የዳንፎስ ኦፕቲማ መቆጣጠሪያ ለኮንደንሲንግ ዩኒት የተጠቃሚ መመሪያ

የኦፕቲማ መቆጣጠሪያ ለኮንደንስ ዩኒት

Controller for condensing unit

Optima™ በተጨማሪም

SW ስሪት 3.6x

www.danfoss.com

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

መግቢያ

መተግበሪያ

ኮንዲንግ አሃድ ቁጥጥር

አድቫንtages

• Condensing pressure control in relation to outside temperature • Fan variable speed regulation

• On/off or variable speed regulation of the compressor • Heating element control in crankcase

• Day/night controller operation  

• Built-in clock function with power reserve

• Built-in Modbus data communication

• Monitoring discharge temperature td  

• Oil return management control at variable speed control

መርህ

The controller receives a signal for demanded cooling, and it then  starts the compressor.  

If the compressor is controlled by variable speed, the suction  pressure (converted to temperature) will be controlled according  to a set temperature value.

Condenser pressure regulation is performed again following  a signal from the ambient temperature sensor and the set  reference. The controller will then control the fan, which allows the  condensing temperature to be maintained at the desired value. The controller can also control the heating element in the  crankcase so that oil is kept separate from the refrigerant.  For excess discharge temperature, the liquid injection will be  activated in the suction line (for compressors with the liquid  injection option).

ተግባራት

• Control of condensing temperature

• Control of fan speed

• On/off control or speed regulation of the compressor • Control of heating element in crankcase

• Liquid injection into economizer port (if possible) • Raising the condenser pressure regulation reference during night  operation

• Extern start/stop via DI1

• Safety cut-out activated via signal from automatic safety control

የሙቀት መጠንን ለመጨመር ደንብ ማጣቀሻ The controller controls the condensing Reference, which is in  detail the difference between condensing temperature and  ambient temperature. The reference setpoint can be shown with a  brief push on the middle button and adjusted with the upper and  lower button. The reference can be raised at night to allow slower  fan speeds to reduce fan noise. This is done via the night set back  feature.

This setting can be changed without entering the  programming mode so care needs to be taken to not adjust  unintentionally.

ቀን/ሌሊት

The controller has an internal clock function which changes  between daytime and night operation.

During night operation, the reference is raised by the ‘Night offset’  value.

This day/night signal can also be activated in two other ways: • Via an on/off input signal – DI2

• Via data communication.  

አዘጋጅ ነጥብ

ማጣቀሻ የምሽት ማካካሻ

ታምብ

Day Night Day

2 | BC172686425380en-000901 © Danfoss | DCS (vt) | 2020.11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

የደጋፊዎች አሠራር

The controller will control the fan so that the condensing  temperature is maintained at the desired value above the outdoor  temperature.

ተጠቃሚው አድናቂውን ለመቆጣጠር ከተለያዩ መንገዶች ሊመርጥ ይችላል፡-

• Internal speed regulation

እዚህ ማራገቢያው በተርሚናል 5-6 በኩል ፍጥነትን ይቆጣጠራል።

At a need of 95% and above, the relay on terminal 15-16 are  activated, while 5-6 are deactivated.

• External speed regulation

For larger fan motors with insufficient internal outlet, an external  speed regulation can be connected to terminal 54-55. A 0 – 10 V  signal indicating the desired speed is then sent from this point.  The relay on terminal 15-16 will be active when the fan is in  operation.  

በምናሌ 'F17' ተጠቃሚው ከሁለቱ መቆጣጠሪያዎች የትኛውን መጠቀም እንዳለበት መወሰን ይችላል።

በጅማሬ ላይ የደጋፊዎች ፍጥነት

When the fan is re-started after an idle period, it will be started  at a speed that is set in the ‘Jog Speed’ function. This speed is  maintained for 10 seconds, after which the speed changes to the  regulation need.  

ዝቅተኛ ጭነቶች ላይ የደጋፊ ፍጥነት

At low loads between 10 and 30%, the speed will remain at that  which is set in the ‘FanMinSpeed’ function.

በዝቅተኛ የአካባቢ ሙቀት የደጋፊ ፍጥነት

To avoid frequent start/stops in low ambient temperatures in  which the fan’s capacity is high, the internal amplification factor is  lowered. This provides a smoother regulation.

The ‘Jog speed’ is also lowered in the area from 10 °C and down to  -20 °C.

ከ -20 ዲግሪ ሴንቲግሬድ በታች ባለው የሙቀት መጠን የጆግ ሎው ዋጋን መጠቀም ይቻላል.

መጭመቂያ ክፍል ቅድመ-አየር ማናፈሻ

The condenser fan starts and operates for a period of time and  speed before the compressor starts. This happens in case of any  mildly flammable refrigerant selected via “o30 Refrigerant”, to  get a safe atmosphere while sucking potential flammable A2L refrigerant gas out of the compressor compartment. There is a fixed delay of about 8 seconds between this pre ventilation and compressor start in order to reduce the airflow  significantly and avoid any condensing problems on low ambient  temperatures.

ፍጥነት

ጆግ

ደቂቃ

ፍጥነት

ጆግ

ጆግ ዝቅተኛ

15 - 16

54 - 55

15 - 16

የሚፈለግ አቅም

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 3

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

የኮምፕረር መቆጣጠሪያ

The compressor is controlled by a signal at the DI1 input.  The compressor will start once the input is connected.  Three restrictions have been implemented to avoid frequent start/ stops:

– One for minimum ON time

– One for minimum OFF time

– One for how much time must elapse between two starts. These three restrictions have the highest priority during  regulation, and the other functions will wait until they are  complete before regulation can continue. When the compressor is  ‘locked’ by a restriction, this can be seen in a status notification. If the DI3 input is used as a safety stop for the compressor, an  insufficient input signal will immediately stop the compressor.  Variable speed compressors can be speed-controlled with a voltage  signal at the AO2 output. If this compressor has been running for a  long period at low speed, the speed is increased for a short moment  for the purpose of oil-return.

ከፍተኛው የፍሳሽ ጋዝ ሙቀት

የሙቀት መጠኑ በሴንሰር ቲዲ ይመዘገባል.

If variable speed control is chosen for the compressor, this control  will initially reduce the compressor capacity if the Td temperature  approaches the set maximum value.  

If a higher temperature is detected than the set max. temperature,  the fan’s speed will be set to 100%. If this does not cause the  temperature to drop, and if the temperature remains high after the  set delay time, the compressor will be stopped. The compressor  will only be re-started once the temperature is 10 K lower than the  set value. The above mentioned re-start restrictions must also be  complete before the compressor can start once again. If the delay time is set to ‘0’, the function will አይደለም stop the  compressor. The Td sensor can be deactivated (o63).

ፈሳሽ መርፌ ወደ ኢኮኖሚዘር ወደብ

The controller can activate the liquid injection into economizer  port if the discharge temperature is approaching the maximum  allowable temperature.  

Note: Liquid injection function use the Aux Relay if the relay is  configured to this function.

ከፍተኛ ግፊት ክትትል

During regulation, the internal high pressure monitoring function  is able to detect an over the limit condensing pressure so that the  regulation can continue.

However, if the c73 setting is exceeded, the compressor will be  stopped and an alarm is triggered.

If, on the other hand, the signal comes from the interrupted safety  circuit connected to DI3, the compressor will immediately be  stopped and the fan will be set to 100%.

When the signal is once again ‘OK’ at the DI3 input, the regulation  will resume.

ዝቅተኛ ግፊት ክትትል

During regulation, the internal low pressure monitoring function  will cut out the compressor upon detecting a suction pressure that  falls below the lower limit, but only once the minimum ON time is  exceeded. An alarm will be issued (A2). This function will be time  delayed, if the compressor starts at low ambient temperature.

የፓምፕ ታች ገደብ

The compressor will be stopped if a suction pressure that falls below  the set value is registered, but only once the minimum ON time is  exceeded.  

DI off:

ማንቂያው አብቅቷል።view Di3 => A97 / DI2=1 => A97

4 | BC172686425380en-000901 © Danfoss | DCS (vt) | 2020.11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

በክራንች መያዣ ውስጥ ያለው ማሞቂያ

The controller has a thermostat function which can control the  heating element for the crankcase. Oil can thus be kept separate  from the refrigerant. The function is active when the compressor  has stopped.

The function is based on the ambient temperature and suction gas  temperature. When the two temperatures are equal ± a temperature  difference, power will be supplied to the heating element. The ‘CCH off diff’ setting indicates when power will no longer be  supplied to the heating element.

The ‘CCH on diff’ indicates when 100% power will be sent to the  heating element.

በሁለቱ ቅንብሮች መካከል ተቆጣጣሪው ዋት ያሰላልtage  and connects to the heating element in a pulse/pause cycle which  corresponds to the desired wattage.

The Taux sensor can be used to record the temperature in the  crankcase if desired.  

When the Taux sensor records a temperature lower than Ts+10 K,  the heating element will be set to 100%, but only if the ambient  temperature is below 0 °C.

የተለየ የሙቀት መቆጣጠሪያ ተግባር

The taux sensor can also be used in a heating function with  programmable temperature. Here, the AUX relay will connect the  heating element.

ዲጂታል ግብዓቶች

There are two digital inputs DI1 and DI2 with contact function and  one digital input DI3 with high voltagሠ ምልክት.  

