SINOTIMER STVP936-1-80A

User Manual: Three-Phase Adjustable Over/Under Voltage Protector

Model: STVP936-1-80A

1. Introduction

The SINOTIMER STVP series automatic over-voltage and under-voltage protector is designed for three-phase 3*127V/220VAC power systems with a rated working current of 80A. This device provides essential protection for electrical equipment by instantaneously cutting off the power supply when over-voltage, under-voltage, or over-current conditions are detected. Once the circuit voltage returns to normal, the protector automatically restores power, ensuring continuous operation and safeguarding your appliances from damage.

This protector integrates multiple protection functions including over-voltage, under-voltage, over-current, three-phase current (voltage) imbalance, phase sequence (reverse phase), zero-break, and phase-break protection. It also features voltmeter and ammeter functions, and the ability to restore factory settings. The device offers comprehensive features, stable performance, and ease of operation.

A detailed user manual in PDF format is available for download: User Manual (PDF)

2. Key Features

  • Over-voltage protection
  • Under-voltage protection
  • Over-current protection
  • Automatic recovery
  • Voltage display (separate ABC phase voltage measurement)
  • Ampere display (separate ABC phase ampere measurement)
  • Three-phase ampere unbalance protection
  • Phase sequence protection (reverse phase protection)
  • Zero line break protection
  • Phase failure protection
  • Fault inquiry function
  • Rotation display of voltage and current for each phase
  • Adjustable over-voltage protection value and recovery value
  • Adjustable under-voltage protection value and recovery value
  • Adjustable over-current protection value and action time
  • Adjustable 3-phase ampere unbalance protection value and action time
  • Adjustable delay time after power-on
  • Adjustable fault recovery delay time
  • Factory data reset function

3. Product Specifications

AttributeValue
Model NumberSTVP936-1-80A
Power Supply3*127V/220VAC 60Hz
Rated Voltage220V
PhaseThree phase
Max. Load Current1~80A Adjustable (default: 80A)
Over-voltage Protection Range121V-150V-OFF Adjustable (default: 140V)
Over-voltage Recovery Range120V-149V (default: 135V)
Over-voltage Action Time0.1~10 seconds (default: 0.2s)
Under-voltage Protection Range118V-80V-OFF Adjustable (default: 90V)
Under-voltage Recovery Range118V-91V (default: 95V)
Under-voltage Action Time0.1~10 seconds (default: 0.2s)
3-Phase Volt Unbalance Protection10%~50%~OFF (default: 20%)
3-Phase Volt Unbalance Action Time0.1~10 seconds (default: 1s)
Delay Time After Power-on2~255 seconds (default: 2s)
Fault Recovery Delay Time2~600 seconds (default: 60s)
Display ModelLCD
Dimensions71.5mm (W) * 95.2mm (H) * 65.7mm (D)
Installation35mm DIN Rail
CertificationCE, RoHS

4. Safety Information

  • Installation and maintenance should only be performed by qualified electricians.
  • Ensure the power supply is disconnected before any installation or wiring work.
  • The device does not provide overload or short-circuit protection. It must be used in conjunction with appropriate external circuit breakers (e.g., C45, C65 mini circuit breakers) for comprehensive protection.
  • Verify all wiring connections are secure and correct before applying power.
  • Do not operate the device in wet or hazardous environments.

5. Installation

5.1 Physical Dimensions

Dimensions of the STVP936-1-80A protector, showing width 71.5mm, height 95.2mm, and depth 65.7mm.
Figure 1: Product Dimensions

5.2 Mounting

The protector is designed for 35mm DIN rail installation. Snap the device onto the DIN rail securely.

Side view of the protector showing its compatibility with a DIN rail for mounting.
Figure 2: DIN Rail Mounting

5.3 Wiring Diagram

Connect the input and output terminals as shown in the diagram below. Ensure correct phase (L1, L2, L3) and neutral (N) connections. The input terminals are located at the top, and output terminals at the bottom.

