adjustment High 1.000
90
RE2
Retransmission 2 selection
0) INPUT1: Input1 (PV1) 1) INPUT2: Input2 (PV2) 2) Math: Math result
0) 4-20: 4-20 mA
1) 0-20: 0-20 mA
91
RES2
Retransmission 2 type
2) 0-5V: 0-5V 3) 1-5V: 1-5V
4) 0-10V: 0-10V
5) 2-10: 2-10V
118/ 119
ANL2
Output 2 retransmission
low value
ANL2ANH2 Low: -19999, High: 99999
120/ 121
ANH2
Output 2 retransmission
high value
ANL2ANH2 Low: -19999, High: 99999
92
OTZ2
Output 2 zero adjustment
Low: -1.000 High 1.000
93
OTS2
Output 2 span Low: -1.000 adjustment High 1.000
141
RE3
Retransmission 3 selection
0) INPUT1: Input1 (PV1) 1) INPUT2: Input2 (PV2) 2) Math: Math result
0) 4-20: 4-20 mA
1) 0-20: 0-20 mA
164
RES3
Retransmission 3 type
2) 0-5V: 0-5V 3) 1-5V: 1-5V
4) 0-10V: 0-10V
5) 2-10: 2-10V
Output 3 low
124/ 125
ANL3
point ANL3ANH3 retransmission Low: -19999, High: 99999
value
126/ 127
ANH3
Output 3 high point temperature
ANL3ANH3 Low: -19999, High: 99999
165
OTZ3
Output 3 zero adjustment (low)
Low: -1.000 High 1.000
166
OTS3
Output 3 span adjustment (high)
Low: -1.000 High 1.000
SET/ COMM
Address
8
ADDR
assignment of digital
Low: 1 High: 247
communication
Def- Data ault Type 0.1 R/W 0 R/W 0 R/W 0.1 R/W 0 R/W 0 R/W 0.1 R/W 0 R/W 0 R/W 0.1 R/W 0 R/W 0 R/W 0 R/W
0 R/W
0 R/W
0.0 R/W 100.0 R/W
0 R/W 0 R/W 0 R/W
0 R/W
0.0 R/W 100.0 R/W
0 R/W 0 R/W 0 R/W
0 R/W
0.0 R/W 100.0 R/W
0 R/W 0 R/W
1 R/W
Scale Scale Low High
Reg Addr
Code
Parameter
Range
Def- Data ault Type
0 65535
0) 2.4: 2.4 Kbits/s 1) 4.8: 4.8 Kbits/s
0 65535
2) 9.6: 9.6 Kbits/s Baud rate of 3) 14.4: 14.4 Kbits/s
4 BAUD digital 4) 19.2: 19.2 Kbits/s
2 R/W
0 65535
communication 5) 28.8: 28.8 Kbits/s 6) 38.4: 38.4 Kbits/s
7) 57.6: 57.6 Kbits/s
0 65535
8) 115.2: 115.2 Kbits/s
0
65535
82
DATA
Data bit count of digital
communication
0) 7bIt: 7 data bits 1) 8bIt: 8 data bits
1 R/W
0 65535
5
PARI
Parity bit of digital communication
0) EVEN: Even Parity 1) Odd: Odd parity 2) NoNE: No parity bit
0 R/W
0 0
65535 65535
83
STOP
Stop bit count of digital
communication
0) 1bIt: One stop bit 1) 2bIt: Two stop bits
0 R/W
SET/ EI (Input 1 only)
0 65535
0) NONE: No alarm
1) R.AL1: Reset alarm 1 output
0 65535
2) R.AL2: Reset alarm 2 output 3) R.AL3: Reset alarm 3 output
0 65535
4) R.AL4: Reset alarm 4 output
0
65535
49
E1FN
Event input 1 function
5) R.AL5: Reset alarm 5 output 6) R.ALL: Reset all alarm outputs 7) FR.ZO: Force PV1 to 0
0 R/W
8) DA.HO: Current PV1 value
holding
0 65535
9) MX.HO: PV1 max value holding
10) MANU: Switch all to A0 manual
control / retransmission outputs
0
65535
50
E2FN
Event input 2 function
Same as E1FN
0 R/W
51
E3FN
Event input 3 function
Same as E1FN
0 R/W
0
65535
52
E4FN
Event input 4 function
Same as E1FN
53
E5FN
Event input 5 function
Same as E1FN
0 R/W 0 R/W
54
E6FN
Event input 6 function
Same as E1FN
0 R/W
-19999 99999 Calibration Mode
-19999 99999
58
ADLO
ADC calibration low coefficient
Low: -1999 High: 1999
59
ADHI
ADC calibration Low: -1999 high coefficient High: 1999
—— R/W —— R/W
-19999 45536
60
RTDL
RTD calibration Low: -1999 low coefficient High: 1999
—— R/W
-19999 45536
61
RTDH
RTD calibration high coefficient
Low: -1999 High: 1999
—— R/W
0
65535
62
CJLO
Cold junction calibration low
coefficient
Low: -5.00 High: 40.00
—— R/W
0
65535
63
CJHI
Cold junction calibration high
coefficient
Low: -1999 High: 1999
64
MA1L
MA1 calibration Low: -1999 low coefficient High: 1999
—— R/W —— R/W