ለሚከተሉት ተግባራት ሊያገለግሉ ይችላሉ:

100%

0%

CCH on

ልዩነት

DI1 DI2

DI3

N

CCH off

ልዩነት

L

tአምብ - ቲs 

LP

HP

DI1፡ መጭመቂያውን ይጀምራል እና ያቆማል

DI2: Here the user can select from various functions Signal from an external safety function

External main switch / night setback signal / separate alarm  function / Monitoring of input signal / signal from an external  speed control

DI3፡ ከዝቅተኛ/ከፍተኛ ግፊት መቀየሪያ የደህንነት ምልክት

የውሂብ ግንኙነት

N

MODBUS

ሎን

The controller is delivered with built-in MODBUS data  communication.

If a different form of data communication is requested, a LON RS 485 module can be inserted in the controller.  

ግንኙነቱ በተርሚናል RS 485 ላይ ይደረጋል። አስፈላጊ

All connections to the data communication must comply with the  requirements for data communication cables.  

ስነ ጽሑፍ ይመልከቱ፡ RC8AC.  

ማሳያ

The controller has one plug for a display. Here display type EKA  163B or EKA 164B (max. length 15 m) can be connected.  EKA 163B is a display for readings.

EKA 164B ሁለቱም ለንባብ እና ኦፕሬሽን ናቸው.

The connection between display and controller must be with a  cable which has a plug at both ends.

A setting can be made to determine whether the Tc or Ts is to be  read out. When the value is read out, the second read-out can be  

MOD

ከፍተኛ 15 ሜ

RS

ሎን

ከፍተኛ 1000 ሜ 

MOD

Address o03 > 0

displayed by briefly pressing the lower button.  

When a display is to be connected to the built-in MODBUS, the  display can advantageously be changed to one of the same type,  but with Index A (version with screw terminals).

The controllers address must be set higher than 0 in order for the  display to be able to communicate with the controller. If connection of two displays is required, one must be connected  to the plug (max. 15 m) and the other must then be connected to  the fixed data communication.

መሻር

The controller contains a functions which can be used together  with the override function in the master gateway/system manager.  

በመረጃ ግንኙነት በኩል ተግባር

የቀን / የምሽት መርሃ ግብር

በጌትዌይ/ስርዓት አስተዳዳሪ ውስጥ ተግባር

የቀን / የሌሊት መቆጣጠሪያ / የጊዜ መርሐግብር

ውስጥ ያገለገሉ መለኪያዎች Optima™ በተጨማሪም

- የምሽት ውድቀት

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 5

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

ተግባራት ቅኝት

ተግባር

ፓራ

ሜትር

Parameter by operation via data  communication

መደበኛ ማሳያ

The display shows the temperature value for the suction pressure Ts or from the condensing  pressure Tc. Enter which of the two are to be displayed in o17.

During operation, when one of the two is shown in the display, the other value can be seen  by pressing and holding in the lower button.

ቲስ / ቲ.ሲ

ቴርሞስታት

የሙቀት መቆጣጠሪያ

ነጥብ አዘጋጅ

The controller’s reference Tc is the outside temperature + set point + any applicable offset.  Enter the set point by pressing the middle button. A offset can be entered in r13.

ማጣቀሻ

ክፍል

Set here if the display is to show SI-units or US-units

0: SI (°C and bar)

1: US (°F እና Psig)።

r05

ክፍል  

°C=0 /°F=1

(በAKM ላይ °C ብቻ፣ መቼቱ ምንም ይሁን)

የማቀዝቀዣ መጀመር / ማቆም

With this setting refrigeration can be started, stopped or a manual override of the outputs  can be allowed. (For manual control the value is set at -1. Then the relay outlets can be force controlled by the respective reading parameters (u58, u59 etc.). Here the read value can be  overwritten.)

Start / stop of refrigeration can also be accomplished with the external switch function  connected to a DI input.

የውጭ ማብሪያ / ማጥፊያ ተግባር ካልተመረጠ, ግቤቱ አጭር መሆን አለበት. የቆመ ማቀዝቀዣ “የተጠባባቂ ማንቂያ” ይሰጣል።

r12

ዋና ማብሪያ

1፡ ጀምር

0: አቁም

-1: የሚፈቀደው የውጤቶች በእጅ ቁጥጥር

የምሽት ውድቀት ዋጋ

The controller reference is raised by this value when the controller switches to night  operation.

r13

የምሽት ማካካሻ

Reference Ts

እዚህ ማጣቀሻው በዲግሪዎች ውስጥ ለመምጠጥ ግፊት Ts ገብቷል.

r23

Ts Ref

Reference Tc

እዚህ ላይ የአሁኑን ተቆጣጣሪ ማጣቀሻ ለኮንደንሲንግ ግፊት Tc በዲግሪዎች ሊነበብ ይችላል.

r29

Tc ማጣቀሻ

የውጭ ማሞቂያ ተግባር

Thermostat cut-in value for an external heating element (only when 069=2 and o40=1) The relay activates when the temperature reaches the set value. Relay releases again when  the temperature has increased by 5 K (the difference is set at 5 K).

r71

AuxTherRef

ዝቅተኛ የሙቀት መጠን (ዝቅተኛው የሚፈቀደው ደንብ ማጣቀሻ) እዚህ ዝቅተኛው የተፈቀደው ማጣቀሻ ለኮንዲንግ ሙቀት Tc ገብቷል።

r82

MinCondTemp

ከፍተኛው የማጠናከሪያ ሙቀት (ከፍተኛው የተፈቀደው ደንብ ማጣቀሻ) እዚህ ከፍተኛው የተፈቀደው ማጣቀሻ ለኮንደንስ ሙቀት Tc ገብቷል።

r83

MaxCondTemp

ከፍተኛው የፍሳሽ ጋዝ ሙቀት

Here the highest permitted discharge gas temperature is entered. The temperature is  measured by sensor Td. If the temperature is exceeded, the fan will be started at 100%. A  timer is also started which can be set in c72. If the timer setting runs out, the compressor will  be stopped and an alarm will be issued. The compressor will be reconnected 10 K below the  cut-out limit, but only after the compressor’s off timer has expired.

r84

MaxDischTemp

የምሽት ውድቀት

(የሌሊት ምልክት መጀመሪያ 0=ቀን፣ 1=ሌሊት)

ማንቂያ

የማንቂያ ቅንብሮች

The controller can give alarm in different situations. When there is an alarm all the light emitting diodes (LED) will flash on the controller front panel, and the alarm relay will cut in.

With data communication the  

importance of the individual alarms  can be defined. Setting is carried out in  the “Alarm destinations” menu via AKM.

የ DI2 ማንቂያ መዘግየት

A cut-out/cut-in input will result in alarm when the time delay has been passed. The function  is defined in o37.

አ28

AI. መዘግየት DI2

ከፍተኛ የሙቀት መጠን ማንቂያ ገደብ

The limit for the condensing temperature, set as difference above the instant reference  (parameter r29), at which the A80 Alarm is activated after expired delay (see parameter A71).  Parameter is set in Kelvin .

አ70

የአየር ፍሰት ዲፍ

ለማንቂያ A80 የዘገየ ጊዜ - እንዲሁም ግቤት A70ን ይመልከቱ። በደቂቃዎች ውስጥ ያዘጋጁ።

አ71

የአየር ፍሰት del

ማንቂያ ዳግም አስጀምር

Ctrl ስህተት

6 | BC172686425380en-000901 © Danfoss | DCS (vt) | 2020.11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

መጭመቂያ

የኮምፕረር መቆጣጠሪያ

The start/stop of the controller can be defined in several ways.

Internal only: Here, only the internal main switch in r12 is used.

External: Here, input DI1 is used as a thermostat switch. With this setting, input DI2 can be  defined as an ‘external safety’ mechanism that can stop the compressor.

የሩጫ ጊዜያት

To prevent irregular operation, values can be set for the time the compressor is to run once it  has been started. And for how long it at least has to be stopped.

ደቂቃ በሰዓቱ (በሴኮንዶች)

c01

ደቂቃ በጊዜ

ደቂቃ የጠፋ ጊዜ (በሴኮንዶች)

c02

ደቂቃ የእረፍት ጊዜ

በመቁረጥ መካከል ያለው ዝቅተኛ ጊዜ (በደቂቃዎች ውስጥ)

c07

ዳግም አስጀምር ጊዜ

ወደ ታች ፓምፕ ገደብ  

መጭመቂያው የሚቆምበት የግፊት ዋጋ

c33

PumpDownLim

መጭመቂያ ደቂቃ. ፍጥነት

እዚህ ለመጭመቂያው የሚፈቀደው ዝቅተኛ ፍጥነት ተዘጋጅቷል.

c46

CmpMinSpeed

የኮምፕረር ጅምር ፍጥነት

የሚፈለገው ፍጥነት ከመድረሱ በፊት መጭመቂያው አይጀምርም።

c47

CmpStrSpeed

መጭመቂያ ከፍተኛ. ፍጥነት

ለኮምፕረር ፍጥነት ከፍተኛ ገደብ

c48

CmpMaxSpeed

መጭመቂያ ከፍተኛ. በምሽት ቀዶ ጥገና ወቅት ፍጥነት

Upper limit for compressor speed during night operation. During night operation, the c48  value is reduced to the percentage እሴት እዚህ ተዘጋጅቷል

c69

CmpMax % Ngt

የኮምፕረር መቆጣጠሪያ ሁነታ ፍቺ

0: ምንም መጭመቂያ የለም - የማጠናከሪያ ክፍል ጠፍቷል

1: Fixed speed – Input DI1 used to start / stop of fixed speed compressor  2: Variable speed – Input DI1 used for start / stop of variable speed-controlled compressor  with a 0 – 10 V signal on AO2

c71

የኮምፑ ሁነታ

ለከፍተኛ የጋዝ ሙቀት መዘግየት ጊዜ (በደቂቃዎች ውስጥ)

When sensor Td records a temperature higher than the limit value entered in r84, the timer  will start. When the delay time expires, the compressor will be stopped if the temperature is  still too high. An alarm will also be issued.

c72

ዲሽ ዴል

ከፍተኛ. ግፊት (ከፍተኛ የኮንዲንግ ግፊት)

The maximum permitted condensing pressure is set here. If the pressure increases, the  compressor will be stopped.

c73

PCMax

ለከፍተኛው ልዩነት. ግፊት (የማቀዝቀዝ ግፊት)

Difference for re-start of compressor if it is cut out due to PcMax.

