ANTSPACE ANTRACK Liquid Cooling Container Instruction Manual
ANTSPACE ANTRACK Liquid Cooling Container

Specification

Product Glance Value
Model ANTRACK
Version V1
Capacity 4 units ANTMINER (Hydro)
Maximum load, kW 24
Detailed Characteristics Value
Hardware configuration
Size (Length*Width*Height), mm (without package) 1000*600*2000
Size (Length*Width*Height), mm (with package) 2380*1170*805
Net weight, kg (without package) 205
Gross weight, kg (with package) 310
Network connection mode RJ45 Ethernet 10/100M
Power supply
Power supply AC input voltage, Volt(1-1) 380~415V AC
Power supply AC input frequency range, Hz 50~60
Maximum power supply AC input current, Amp(1-2) 80
Fan
Rated power, W 120
Noise, dBA@1m 68
Size (Length*Height*Thickness), mm 280*280*80
Pump
Rated power, W 450
Noise, dBA@1m 55
Size (Length*Width* Height), mm 360*210*268
Plate heat exchanger
Maximum heat exchange power, kW 30
Size (Length*Width* Height), mm 305*106*64
Diameter of water pipe connector, mm DN25
Environment requirements
Ambient temperature, °C 15~45
Water flow, L/min 32.0~40.0
Water pressure, bar ≤3.5
Working fluid(1-3) Antifreeze (10%)
Liquid PH 7.8~8.5
Storage temperature, °C -20~70
Operation humidity(non-condensing), RH 10~90%

Notes: 

(1-1) Caution: Wrong input voltage may cause server damaged.
(1-2) Three-phase AC input.
(1-3) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time

Version: V1
Jan. 2025
BITMAIN TECHNOLOGIES INC.
www.bitmain.com
ANTSPACE Logo

Documents / Resources

ANTSPACE ANTRACK Liquid Cooling Container [pdf] Instruction Manual
ANTRACK Liquid Cooling Container, ANTRACK, Liquid Cooling Container, Cooling Container

References

Leave a comment

Your email address will not be published. Required fields are marked *