-19999 99999
65
MA1G
MA1 calibration high coefficient
Low: -1999 High: 1999
66
V1L
V1 calibration low Low: -1999 coefficient High: 1999
—— R/W —— R/W
-19999 99999
67
V1G
V1 calibration Low: -1999 high coefficient High: 1999
—— R/W
-19999 45536
68
MA2L
MA2 calibration Low: -1999 low coefficient High: 1999
—— R/W
-19999 45536
69
MA2G
MA2 calibration high coefficient
Low: -1999 High: 1999
—— R/W
0
65535
70
V2L
V2 calibration low Low: -1999 coefficient High: 1999
71
V2G
V2 calibration Low: -1999 high coefficient High: 1999
—— R/W —— R/W
Internal Usage
Sense voltage
0
65535
72 CJCL
during cold Low: 0 junction High: 7552
—— R
calibration low
73
CJCT
Cold Junction Low: -4000 Temperature High: 9000
—— R
-19999 99999 38/39 PV1 Process Value 1 Low: -19999, High: 99999
—— R
40/41 PV2 Process Value 2 Low: -19999, High: 99999
—— R
74 DATE
Date Low: 0, High: 65535
—— R
-19999 99999 75 SRNO Serial No Low: 0, High: 65535
—— R
76 EROR Error code Low: 0, High: 65535
—— R
-19999 45536
1
MODE
Operation/ Alarm mode
Low: 0, High: 65535
—— R
-19999 45536 140 PROG Program code 53. XX
—— R
79 CMND Command code Low: 0, High: 65535
—— R/W
80 JOB1 Job code Low: 0, High: 65535
—— R/W
0
65535
81 PASS
Parameter Password
Low: 0, High: 9999
0 R/W
Scale Scale Low High
0 65535
0 65535 0 65535 0 65535
0 65535
0 65535 0 65535 0 65535 0 65535 0 65535 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536 -19999 45536
5. Communication Address Full Table v1.2
Comm. Reg. Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22/23 24/25 26/27 28/29 30/31 32/33 34/35 36/37 38/39 40/41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66
Parameter Notation MODE UNIT1
DP1 BAUD PARI FILT LCUT ADDR A1DL A2DL A3DL A4DL
SB SDT A1HY A2HY A3HY A4HY CODE OTZ1 OTS1 IN1LO IN1HI A1SP A2SP A3SP A4SP ANL1 ANH1 PV1 PV2 INPT1 INPT2 DP2 MATH SQRT DSP1 DSP2 E1FN E2FN E3FN E4FN E5FN E6FN AOSW AO1 AO2 ADLO ADHI RTDL RTDH CJLO CJHI MAIL MAIG VIL
Type
Internal Input/ Base Input/ Base Communication Communication
Base Base Communication Alarm Alarm Alarm Alarm Alarm Alarm Alarm Alarm Alarm Alarm Base Retransmission Retransmission Input/ Base Input/ Base Alarm Alarm Alarm Alarm Retransmission Retransmission Internal Internal Input/ Base Input/ Base Input/ Base Base Base Input Input Event Event Event Event Event Event Manual Manual Manual Calibration Calibration Calibration Calibration Calibration Calibration Calibration Calibration Calibration
Comm. Address
67 68 69 70 71 72 73 74 75 76 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104/105 106/107 108/109 110/111 112/113 114/115 116/117 118/119 120/121 122 123 124/125 126/127 139 140 141 164 165 166 167
6. PROGRAMMING
Parameter Notation
VIG MA2L MA2G V2L V2G CJCL CJCT DATE SRNO EROR CMND JOB1 PASS DATA STOP OFTL1 OFTH1 OFTL2 OFTH2 RE1 RES1 RE2 RES2 OTZ2 OTS2 OFS1 OFS2 A1FN A2FN A3FN A4FN A5FN A5HY A5DL LOCK A5SP IN2LO IN2HI CALO1 CAHI1 CALO2 CAHI2 ANL2 ANH2 MAT_HD MAT_DL ANL3 ANH3 AO3 PROG RE3 RES3 OTZ3 OTS3 FILE
Type
Calibration Calibration Calibration Calibration Calibration
Internal Internal Internal Internal Internal Internal Internal Internal Communication Communication Input/ Base Input/ Base Input/ Base Input/ Base Retransmission Retransmission Retransmission Retransmission Retransmission Retransmission Base Base Alarm Alarm Alarm Alarm Alarm Alarm Alarm Base Alarm Input/ Base Input/ Base Input/ Base Input/ Base Input/ Base Input/ Base Retransmission Retransmission Base Base Retransmission Retransmission Alarm Internal Retransmission Retransmission Retransmission Retransmission File/ Manual