(All timers must expire before re-start is permitted)

c74

ፒሲ ልዩነት

ዝቅተኛ የመሳብ ግፊት

Enter the lowest permitted suction pressure here. The compressor is stopped if the pressure  drops below the minimum value.

c75

PsLP

የመምጠጥ ግፊት ልዩነት

Difference for re-start of compressor if it is cut out due to PsLP.

(All timers must expire before re-start is permitted)

c76

PsDiff

Ampየሊፊኬሽን ምክንያት Kp ለ compressor regulation

የKp እሴት ከተቀነሰ ደንቡ ቀርፋፋ ይሆናል።

c82

ሲምፕ ኬ.ፒ

የውህደት ጊዜ Tn ለ compressor regulation

የTn እሴት ከተጨመረ፣ ደንቡ በተቀላጠፈ ሁኔታ ይሰራል

c83

Comp Tn ሰከንድ

ፈሳሽ መርፌ ማካካሻ

The liquid injection relay is activated when the temperature is over “r84” minus “c88” (but  only if the compressor is running).

c88

LI Offset

ፈሳሽ መርፌ hysterese

The liquid injection relay is then deactivated when the temperature has dropped to “r84”  minus “c88” minus “c89”.

c89

LI Hyst

ፈሳሽ መርፌ ከተከተለ በኋላ የኮምፕረር ማቆሚያ መዘግየት

መጭመቂያው በሰዓቱ ከተላለፈ በኋላ “Aux relay” ጠፍቷል

c90

LI መዘግየት

ከግፊት አስተላላፊ ጥፋቶች ጋር በተያያዘ የሚፈለገው የኮምፕረር ፍጥነት። በድንገተኛ ቀዶ ጥገና ወቅት ፍጥነት.

c93

CmpEmrgSpeed

ዝቅተኛ የአካባቢ ሙቀት እና ዝቅተኛ ግፊት ጊዜ ላይ ደቂቃ

c94

c94 LpMinOnTime

የ Comp min ፍጥነት ወደ StartSpeed ​​የሚጨምርበት Tc ይለካል

c95

c95 TcSpeedLim

በመቆጣጠሪያው ፊት ላይ ያለው LED ማቀዝቀዣው በሂደት ላይ መሆኑን ያሳያል.

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 7

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

አድናቂ

የደጋፊዎች ቁጥጥር

Ampየመፍቻ ምክንያት Kp

የ KP ዋጋ ከተቀነሰ የደጋፊው ፍጥነት ይቀየራል።

n04

ኬፒ ፋክተር

የውህደት ጊዜ Tn

የቲኤን እሴት ከተጨመረ የደጋፊው ፍጥነት ይቀየራል።

n05

Tn ሰከንድ

Ampየማጣራት ምክንያት Kp max

ደንቡ ይህንን Kp ይጠቀማል፣ የሚለካው እሴት ከማጣቀሻ በጣም የራቀ ነው።

n95

ሲምፕ ኪፒ ከፍተኛ

የደጋፊዎች ፍጥነት

ትክክለኛው የአየር ማራገቢያ ፍጥነት እንደ % የስም ፍጥነት እዚህ ይነበባል።

F07

የደጋፊ ፍጥነት %

የአየር ማራገቢያ ፍጥነት ለውጥ

A permitted change in fan speed can be entered for when the fan speed is to be lowered.  The setting can be entered as a percentagሠ ዋጋ በሰከንድ.

F14

ዳውንስሎፕ

የጆግ ፍጥነት

Set the fan’s start-up speed here. After ten seconds the function jog function will stop and  the fan speed will then be controlled by the normal regulation.

F15

የጆግ ፍጥነት

በዝቅተኛ የሙቀት መጠን የጆግ ፍጥነት

Enter the desired jog speed for outside temperatures of -20 °C and lower here. (For outside temperatures between +10 and -20, the controller will calculate and utilise a  speed between the two jog settings.)

F16

LowTempJog

Fan control definition

0: ጠፍቷል

1: The fan is connected to terminal 5-6 and is speed-controlled by an internal phase cut. The  relay on terminal 15-16 connects at speed requirements of 95% or higher.  2: The fan is connected to an external speed control device. The speed control signal is  connected to terminals 28-29. The relay on terminal 15-16 will connect when regulation is  required. (During external control, the settings F14, F15 and F16 will remain in force)

F17

FanCtrlMode

ዝቅተኛ የአድናቂዎች ፍጥነት

Set the lowest permitted fan speed here. The fan will be stopped if the user enters a lower  speed.

F18

MinFanSpeed

ከፍተኛ አድናቂ ፍጥነት

The fan’s top speed can be limited here. The value can be entered by setting the nominal  speed of 100% to the desired percentage.

F19

MaxFanSpeed

በእጅ የአየር ማራገቢያ ፍጥነት መቆጣጠሪያ

An override of the fan speed control can be performed here. This function is only relevant  when the main switch is in service mode.

F20

በእጅ ደጋፊ%

የደረጃ ማካካሻ

እሴቱ በደረጃ ቁጥጥር ወቅት የሚወጣውን የኤሌክትሪክ ድምጽ ይቀንሳል. እሴቱ መቀየር ያለበት በልዩ የሰለጠኑ ሰራተኞች ብቻ ነው።

F21

ደጋፊ ኮም

The condenser fan will pre-ventilate the compressor compartment to ensure a safe  environment before compressor start on selected A2L-refrigerants via o30

F23

 FanVent ጊዜ

The LED on the controller’s front will show whether Fan is in progress supplied either  through fan speed control output or fan relay.

እውነተኛ ሰዓት

When using data communication the clock is automatically adjusted by the system unit. If  the controller is without data communication, the clock will have a power reserve of four  hours.

(Times cannot be set via data  

communication. Settings are only  relevant when there is no data  communication).

ወደ ቀን አሠራር ይቀይሩ

የቁጥጥር ማመሳከሪያው የገባው ስብስብ ነጥብ የሚሆንበትን ጊዜ አስገባ.

t17

የቀን ጅምር

ወደ ማታ አሠራር ይቀይሩ

የመቆጣጠሪያው ማመሳከሪያ የሚነሳበትን ጊዜ በ r13 ያስገቡ.

t18

የሌሊት ጅምር

ሰዓት፡ የሰዓት ቅንብር

t07

ሰዓት፡ ደቂቃ ቅንብር

t08

ሰዓት፡ የቀን ቅንብር

t45

ሰዓት፡ ወር ቅንብር

t46

ሰዓት፡ የዓመት ቅንብር

t47

የተለያዩ

የተለያዩ

If the controller is built into a network with data communication, it must have an address, and  the system unit of the data communication must then know this address.

The address is set between 0 and 240, depending on the system unit and the selected data  communication.  

The function is not used when the data communication is MODBUS. It is retrieved here via  the system’s scan function.

o03

o04

8 | BC172686425380en-000901 © Danfoss | DCS (vt) | 2020.11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

የመዳረሻ ኮድ 1 (የሁሉም ቅንብሮች መዳረሻ)

If the settings in the controller are to be protected with an access code you can set a  numerical value between 0 and 100. If not, you can cancel the function with setting 0 (99 will  always give you access).

o05

አሲ.ሲ. ኮድ

የመቆጣጠሪያ ሶፍትዌር ስሪት

o08

SW ver

ለማሳያው ምልክት ይምረጡ  

Here you define the signal to be shown by the display.

1: Suction pressure in degrees, Ts.

2: ግፊትን በዲግሪዎች, ቲ.ሲ.

o17

የማሳያ ሁነታ

የግፊት አስተላላፊ ቅንብሮች ለ መዝ

የስራ ክልል ለግፊት አስተላላፊ - ደቂቃ. ዋጋ

o20

MinTransPs

የግፊት አስተላላፊ ቅንብሮች ለ መዝ

የስራ ክልል ለግፊት አስተላላፊ - ከፍተኛ. ዋጋ

o21

MaxTransPs

የማቀዝቀዣ ቅንብር ("r12" = 0 ከሆነ ብቻ)

Before refrigeration is started, the refrigerant must be defined. You may choose between the  following refrigerants

2=R22. 3=R134a. 13=User defined. 17=R507. 19=R404A. 20=R407C. 21=R407A. 36=R513A.  37=R407F. 40=R448A. 41=R449A. 42=R452A. 39=R1234yf. 51=R454C. 52=R455A Warning: Wrong selection of refrigerant may cause damage to the compressor. Other refrigerants: Here setting 13 is selected and then three factors -Ref.Fac a1, a2 and a3 –  via AKM must be set.

o30

ማቀዝቀዣ

የዲጂታል ግቤት ምልክት - DI2

መቆጣጠሪያው ዲጂታል ግብዓት 2 አለው ይህም ከሚከተሉት ተግባራት ውስጥ ለአንዱ ጥቅም ላይ ሊውል ይችላል፡ 0፡ ግብአቱ ጥቅም ላይ አይውልም።

1: Signal from a safety circuit (short-circuited =ok for compressor operation). Disconnected =  compressor stop and A97 alarm).

