BITMAIN ANTRACK V1 Hydro Cooling Mining Rack 24kW

BITMAIN-ANTRACK-V1-Hydro-Cooling-Mining-Rack-24kW-PRODUCVT

Product Usage Instructions

Installation

Follow these steps to install the ANTRACK unit:

  1. Ensure the input voltage is within the specified range to prevent server damage.
  2. Connect the three-phase AC input to the designated port.
  3. Set up the fluid system ensuring the water conductivity meets the requirements.

Operation
To operate the ANTRACK unit:

  1. Power on the unit and monitor the temperature and humidity levels.
  2. Maintain the antifreeze concentration at 10% to prevent freezing issues.
  3. Check the system regularly and replace fluids if necessary.

Maintenance
Regular maintenance is essential for optimal performance:

  1. Clean the filters and vents to ensure proper airflow.
  2. Inspect and replace any damaged components promptly.
  3. Keep the unit free from dust and debris to prevent overheating.

Specification

Product Glance Value
Model ANTRACK
Version V1
Capacity 4 units ANTMINER (Hydro)
Maximum load, kW 24
Detailed Characteristics Value
Hardware configuration
Size (Length*Width*Height), mm (without package) 1000*600*2100
Size (Length*Width*Height), mm (with package) 2260*1130*780
Net weight, kg (without package) 195
Gross weight, kg (with package) 290
Network connection mode RJ45 Ethernet 10/100M
Power supply
Power supply AC input voltage, Volt(1-1) 380~415V AC
Power supply AC input frequency range, Hz 50~60
Maximum power supply AC input current, Amp(1-2) 80
Fan
Rated power, W 120
Noise, dBA@1m 68
Size (Length*Height*Thickness), mm 280*280*80
Pump
Rated power, W 450
Noise, dBA@1m 55
Size (Length*Width* Height), mm 360*210*268
Plate heat exchanger
Maximum heat exchange power, kW 30
Size (Length*Width* Height), mm 305*106*64
Diameter of water pipe connector, mm DN25
Environment requirements
Ambient temperature, °C 15~45
Water flow, L/min 32.0~40.0
Water pressure, bar ≤3.5
Working fluid(1-3) Antifreeze (10%)
Liquid PH 7.8~8.5
Storage temperature, °C -20~70
Operation humidity(non-condensing), RH 10~90%

Notes

  1. Caution: Wrong input voltage may cause server damaged.
  2. Three-phase AC input.
    If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.

BITMAIN TECHNOLOGIES INC.
www.bitmain.com

FAQ

  • Q: What should I do if the water conductivity is above 100 s/cm?
    A: If the water conductivity exceeds 100 s/cm, the fluid must be replaced immediately to prevent damage to the system.
  • Q: Can I use a different input voltage than specified?
    A: Using the wrong input voltage may cause server damage, so it is crucial to adhere to the specified voltage range.