Signal Input INPT: Select the sensor type or signal type for signal input Range: (Thermocouple) J_tC, K_tC, T_tC, E_tC, B_tC, R_tC, S_tC, N_tC, L_tC, U_tC, P_tC, C_tC, d_tC(RTD) PT.DN, PT.JS, (Linear) 4-20, 0-20, 0-5V, 1-5V, 0-10V, 0-1V, 0-50mV
Retransmission The signal conditioner will output (retransmit) PV on its output terminals of output1, output2 and output3. ANL1 and ANH1 are adjusted to specify the low scale and high scale values of output1 retransmission. Similarly, ANL2, ANL3, ANH2 and ANH3 parameters are adjusted for output2 and output3.
Square Root function (SQRT) The square root function (SQRT) function will output the square root value of the PV. The square root function will be enabled by setting the parameter SQRT.
Manual Control
Some application requires to test with the manual output from the signal conditioner. Use key
to access the MANU mode, to navigate to the manual mode control parameter AOSW. Set AOSW
to ON to start the manual mode output. Use the key to select the desired output parameters
AO1, AO2 and AO3. Use the key to move to the digital position. Use the
keys to
set the required output values. Set AOSW to OFF to stop the manual output.
7. ERROR CODE
Error Display Code Symbol
Description & Reason
Corrective Action
10
ER10
Communication error: bad function code
Correct the communication software to meet the protocol requirements.
11
ER11
Communication error: register address out of range
Do not issue an over-range address of the register to the slave
14
ER14
Communication error: attempt to write a read-only data
Do not write read-only data or protected data to the slave.
15
Communication error: write a ER15 value which is out of range to a
register
Do not write an over-range data to the slave register
29
EEPR
EEPROM can’t be written correctly
Return to factory for repair.
30
CJER
Cold junction compensation for Thermocouple malfunction
Return to factory for repair.
Input sensor break, or input
39
SBER
current below 1 mA if 4-20 mA is used, or input voltage below
Replace the input sensor.
0.25V if 1 – 5V is used
40
ADER
A to D converter or related component(s) malfunction
Return to factory for repair.
8. WIRING DIAGRAM
Terminal Connection
0
-19999 -19999 -19999
0 0 0
65535
45536 99999 99999 65535 65535 65535
Zero and Span adjustment The signal conditioner has the option to adjust the zero and span of the outputs to meet the required accuracy. The user can adjust the parameters otZ1, otZ2 and otZ3 to adjust the zero value of the output1, output2 and output3 respectively. The user can adjust the parameters otS1, otS2 and otS3 to adjust the span value of the output1, output2 and output3 respectively. The allowable range for zero and span adjustment is from -1.000 to 1.000.
0 65535
0 65535 0 65535 0 65535
For assistance contact Tech Support: service@brainchild.com.tw; 886-2-2786-1299; http:// www.brainchildtw.com **This specification is subject to possible change without prior notice. Copyright © 2025, All Right Reserved
0 65535
V1.2 QS0IA101A
Documents / Resources
![]() |
Brainchild IA10 Indicator and Alarm Unit [pdf] User Guide QS0IA101A, EN, IA10 Indicator and Alarm Unit, IA10, Indicator and Alarm Unit, Alarm Unit, Unit |