2: Main switch. Regulation is carried out when the input is short-circuited, and regulation is  stopped when the input is put in pos. OFF.

3: Night operation. When the input is short-circuited, there will be regulation for night  operation.

4: Separate alarm function. Alarm will be given when the input is short-circuited. 5: Separate alarm function. Alarm will be given when the input is opened. 6: Input status, on or off (DI2 status can be tracked via data communication). 7: Alarm from the compressor’s external speed control.

o37

DI2 ውቅር

Aux ቅብብል ተግባር

0: ማስተላለፊያው ጥቅም ላይ አይውልም

1፡ የውጭ ማሞቂያ ኤለመንት (የሙቀት መጠን በ r71፣ ሴንሰር ፍቺ በ069) 2፡ ለፈሳሽ መርፌ ጥቅም ላይ ይውላል (የሙቀት መጠን በ r84)

3፡ የዘይት መመለሻ አስተዳደር ተግባር ቅብብሎሹን ማግበር አለበት።

o40

AuxRelayCfg

የግፊት አስተላላፊ ቅንብሮች ለፒሲ

የስራ ክልል ለግፊት አስተላላፊ - ደቂቃ. ዋጋ

o47

ሚንትራንስፒሲ

የግፊት አስተላላፊ ቅንብሮች ለፒሲ

የስራ ክልል ለግፊት አስተላላፊ - ከፍተኛ. ዋጋ

o48

MaxTransPc

የኮንደንስ አሃድ አይነት ይምረጡ.

የፋብሪካ ስብስብ.  

After the first setting, the value is ‘locked’ and can only be changed once the controller has  been reset to its factory setting.  

When entering the refrigerant setting, the controller will ensure that the ‘Unit type’ and  refrigerant are compatible.

o61

የክፍል ዓይነት

S3 ውቅር

0 = S3 ግብዓት ጥቅም ላይ አልዋለም

1 = S3 ግቤት የመልቀቂያ ሙቀትን ለመለካት ጥቅም ላይ ይውላል

o63

S3 ውቅር

እንደ ፋብሪካ መቼት አስቀምጥ

With this setting you save the controller’s actual settings as a new basic setting (the earlier  factory settings are overwritten).

o67

የTaux ዳሳሽ (S5) አጠቃቀምን ይግለጹ

0: ጥቅም ላይ አልዋለም

1: የዘይት ሙቀትን ለመለካት ጥቅም ላይ ይውላል

2: Used to measure the temperature of the external heating function

3: Other use. Measuring of optional temperature

o69

Taux ውቅር

በክራንች መያዣ ውስጥ ኤለመንት ለማሞቅ ጊዜ

በዚህ ጊዜ ውስጥ ተቆጣጣሪው ራሱ የጠፋ እና የበራ ጊዜ ያሰላል። ሰዓቱ በሰከንዶች ውስጥ ገብቷል.

P45

PWM ጊዜ

ለማሞቂያ ኤለመንቶች ልዩነት 100% ON ነጥብ

ልዩነቱ ከ'Tamb minus Ts = 0 K' እሴት በታች ባሉ በርካታ ዲግሪዎች ላይ ይሠራል

P46

CCH_OnDiff

የማሞቂያ ኤለመንቶች ልዩነት ሙሉ ጠፍቷል ነጥብ

ልዩነቱ ከ'Tamb minus Ts = 0 K' እሴት በላይ ባሉት ዲግሪዎች ብዛት ላይ ነው።

P47

CCH_OffDiff

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 9

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

አሃድ ለማቀዝቀዝ የሚሠራበት ጊዜ

The condensing unit’s operating time can be read out here. The read-out value must be  multiplied by 1,000 in order to obtain the correct value.

(ከተፈለገ የሚታየው ዋጋ ሊስተካከል ይችላል)

P48

ክፍል Runtime

ለኮምፕሬተር የሚሠራበት ጊዜ

The compressors operating time can be read out here. The read-out value must be multi plied by 1,000 in order to obtain the correct value.

(ከተፈለገ የሚታየው ዋጋ ሊስተካከል ይችላል)

P49

Comp Runtime

በክራንች መያዣ ውስጥ ለማሞቅ ኤለመንት የሚሠራበት ጊዜ

The heating element’s operating time can be read out here. The read-out value must be  multiplied by 1,000 in order to obtain the correct value (the displayed value can be adjusted  if required).

P50

CCH የሩጫ ጊዜ

የ HP ማንቂያዎች ብዛት

The number of HP alarms can be read out here

(the displayed value can be adjusted if required).

P51

የ HP ማንቂያ Cnt

የ LP ማንቂያዎች ብዛት

The number of LP alarms can be read out here

(the displayed value can be adjusted if required).

P52

LP ማንቂያ Cnt

የመልቀቂያ ማንቂያዎች ብዛት

The number of Td alarms can be read out here

(the displayed value can be adjusted if required).

P53

ማንቂያ አስወግድ Cnt

የታገዱ የኮንደንደር ማንቂያዎች ብዛት  

The number of blocked condenser alarms can be read out here

(the displayed value can be adjusted if required).

P90

BlckAlrm Cnt

የዘይት መመለሻ አስተዳደር የፍጥነት ገደብ

If the compressor speed exceeds this limit, a time counter will be increased. It will be  decreased if the compressor speed falls down below this limit.

P77

 ORM ስፒድሊም

ዘይት መመለሻ ጊዜ አስተዳደር

Limit value of the above described time counter. If the counter exceeds this limit, the  compressor speed will be raised to the boost speed.

P78

ORM ጊዜ

የዘይት መመለሻ አስተዳደር የፍጥነት መጨመር

ይህ የመጭመቂያ ፍጥነት ዘይቱ ወደ መጭመቂያው መመለሱን ያረጋግጣል

P79

ORM BoostSpd

የዘይት መመለሻ አስተዳደር የማሳደግ ጊዜ።  

መጭመቂያው በቦስት ፍጥነት መስራት ያለበት ጊዜ

P80

ORM BoostTim

አገልግሎት

አገልግሎት

የግፊት ፒሲ አንብብ

u01

ፒሲ ባር

የሙቀት Taux አንብብ

u03

T_aux

በ DI1 ግቤት ላይ ያለ ሁኔታ። በርቷል/1=ተዘጋ

u10

DI1 ሁኔታ

በምሽት ኦፕሬሽን (ላይ ወይም ጠፍቷል) በ = የማታ ስራ ላይ ያለ ሁኔታ

u13

NightCond

Superheat ያንብቡ

u21

ከፍተኛ ሙቀት SH

የሙቀት መጠንን በ S6 ዳሳሽ ያንብቡ

u36

S6 ሙቀት

የመጭመቂያውን አቅም በ% ያንብቡ

u52

ኮምፓፕ %

በ DI2 ግቤት ላይ ያለ ሁኔታ። በርቷል/1=ተዘጋ

u37

DI2 ሁኔታ

ለ compressor ቅብብል ላይ ያለ ሁኔታ

u58

Comp Relay

ለደጋፊዎች ቅብብል ላይ ያለ ሁኔታ

u59

የደጋፊዎች ቅብብል

ለማንቂያ ቅብብል ላይ ያለ ሁኔታ

u62

የማንቂያ ቅብብል

በሪሌይ ላይ ያለው ሁኔታ "Aux"

u63

ኦክስ ቅብብል

በክራንክኬዝ ውስጥ ለማሞቂያ ኤለመንት ቅብብል ላይ ያለ ሁኔታ

u71

CCH ሪሌይ

በግቤት DI3 ላይ ያለ ሁኔታ (በ/1 = 230 ቮ)

u87

DI3 ሁኔታ

በሙቀት ውስጥ የኮንዲንግ ግፊትን ያንብቡ

U22

Tc

ግፊትን ያንብቡ መዝ

U23

Ps

በሙቀት ውስጥ የመሳብ ግፊትን ያንብቡ

U24

Ts

የአካባቢ ሙቀት Tamb ያንብቡ

U25

ቲ_ድባብ

የመልቀቂያ ሙቀት Td ያንብቡ

U26

ቲ_ፈሳሽ

የሚጠባ ጋዝ ሙቀትን በቲ.ኤስ

U27

ቲ_መምጠጥ

ጥራዝtagሠ በአናሎግ ውፅዓት AO1 ላይ

U44

AO_1 ቮልት

ጥራዝtagሠ በአናሎግ ውፅዓት AO2 ላይ

U56

AO_2 ቮልት

10 | BC172686425380en-000901 © Danfoss | DCS (vt) | 2020.11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

የአሠራር ሁኔታ

(መለኪያ)

The controller goes through some regulating situations where it is just waiting for the next  point of the regulation. To make these “why is nothing happening” situations visible, you  can see an operating status on the display. Push briefly (1s) the upper button. If there is a  status code, it will be shown on the display. The individual status codes have the following  meanings:

Ctrl ሁኔታ፡-

መደበኛ ደንብ

S0

0

መጭመቂያው በሚሠራበት ጊዜ ቢያንስ ለ x ደቂቃዎች መሮጥ አለበት።

S2

2

መጭመቂያው ሲቆም ቢያንስ ለ x ደቂቃዎች ቆሞ መቆየት አለበት።

S3

3

ማቀዝቀዣ በዋናው ማብሪያ / ማጥፊያ ቆሟል። ወይ r12 ወይም DI-input

S10

10

የውጤቶች በእጅ ቁጥጥር

S25

25

ምንም ማቀዝቀዣ አልተመረጠም።

S26

26

የደህንነት መቋረጥ ከፍተኛ. የማቀዝቀዝ ግፊት አልፏል. ሁሉም መጭመቂያዎች ቆመዋል።

S34

34

ሌሎች ማሳያዎች፡-

የይለፍ ቃል ያስፈልጋል። የይለፍ ቃል አዘጋጅ

PS

ደንቡ በዋናው ማብሪያ / ማጥፊያ በኩል ይቆማል

ጠፍቷል

ምንም ማቀዝቀዣ አልተመረጠም።

ማጣቀሻ

ለማጠራቀሚያው ክፍል ምንም ዓይነት አልተመረጠም።

ተይብ

የተሳሳተ መልእክት

In an error situation the LED’s on the front will flash and the alarm relay will be activated. If you push the top button in this situation you can see the  alarm report in the display.

