BITMAIN-logo

BITMAIN ANTRACK Hydro Cooling Mining

BITMAIN-ANTRACK-Hydro-Cooling-Mining-productSpecifications
Product Glance Value
Model ANTRACK
Version V1
Capacity 4 units ANTMINER (Hydro)
Maximum load, kW 24
Detailed Characteristics Value
Hardware configuration
Size (Length*Width*Height), mm (without package) 1000*600*2100
Size (Length*Width*Height), mm (with package) 2260*1130*780
Net weight, kg (without package) 207
Gross weight, kg (with package) 300
Network connection mode RJ45 Ethernet 10/100M
Power supply
Power supply AC input voltage, Volt(1-1) 380~415V AC
Power supply AC input frequency range, Hz 50~60
Maximum power supply AC input current, Amp(1-2) 80
Fan
Rated power, W 120
Noise, dBA@1m 68
Size (Length*Height*Thickness), mm 280*280*80
Pump
Rated power, W 450
Noise, dBA@1m 55
Size (Length*Width* Height), mm 360*210*268
Plate heat exchanger
Maximum heat exchange power, kW 30
Size (Length*Width* Height), mm 305*106*64
Diameter of water pipe connector, mm DN25
Environment requirements
Ambient temperature, °C 15~45
Water flow, L/min 32.0~40.0
Water pressure, bar ≤3.5
Working fluid(1-3) Antifreeze (10%)
Liquid PH 7.8~8.5
Storage temperature, °C -20~70
Operation humidity(non-condensing), RH 10~90%

Product Usage Instructions

  1. Caution: Ensure correct input voltage to prevent server damage.
  2. Fluid Maintenance: If water conductivity reaches 100 s/cm, replace the fluid. Initial conductivity should be less than 20 s/cm.
Notes
  1. Caution: Wrong input voltage may cause server damaged.
  2. Three-phase AC input.
  3. If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.

Frequently Asked Questions

  • Q: What should I do if the server is not powering on?
    • A: Check the input voltage and ensure it is within the specified range to avoid damage.
  • Q: How often should the fluid be replaced?
    • A: Replace the fluid if the water conductivity reaches 100 s/cm. Initially, ensure the conductivity is less than 20 s/cm.

Documents / Resources

BITMAIN ANTRACK Hydro Cooling Mining [pdf] User Guide
ANTRACK V1, ANTRACK Hydro Cooling Mining, ANTRACK, Hydro Cooling Mining, Cooling Mining, Mining

References

Leave a comment

Your email address will not be published. Required fields are marked *