ANTSPACE ANTRACK Liquid Cooling Container Instruction Manual
Specification
Product Glance | Value |
Model | ANTRACK |
Version | V1 |
Capacity | 4 units ANTMINER (Hydro) |
Maximum load, kW | 24 |
Detailed Characteristics | Value |
Hardware configuration | |
Size (Length*Width*Height), mm (without package) | 1000*600*2000 |
Size (Length*Width*Height), mm (with package) | 2380*1170*805 |
Net weight, kg (without package) | 205 |
Gross weight, kg (with package) | 310 |
Network connection mode | RJ45 Ethernet 10/100M |
Power supply | |
Power supply AC input voltage, Volt(1-1) | 380~415V AC |
Power supply AC input frequency range, Hz | 50~60 |
Maximum power supply AC input current, Amp(1-2) | 80 |
Fan | |
Rated power, W | 120 |
Noise, dBA@1m | 68 |
Size (Length*Height*Thickness), mm | 280*280*80 |
Pump | |
Rated power, W | 450 |
Noise, dBA@1m | 55 |
Size (Length*Width* Height), mm | 360*210*268 |
Plate heat exchanger | |
Maximum heat exchange power, kW | 30 |
Size (Length*Width* Height), mm | 305*106*64 |
Diameter of water pipe connector, mm | DN25 |
Environment requirements | |
Ambient temperature, °C | 15~45 |
Water flow, L/min | 32.0~40.0 |
Water pressure, bar | ≤3.5 |
Working fluid(1-3) | Antifreeze (10%) |
Liquid PH | 7.8~8.5 |
Storage temperature, °C | -20~70 |
Operation humidity(non-condensing), RH | 10~90% |
Notes:
(1-1) Caution: Wrong input voltage may cause server damaged.
(1-2) Three-phase AC input.
(1-3) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time
Version: V1
Jan. 2025
BITMAIN TECHNOLOGIES INC.
www.bitmain.com