ሁለት ዓይነት የስህተት ሪፖርቶች አሉ - በዕለት ተዕለት እንቅስቃሴው ውስጥ የሚፈጠር ማንቂያ ሊሆን ይችላል ወይም በመትከል ላይ ጉድለት ሊኖር ይችላል. የ A-ማንቂያ ደወል የተቀመጠው የጊዜ መዘግየቱ እስኪያበቃ ድረስ አይታዩም።  

E-alarms, on the other hand, will become visible the moment the error occurs.

(An A alarm will not be visible as long as there is an active E alarm).

ሊታዩ የሚችሉ መልእክቶች እነኚሁና፡

Code / Alarm text via data  communication

መግለጫ

ድርጊት

A2/- LP ማንቂያ

ዝቅተኛ የመሳብ ግፊት

ለኮንዲንግ ክፍሉ መመሪያዎችን ይመልከቱ

A11/- የለም Rfg. ሴል.

ምንም ማቀዝቀዣ አልተመረጠም።

o30 አዘጋጅ

A16 /- DI2 ማንቂያ

DI2 ማንቂያ

በ DI2 ግብዓት ላይ ምልክት የሚልከውን ተግባር ያረጋግጡ

A17 / - HP ማንቂያ

C73/DI3 ማንቂያ (ከፍተኛ/ዝቅተኛ ግፊት ማንቂያ)

ለኮንዲንግ ክፍሉ መመሪያዎችን ይመልከቱ

A45 /- በተጠባባቂ ሁነታ

የመጠባበቂያ ቦታ (የቆመ ማቀዝቀዣ በ r12 ወይም DI1-input)

r12 እና/ወይም DI1 ግብአት ደንቡን ይጀምራል

A80 / - ኮን. ታግዷል

የአየር ፍሰት ቀንሷል።

የማጣቀሚያውን ክፍል ያጽዱ

A96 / - ከፍተኛ ዲስክ. የሙቀት መጠን

የፍሳሽ ጋዝ ሙቀት አልፏል

ለኮንዲንግ ክፍሉ መመሪያዎችን ይመልከቱ

A97 / - የደህንነት ማንቂያ

በ DI2 ወይም DI 3 ላይ ያለው የደህንነት ተግባር ነቅቷል።

Check the function that sends a signal at the DI2 or DI3  input and the direction of rotation of the compressor

A98 / - የመንጃ ማንቂያ

የፍጥነት መቆጣጠሪያ ማንቂያ

የፍጥነት መቆጣጠሪያን ይፈትሹ

E1 /- Ctrl. ስህተት

በመቆጣጠሪያው ውስጥ ያሉ ስህተቶች

ዳሳሽ እና ግንኙነትን ያረጋግጡ

E20 /- ፒሲ ዳሳሽ ስህተት

የግፊት አስተላላፊ ፒሲ ላይ ስህተት

E30 /- Taux ዳሳሽ ስህተት

በAux ዳሳሽ፣ S5 ላይ ስህተት

E31/—ታምብ ዳሳሽ ስህተት

በአየር ዳሳሽ ላይ ስህተት፣ S2

E32 / —Tdis ዳሳሽ ስህተት

የመልቀቂያ ዳሳሽ ላይ ስህተት፣ S3

E33 / —Tsuc ዳሳሽ ስህተት

በመምጠጥ ጋዝ ዳሳሽ ላይ ስህተት፣ S4

E39/- Ps Sensor Err

የግፊት አስተላላፊው ላይ ስህተት

የውሂብ ግንኙነት

የግለሰብ ማንቂያዎች አስፈላጊነት በቅንብር ሊገለጽ ይችላል። ቅንብሩ በቡድን "የማንቂያ መድረሻዎች" ውስጥ መከናወን አለበት.ቅንብሮች ከ  

ቅንብሮች ከ  

መዝገብ የማንቂያ ቅብብል በኩል ይላኩ

Non High Low-High Network

የስርዓት አስተዳዳሪ

AKM (AKM መድረሻ)

High 1 X X X X Middle 2 X X X Low 3 X X X Log only X

ተሰናክሏል።

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

ኦፕሬሽን

ማሳያ

The values will be shown with three digits, and with a setting you  can determine whether the temperature is to be shown in °C or in  °F.

ብርሃን አመንጪ ዳዮዶች (LED) በፊት ፓነል ላይ

The LED’s on the front panel will light up when the relevant relay is  activated.

 = ማቀዝቀዣ

 = በክራንክኬዝ ውስጥ ያለው የማሞቂያ ኤለመንት በርቷል።

 ደጋፊ እየሮጠ

The light-emitting diodes will flash when there is an alarm. In this situation you can download the error code to the display  and cancel/sign for the alarm by giving the upper button a brief  push.

አዝራሮቹ

When you want to change a setting, the upper and the lower  button will give you a higher or lower value depending on the  button you are pushing. But before you change the value, you  must have access to the menu. You obtain this by pushing the  upper button for a couple of seconds – you will then enter the  

column with parameter codes. Find the parameter code you  want to change and push the middle buttons until value for the  parameter is shown. When you have changed the value, save the  new value by once more pushing the middle button. (If not operated for 20 (5) seconds, the display will change back to  the Ts/Tc temperature display).

Exampሌስ

ምናሌ አዘጋጅ

1. Push the upper button until a parameter r05 is shown 2. Push the upper or the lower button and find that parameter you  want to change

3. Push the middle button until the parameter value is shown 4. Push the upper or the lower button and select the new value 5. Push the middle button again to freeze the value.

የማስጠንቀቂያ ደወል መቆራረጥ/የደረሰኝ ማንቂያ/የደወል ኮድ ይመልከቱ  

• የላይኛውን ቁልፍ አጭር ተጫን

If there are several alarm codes they are found in a rolling stack.  Push the uppermost or lowermost button to scan the rolling  stack.

ነጥብ አዘጋጅ

1. Push the middle button until the temperature value is shown 2. Push the upper or the lower button and select the new value 3. Push the middle button again to conclude the setting.

Reading the temperature at Ts (if Tc is the primary display) or Tc (if Ts is  the primary display)

• A short press of the lower button

ጥሩ ጅምር ያድርጉ

በሚከተለው ሂደት ደንቡን በፍጥነት መጀመር ይችላሉ-

Open parameter r12 and stop the regulation (in a new and not  previously set unit, r12 will already be set to 0 which means  stopped regulation.  

ማቀዝቀዣውን በፓራሜትር o30 ይምረጡ

Open parameter r12 and start the regulation. Start/stop at input  DI1 or DI2 must also be activated.

Go through the survey of factory settings. Make any necessary  changes in the respective parameters.

ለአውታረ መረብ.  

– Set the address in o03  

– Activate scan function in the system manager.

ማስታወሻ

When delivering the condensing unit, the controller will be set  to the condensing unit type (setting o61). This setting will be  compared with your refrigerant setting. If you select a “non permitted refrigerant”, the display will show “ref” and await a new  setting.

(In the event of a controller change, 061 must be set as indicated  in the instructions from Danfoss)

12 | BC172686425380en-000901 © Danfoss | DCS (vt) | 2020.11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

የምናሌ ዳሰሳ SW = 3.6x

መለኪያ

Min. value Max. value

ፋብሪካ  

ቅንብር

ትክክለኛ  

ቅንብር

ተግባር

ኮድ

መደበኛ ክወና

Set point (regulation reference follows the number of degrees above the outside temperature  Tamb)

--

2.0 ኪ

20.0 ኪ

8.0 ኪ

ደንብ

SI ወይም US ማሳያን ይምረጡ። 0=SI (ባር እና ° ሴ)። 1=US (Psig እና °F)

r05

0/°ሴ

1 / ረ

0/°ሴ

የውስጥ ዋና መቀየሪያ. መመሪያ እና አገልግሎት = -1, አቁም ደንብ = 0, ጀምር ደንብ =1

r12

-1

1

0

በምሽት ቀዶ ጥገና ወቅት ማካካሻ. በምሽት ክወና ወቅት ማመሳከሪያው በዚህ ዋጋ ይነሳል

r13

0 ኪ

10 ኪ

2 ኪ

የመምጠጥ ግፊት Ts ነጥብ ያዘጋጁ

r23

-25 ° ሴ

10 ° ሴ

-7 ° ሴ

ለቲ.ሲ

r29

ቴርሞስታት የተቆረጠ ዋጋ ለውጫዊ ማሞቂያ ኤለመንት (069=2 እና o40=1)

r71

-30,0 ° ሴ

0,0 ° ሴ

-25 ° ሴ

ደቂቃ የማጠናከሪያ ሙቀት (ዝቅተኛው የተፈቀደ የቲ.ሲ. ማጣቀሻ)

r82

0 ° ሴ

40 ° ሴ

25 ° ሴ

ከፍተኛ. የማጠናከሪያ ሙቀት (ከፍተኛው የተፈቀደ የቲ.ሲ. ማጣቀሻ)

r83

20 ° ሴ

50 ° ሴ

40 ° ሴ

ከፍተኛ. የፍሳሽ ጋዝ ሙቀት Td

r84

50 ° ሴ

140 ° ሴ

125 ° ሴ

ማንቂያዎች

በ DI2 ግብዓት ላይ በምልክት ላይ የማንቂያ ጊዜ መዘግየት። የሚሰራው o37=4 ወይም 5 ከሆነ ብቻ ነው።

አ28

0 ደቂቃ

240 ደቂቃ

30 ደቂቃ

በማጠራቀሚያ ውስጥ በቂ ያልሆነ የማቀዝቀዝ ማንቂያ። የሙቀት ልዩነት 30.0 K = ማንቂያ ተሰናክሏል

አ70

3.0 ኪ

30.0 ኪ

10.0 ኪ

ለ A80 ማንቂያ የዘገየ ጊዜ። በተጨማሪም ግቤት A70 ይመልከቱ።

አ71

5 ደቂቃ

240 ደቂቃ

30 ደቂቃ

መጭመቂያ

ደቂቃ በሰዓቱ

c01

1 ሰ

240 ሰ

5 ሰ

ደቂቃ ጠፍቷል-ጊዜ

c02

3 ሰ

240 ሰ

120 ሰ

ደቂቃ በ compressor መካከል ያለው ጊዜ ይጀምራል

c07

0 ደቂቃ

30 ደቂቃ

5 ደቂቃ

መጭመቂያው የሚቆምበት ዝቅተኛ የፓምፕ ገደብ (ማዋቀር 0.0 = ምንም ተግባር የለም)

***

c33

0,0 ባር

6,0 ባር

0,0 ባር

ደቂቃ መጭመቂያ ፍጥነት

c46

25 Hz

70 Hz

30 Hz

ለኮምፕሬተር ፍጥነትን ጀምር

c47

30 Hz

70 Hz

50 Hz

ከፍተኛ. መጭመቂያ ፍጥነት

c48

50 Hz

100 Hz

100 Hz

ከፍተኛ. በምሽት በሚሠራበት ጊዜ የመጭመቂያ ፍጥነት (% -የ c48 እሴት)

c69

50%

100%

70%

የኮምፕረር መቆጣጠሪያ ሁነታ ፍቺ

0: ምንም መጭመቂያ የለም - የማጠናከሪያ ክፍል ጠፍቷል

1: ቋሚ ፍጥነት - ግቤት DI1 ቋሚ የፍጥነት መጭመቂያ ለመጀመር / ለማቆም ያገለግላል  

2: Variable speed – Input DI1 used for start / stop of variable speed-controlled compressor  with a 0 – 10 V signal on AO2

*

c71

0

2

1

ለከፍተኛ Td የጊዜ መዘግየት። ጊዜው ሲያልቅ መጭመቂያው ይቆማል።

c72

0 ደቂቃ

20 ደቂቃ

1 ደቂቃ

ከፍተኛ. ግፊት. ከፍተኛ ግፊት ከተመዘገበ መጭመቂያው ይቆማል

***

c73

7,0 ባር

31,0 ባር

23,0 ባር

ለከፍተኛው ልዩነት. ግፊት (c73)

c74

1,0 ባር

10,0 ባር

3,0 ባር

ደቂቃ የመሳብ ግፊት Ps. ዝቅተኛ ግፊት ከተመዘገበ መጭመቂያው ይቆማል

***

c75

-0,3 ባር

6,0 ባር

1,4 ባር

የ ደቂቃ ልዩነት የመሳብ ግፊት እና ወደ ታች ፓምፕ

c76

0,1 ባር

5,0 ባር

0,7 ባር

Amplification ምክንያት Kp ለ compressors PI-regulation

c82

3,0

30,0

20,0

የውህደት ጊዜ Tn ለ compressors PI-regulation

c83

30 ሰ

360 ሰ

60 ሰ

ፈሳሽ መርፌ ማካካሻ

c88

0,1 ኪ

20,0 ኪ

5,0 ኪ

ፈሳሽ መርፌ hysterese

c89

3,0 ኪ

30,0 ኪ

15,0 ኪ

ፈሳሽ መርፌ ከተከተለ በኋላ የኮምፕረር ማቆሚያ መዘግየት

c90

0 ሰ

10 ሰ

3 ሰ

የሚፈለገው የኮምፕረር ፍጥነት ከግፊት አስተላላፊው Ps ምልክት ካልተሳካ

c93

25 Hz

70 Hz

60 Hz

ዝቅተኛ ድባብ LP በሰዓቱ

c94

0 ሰ

120 ሰ

0 ሰ

የ Comp min ፍጥነት ወደ StartSpeed ​​የሚጨምርበት Tc ይለካል

c95

10,0 ° ሴ

70,0 ° ሴ

50,0 ° ሴ

የመቆጣጠሪያ መለኪያዎች

Amplification ምክንያት Kp ለ PI-ደንብ

n04

1.0

20.0

7.0

የውህደት ጊዜ Tn ለ PI-regulation

n05

20

120

40

መለኪያው ከማጣቀሻው በጣም በሚርቅበት ጊዜ Kp max ለ PI ደንብ

n95

5,0

50,0

20,0

አድናቂ

የአየር ማራገቢያ ፍጥነት ንባብ በ%

F07

የሚፈቀደው የደጋፊ ፍጥነት ለውጥ (ወደ ዝቅተኛ እሴት) % በሰከንድ።

F14

1,0%

5,0%

5,0%

የጆግ ፍጥነት (ደጋፊው ሲጀመር እንደ % ፍጥነት)

F15

40%

100%

40%

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 13

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

ቀጠለ

ኮድ

ደቂቃ

ከፍተኛ.

ፋክ

ትክክለኛ

በዝቅተኛ የሙቀት መጠን የጆግ ፍጥነት

F16

0%

40%

10%

የአየር ማራገቢያ መቆጣጠሪያ ፍቺ፡ 0=ጠፍቷል; 1=ውስጣዊ ቁጥጥር። 2=የውጭ ፍጥነት መቆጣጠሪያ

F17

0

2

1

ዝቅተኛ የአድናቂዎች ፍጥነት። ፍላጎት መቀነስ አድናቂውን ያቆማል።

F18

0%

40%

10%

ከፍተኛ አድናቂ ፍጥነት

F19

40%

100%

100%

የደጋፊውን ፍጥነት በእጅ መቆጣጠር. (r12 ወደ -1 ሲዋቀር ብቻ)

**

F20

0%

100%

0%

የደረጃ ማካካሻ (ልዩ የሰለጠኑ ሰዎች ብቻ መቀየር አለባቸው።)

F21

0

50

20

መጭመቂያ ከመጀመሩ በፊት በ A2L-ማቀዝቀዣዎች ላይ የቅድመ-አየር ማናፈሻ ጊዜ

F23

30

180

30

እውነተኛ ሰዓት

ወደ ቀን ሥራ የሚቀይሩበት ጊዜ

t17

0 ሰዓት

23 ሰዓት

0

ወደ ማታ አሠራር የሚቀይሩበት ጊዜ

t18

0 ሰዓት

23 ሰዓት

0

ሰዓት - የሰዓታት አቀማመጥ

t07

0 ሰዓት

23 ሰዓት

0

ሰዓት - ደቂቃ ቅንብር

t08

0 ደቂቃ

59 ደቂቃ

0

ሰዓት - የቀን ቅንብር

t45

1 ቀን

31 ቀናት

1

ሰዓት - የወር አቀማመጥ

t46

1 ወር

12 ወር

1

ሰዓት - የዓመቱ አቀማመጥ

t47

0 አመት

99 አመት

0

የተለያዩ

የአውታረ መረብ አድራሻ

o03

0

240

0

ማብሪያ / ማጥፊያ (የአገልግሎት ፒን መልእክት)

አስፈላጊ! o61 አለበት ከ o04 በፊት ይዘጋጁ

(used at LON 485 only)

o04

0/ ጠፍቷል

1/ በርቷል

0/ ጠፍቷል

የመዳረሻ ኮድ (የሁሉም ቅንብሮች መዳረሻ)

o05

0

100

0

የመቆጣጠሪያዎች ሶፍትዌር ስሪት ማንበብ

o08

ለማሳየት ሲግናል ይምረጡ view. 1=Suction pressure in degrees, Ts. 2=Condensing pressure in  degrees, Ts

o17

1

2

1

የግፊት አስተላላፊ የስራ ክልል መዝ - ደቂቃ. ዋጋ

o20

-1 ባር

5 ባር

-1

የግፊት አስተላላፊ የስራ ክልል Ps-max. ዋጋ

o21

6 ባር

200 ባር

12

የማቀዝቀዣ ቅንብር;

2=R22. 3=R134a. 13=User defined. 17=R507. 19=R404A. 20=R407C. 21=R407A. 36=R513A.  37=R407F. 40=R448A. 41=R449A. 42=R452A. 39=R1234yf. 51=R454C. 52=R455A

*

o30

0

42

0

በ DI2 ላይ የግቤት ምልክት ተግባር፡-

(0=not used, 1=External safety function. Regulate when closed, 2=external main switch,  3=Night operation when closed, 4=alarm function when closed, 5=alarm function when  open. 6=on/off Status for monitoring. 7=Alarm from speed regulation

o37

0

7

0

Aux relay ተግባር፡-

(0=ጥቅም ላይ ያልዋለ፣ 1=የውጭ ማሞቂያ ኤለመንት፣ 2=ፈሳሽ መርፌ፣ 3=የዘይት መመለስ ተግባር)

***

o40

0

3

1

የግፊት አስተላላፊ የስራ ክልል ፒሲ - ደቂቃ. ዋጋ

o47

-1 ባር

5 ባር

0 ባር

የግፊት አስተላላፊ የስራ ክልል ፒሲ - ከፍተኛ. ዋጋ

o48

6 ባር

200 ባር

32 ባር

Setting of condensing unit type (is factory set when the controller is mounted and cannot be  subsequently changed)

*

o61

0

69

0

የዳሳሽ ግቤት S3 የሚለቀቅ ጋዝ ሙቀትን ለመለካት ጥቅም ላይ ይውላል (1=አዎ)

o63

0

1

1

የመቆጣጠሪያዎች የፋብሪካ ቅንብሮችን አሁን ባለው ቅንጅቶች ይተኩ

o67

ጠፍቷል (0)

በ (1)

ጠፍቷል (0)

Defines the use of the Taux sensor: 0=not used; 1=measuring of oil temperature;  2=measurement from external heat function 3=other optional use

o69

0

3

0

በክራንክኬዝ ውስጥ ኤለመንት ለማሞቅ የሚቆይበት ጊዜ (በርቷል + ጠፍቷል ጊዜ)

P45

30 ሰ

255 ሰ

240 ሰ

ለማሞቂያ ኤለመንቶች ልዩነት 100% ON ነጥብ

P46

-20 ኪ

-5 ኪ

-10 ኪ

ለማሞቂያ ኤለመንቶች ልዩነት 100% OFF ነጥብ

P47

5 ኪ

20 ኪ

10 ኪ

Read-out of operating time for condenser unit. (Value must be multiplied by 1,000). The value  can be adjusted.

P48

0 ሰ

Read-out of compressor operating time. (Value must be multiplied by 1,000). The value can  be adjusted.

P49

0 ሰ

Read-out of operating time of heating element in crankcase. (Value must be multiplied by  1,000). The value can be adjusted.

P50

0 ሰ

ከ HP ማንቂያዎች ብዛት ተነበበ። እሴቱ ሊስተካከል ይችላል.

P51

0

ከ LP ማንቂያዎች ብዛት ተነበበ። እሴቱ ሊስተካከል ይችላል.

P52

0

ከTd ማንቂያዎች ብዛት ተነበበ። እሴቱ ሊስተካከል ይችላል.

P53

0

የታገዱ የኮንደነር ማንቂያዎች ብዛት ተነበበ። እሴቱ ሊስተካከል ይችላል

P90

0

ዘይት መመለስ አስተዳደር. ለቆጣሪው መነሻ ነጥብ የመጭመቂያ ፍጥነት

P77

25 Hz

70 Hz

40 Hz

14 | BC172686425380en-000901 © Danfoss | DCS (vt) | 2020.11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

ቀጠለ

ኮድ

ደቂቃ

ከፍተኛ.

ፋክ

ትክክለኛ

ዘይት መመለስ አስተዳደር. ለቆጣሪ ዋጋ ይገድቡ

P78

5 ደቂቃ

720 ደቂቃ

20 ደቂቃ

ዘይት መመለስ አስተዳደር. የፍጥነት መጨመር

P79

40 Hz

100 Hz

50 Hz

ዘይት መመለስ አስተዳደር. የማበልጸጊያ ጊዜ።

P80

10 ሰ

600 ሰ

60 ሰ

አገልግሎት

በፒሲ ላይ የንባብ ግፊት

u01

ባር

የተነበበ የሙቀት መጠን Taux

u03

° ሴ

በ DI1 ግቤት ላይ ያለ ሁኔታ። 1=ላይ=ተዘጋ

u10

በምሽት ኦፕሬሽን (ላይ ወይም ጠፍቷል) ሁኔታ 1= ላይ = የማታ ስራ

u13

ሱፐር ሙቀት አንብብ

u21

K

የንባብ ሙቀት በ S6 ዳሳሽ

u36

° ሴ

በ DI2 ግቤት ላይ ያለ ሁኔታ። 1=ላይ=ተዘጋ

u37

የመጭመቂያውን አቅም በ% ያንብቡ

u52

%

ወደ መጭመቂያው በማስተላለፍ ላይ ያለ ሁኔታ። 1=ላይ=ተዘጋ

**

u58

ለደጋፊው በማስተላለፍ ላይ ያለ ሁኔታ። 1=ላይ=ተዘጋ

**

u59

ወደ ማንቂያው በማስተላለፍ ላይ ያለ ሁኔታ። 1=ላይ=ተዘጋ

**

u62

በ "Aux" ቅብብል ላይ ያለ ሁኔታ. 1=ላይ=ተዘጋ

**

u63

በክራንች መያዣ ውስጥ ወደ ማሞቂያ ኤለመንት በማስተላለፍ ላይ ያለ ሁኔታ። 1=ላይ=ተዘጋ

**

u71

በከፍተኛ ጥራዝ ላይ ያለ ሁኔታtagሠ ግቤት DI3. 1= ላይ=230 ቪ

u87

በሙቀት ውስጥ የማጠናከሪያ ግፊትን ያንብቡ

U22

° ሴ

የተነበበ ግፊት መዝ

U23

ባር

በሙቀት ውስጥ የመሳብ ግፊትን ያንብቡ

U24

° ሴ

የንባብ የአካባቢ ሙቀት Tamb

U25

° ሴ

የተነበበ የመልቀቂያ ሙቀት Td

U26

° ሴ

የተነበበ የጋዝ ሙቀት ቲ

U27

° ሴ

ጥራዝ አንብብtagሠ በውጤቱ AO1 ላይ

U44

V

ጥራዝ አንብብtagሠ በውጤቱ AO2 ላይ

U56

V

*) ደንቡ ሲቆም ብቻ ነው (r12=0)

**) በእጅ ቁጥጥር ሊደረግበት ይችላል, ግን r12 = -1 በሚሆንበት ጊዜ ብቻ

***) This parameter depends on parameter o30 and o61 settings

የፋብሪካ ቅንብር

ወደ ፋብሪካው የተቀመጡ እሴቶች መመለስ ከፈለጉ በዚህ መንገድ ሊከናወን ይችላል-

- የአቅርቦትን ጥራዝ ይቁረጡtagሠ ወደ መቆጣጠሪያው

- የአቅርቦት ቁልፉን እንደገና በሚያገናኙበት ጊዜ የላይኛው እና የታችኛው ቁልፍ ተጭነው ይያዙtage

የአሃድ ስታቲስቲክስ መለኪያዎችን ዳግም ማስጀመር

All the Unit status parameters (P48 to P53 and P90) can be set / cleared using the following procedure • Set Main Switch to 0

  • የስታቲስቲክስ መለኪያዎችን ይቀይሩ - እንደ የማንቂያ ቆጣሪዎችን ወደ 0 ማቀናበር
  • 10 ሰከንድ ይጠብቁ - ወደ EEROM መፃፍ ለማረጋገጥ
  • Make a repower of the Controller – transfer new settings to “statistics function” • Set Main Switch ON – and the parameters is set to the new value

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 15

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

ግንኙነቶች

0 - 10 V

0 - 10 V

R=120 

R=120 

AKS32R

AKS32R

– – +

24 25 26 27 3028 29 3331 32 36 37383934 35 4041 4243 51 52 53 57565554 60 61 62 

DI1 DI2 Pc PsS2 S3 S4 S5 S6

ማሳያRS EKA

AO2AO1

ፈን

ማንቂያ

485MODBUS

Comp CCH Fan Aux

ኤል.ኤን DI3

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

22 23 እ.ኤ.አ 

LP

HP

DI1

የዲጂታል ግቤት ምልክት.

230 ቪ 230 ቮ 230 ቮ 230 ቮ 230 ቮ 230 ቮ 230 ቮ 230 ቪ

AO1፣ ተርሚናል 54፣ 55

Output signal, 0 – 10 V. Must be used if the fan is equipped with  

ማቀዝቀዝ ለመጀመር/ለማቆም ጥቅም ላይ ይውላል (የክፍል ቴርሞስታት)  

መግቢያው አጭር ዙር ሲሆን ይጀምራል።

DI2

የዲጂታል ግቤት ምልክት.  

የተገለጸው ተግባር ገባሪ የሚሆነው ግብአቱ አጭር ሲከፈት/ሲከፈት ነው። ተግባሩ በ o37 ውስጥ ተገልጿል.  

Pc

የግፊት ማስተላለፊያ፣ ሬቲሜትሪክ AKS 32R፣ ከ0 እስከ 32 ባር ከተርሚናል 28፣ 29 እና ​​30 ጋር ይገናኙ።

Ps

የግፊት አስተላላፊ፣ ሬሾሜትሪክ ለምሳሌ AKS 32R፣ -1 እስከ 12 bar ከተርሚናል 31፣ 32 እና 33 ጋር የተገናኘ።

S2

የአየር ዳሳሽ ፣ ታምብ Pt 1000 ohm ዳሳሽ፣ ለምሳሌ ኤኬኤስ 11

S3

የፍሳሽ ጋዝ ዳሳሽ፣ ቲ.ዲ. Pt 1000 ohm ዳሳሽ፣ ለምሳሌ ኤኬኤስ 21

S4

የመሳብ ጋዝ ሙቀት፣ ቲ. Pt 1000 ohm ዳሳሽ፣ ለምሳሌ ኤኬኤስ 11

ኤስ 5፣  

Extra temperature measurement, Taux. Pt 1000 ohm sensor, eg.  AKS 11

ኤስ 6፣  

Extra temperature measurement, S6. Pt 1000-ohm sensor, eg. AKS  11

EKA ማሳያ

If there is external reading/operation of the controller, display type EKA 163B or EKA 164B can be connected.  

RS485 (ተርሚናል 51፣ 52,53፣XNUMX)

For data communication, but only if a data communication module is inserted in the controller. The module can be Lon. If data communication is used, it is important that the installation of the data communication cable is performed correctly. See separate literature No. RC8AC…

internal speed control and 0 – 10 V DC input, e.g. EC-motor.

AO2፣ ተርሚናል 56፣ 57

የውጤት ምልክት, 0 - 10 V. መጭመቂያው የፍጥነት መቆጣጠሪያ ከሆነ ጥቅም ላይ መዋል አለበት.

MODBUS (ተርሚናል 60፣61፣62)

በModbus የውሂብ ግንኙነት ውስጥ አብሮ የተሰራ።

የመረጃ ልውውጥ ጥቅም ላይ ከዋለ የውሂብ ግንኙነት ገመዱን መትከል በትክክል መፈጸሙ አስፈላጊ ነው. የተለየ ስነ ጽሑፍ ቁጥር RC8AC ይመልከቱ…

(Alternatively, the terminals can be connected to an external display type EKA 163A or 164A, but then they cannot be used for data communication. Any data communication must then be carried out by one of the other methods.)

አቅርቦት ጥራዝtage

230 V AC (ይህ ለሁሉም 230 ቮ ግንኙነቶች አንድ አይነት ደረጃ መሆን አለበት)።

ፈን

የደጋፊዎች ግንኙነት። ፍጥነት ከውስጥ ቁጥጥር.

ማንቂያ

በማንቂያ ሁኔታዎች እና ተቆጣጣሪው ኃይል ከሌለው በተርሚናል 7 እና 8 መካከል ግንኙነት አለ.

ኮም

መጭመቂያThere is a connection between terminal 10 and 11, when the compressor is running.

ሲ.ሲ.ኤች.

በክራንች መያዣ ውስጥ ያለው ማሞቂያ

ማሞቂያ በሚፈጠርበት ጊዜ በተርሚናሎች 12 እና 14 መካከል ግንኙነት አለ.

አድናቂ

There is connection between terminals 15 and 16 when the fan’s  speed is raised to over 95%. (Fan signal changes from terminal 5-6  to 15-16. Connect wire from terminal 16 to the fan.)

16 | BC172686425380en-000901 © Danfoss | DCS (vt) | 2020.11

User Guide | Controller for condensing unit, Optima™ በተጨማሪም

አክስ

Liquid injection in suction line / external heating element / oil  return function for speed-controlled compressor

በተርሚናሎች 17 እና 19 መካከል ግንኙነት አለ፣ ተግባሩ ሲሰራ።

DI3

Digital input signal from low/high pressure monitoring.  The signal must have a voltagሠ የ 0/230 V AC.

የኤሌክትሪክ ድምጽ

Cables for sensors, DI inputs and data communication must be kept separate from other electric cables:

- የተለየ የኬብል ማስቀመጫዎችን ይጠቀሙ

– Keep a distance between cables of at least 10 cm. – Long cables at the DI input should be avoided

ውሂብ

አቅርቦት ጥራዝtage

230 ቮ AC +10/-15 %. 5 VA፣ 50/60 Hz

Sensor S2, S3,  S4, S5, S6

Pt 1000

ትክክለኛነት

የመለኪያ ክልል

-60 - 120 ° ሴ

(S3 to 150 °C)

ተቆጣጣሪ

± 1 ኪ ከ -35 ° ሴ

± 0.5 ኪ -35 - 25 ° ሴ;

± 1 ኪ ከ 25 ° ሴ በላይ

Pt 1000 ዳሳሽ

± 0.3 ኪ በ 0 ° ሴ

± 0.005 ኪ በዲግሪ

መለካት  

Pc, Ps

ጫና  

አስተላላፊ

ሬዮሜትሪክ ለምሳሌ. AKS 32R, DST-P110

ማሳያ

LED፣ 3-አሃዞች

ውጫዊ ማሳያ

EKA 163B ወይም 164B (ማንኛውም EKA 163A ወይም 164A)

ዲጂታል ግብዓቶች  

DI1፣ DI2

የእውቂያ ተግባራት ምልክት

ለዕውቂያዎች የሚያስፈልጉ መስፈርቶች፡- ወርቅ መቀባት

የኬብሉ ርዝመት ከፍተኛ መሆን አለበት። 15 ሜ

ገመዱ ረዘም ያለ ሲሆን ረዳት ማስተላለፊያዎችን ይጠቀሙ

ዲጂታል ግቤት DI3

230 ቪ ኤሲ ከደህንነት ፕሬሶስታት። ዝቅተኛ / ከፍተኛ ግፊት

Electrical con

የአንገት ገመድ

ከፍተኛ.1.5 ሚሜ2 ባለብዙ-ኮር ገመድ

Triac ውፅዓት

አድናቂ

Max. 240 V AC, Min. 28 V AC

ማክስ 2.0 ሀ

መፍሰስ <1 mA

ቅብብል*

CE (250 ቪ ኤሲ)

ኮም, ሲ.ሲ.ኤች

4 (3) አ

ማንቂያ፣ ደጋፊ፣ አክስ

4 (3) አ

የአናሎግ ውፅዓት

2 pcs. 0 - 10 ቪ ዲ.ሲ

(For external speed control of fans and compressors) Min. load = 10 K ohm. (Max. 1 mA)

አካባቢ

-25 - 55 ° ሴ, በቀዶ ጥገና ወቅት

-40 - 70 ° ሴ, በማጓጓዝ ጊዜ

20 - 80% Rh, አልተጨመቀም

ምንም አስደንጋጭ ተጽዕኖ/ ንዝረት የለም።

ጥግግት

አይፒ 20

በመጫን ላይ

DIN-ባቡር ወይም ግድግዳ

ክብደት

0.4 ኪ.ግ

Data communi cation

ቋሚ

MODBUS

የቅጥያ አማራጮች

ሎን

Power reserve  for the clock

4 ሰዓታት

ማጽደቂያዎች

EC ዝቅተኛ ጥራዝtage Directive and EMC demands re CE marking complied with

LVD tested acc. EN 60730-1 and EN 60730-2-9, A1, A2 EMC-tested acc. EN 61000-6-2 and EN 61000-6-3

የመጫኛ ግምት

Accidental damage, poor installation, or site conditions can give rise to malfunctions of the control system and ultimately lead to a plant breakdown. Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation, for example, አሁንም ችግሮችን ሊያስከትል ይችላል. የኤሌክትሮኒክስ ቁጥጥሮች ለመደበኛ, ጥሩ የምህንድስና ልምምድ ምትክ አይደሉም.

Danfoss will not be responsible for any goods, or plant components, damaged as a result of the above defects. It is the installer’s  responsibility to check the installation thoroughly, and to fit the  necessary safety devices. Special reference is made to the neces sity of signals to the controller when the compressor is stopped  and to the need of liquid receivers before the compressors. Your local Danfoss agent will be pleased to assist with further advice, etc.

* Comp እና CCH 16 A ቅብብሎሽ ናቸው። ማንቂያ እና ደጋፊ 8 A ቅብብል ናቸው። ከፍተኛ. ጭነት መከበር አለበት

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 17

በማዘዝ ላይ

ዓይነት

ተግባር

ኮድ ቁ.

Optima™ በተጨማሪም

Condensing unit controller

Prepared for data communication

Plug for screw terminals not enclosed

084B8080

ይሰኩት

Plug with screw terminals

084B8166

ኢካ 175

Data communication module LON RS485

084B8579

EKA 163B

ለቀጥታ ግንኙነት ውጫዊ ማሳያ

084B8574

EKA 164B

External display with operation buttons and plug for direct  connections

084B8575

ኢካ 163 አ

ውጫዊ ማሳያ ከ screw ተርሚናሎች ጋር

084B8562

ኢካ 164 አ

ውጫዊ ማሳያ ከኦፕሬሽን አዝራሮች እና ዊንጣዎች ተርሚናሎች ጋር

084B8563

Wire with plug

ሽቦ ለማሳያ ክፍል (9 ሜትር፣ ከመሰኪያ ጋር)

084B7630

(24 ኮምፒዩተሮችን)

ኢካ 183 አ

የፕሮግራም አወጣጥ ቁልፍ

084B8582

© Danfoss | DCS (vt) | 2020.11 BC172686425380en-000901 | 18