Front view of the protector with input (N, L1, L2, L3) and output (N, L1, L2, L3) terminals clearly labeled with arrows.
Figure 3: Input/Output Terminal Labels
Detailed wiring diagram showing connections from a power switch to the voltage protector (IN terminals) and from the voltage protector (OUT terminals) to an air circuit breaker.
Figure 4: General Wiring Diagram

6. Setup and Configuration

To enter the setting mode, press and hold the SET button for 3 seconds. Then, continuously press SET to cycle through the parameters. Use the and buttons to adjust the values. When "ENd" appears, press SET again to save the data and exit the setting mode.

If no operation is performed within 10 seconds after pressing SET, the device will automatically exit the setting mode, and any unsaved changes will be lost.

6.1 Parameter Settings Table

StepContentLCD DisplayDescription / Range (Default)
1Over-voltage protection valueUvo 280V221V-300V-OFF (280V)
2Over-voltage recovery valueUvor 250V220V-299V (250V)
3Over-voltage protection action time0.2S0.1-10s (0.2s)
4Under-voltage protection valueUve 160V219V-150V-OFF (160V)
5Under-voltage recovery valueUver 180V151V-220V (180V)
6Under-voltage protection action time0.2S0.1-10s (0.2s)
7Over-current protection value>In 80A1-80A (80A)
8Over-current protection action time5S1-512s (5s)
93 phases amp unbalance protection value>In %5%-90%-OFF (25%). Not active if current < 2A.
103 phases amp unbalance protection action time1.0 S0.1-10s (1s)
11Phase sequence protectionON ABCON or OFF (ON)
12Power on delay time2 S2-255s (2s)
13Fault recovery delay time60 S2-512s (60s)
14Fault inquiry codeE0Press ▲ to view last 5 fault records (E1-E5). >U for overvoltage, <U for undervoltage.
15EndingENdPress SET to save and exit.

6.2 Factory Reset

To reset the device to factory settings, press and hold the and buttons simultaneously for 3 seconds.

7. Operation

Once installed and configured, the device will continuously monitor the three-phase power supply. The LCD screen will automatically rotate to display the real-time voltage and current for each phase (L1, L2, L3).

In case of an over-voltage, under-voltage, or over-current event, the protector will automatically trip and cut off the power supply to protect connected equipment. After the fault condition clears and the recovery delay time has passed, the device will automatically restore power.

8. Troubleshooting

8.1 Fault Inquiry

If a fault occurs, the device will display an error code (E0). You can press the button to query the last 5 fault records (E1-E5). The display will indicate:

  • ">U" for overvoltage events.
  • "<U" for undervoltage events.

8.2 Phase Sequence Error

If the LCD displays "ABC" character, it indicates a phase sequence error. To correct this, arbitrarily reverse any two of the three phase lines (L1, L2, L3) at the input.

9. Maintenance

  • Keep the device clean and free from dust and moisture.
  • Regularly check wiring connections for tightness and signs of wear or damage.
  • Do not attempt to repair the device yourself. Refer to qualified personnel for service.

10. Warranty and Support

For technical support, inquiries, or warranty claims, please contact the distributor:

Distributor: XNY INTERNATIONAL LIMITED

Address: Room 20A, Kiu Fu Commercial Building, 300 Lockhart Road, Wanchai, Hong Kong.

Tel: 0086 57761733853

Fax: 0086 577 89736991

WhatsApp: 0086 1565857 3377

Wechat: sinotimer

Skype: sinotimer

Web: www.sinotimer.com

Email: info@sinotimer.com

Related Documents - STVP936-1-80A

Preview SINOTIMER SVP719 User Manual: Voltage Protector, Energy Meter, and Power Consumption Monitor
Comprehensive user manual for the SINOTIMER SVP719, detailing its features as an adjustable over/under voltage protector, surge protector, over-current limit relay, and a Watt/kWh energy meter for monitoring power consumption.
Preview SVP-916 Intelligent Over-Voltage Limit Current Protector Instruction Manual
Instruction manual for the SINOTIMER SVP-916 intelligent over-voltage, under-voltage, and over-current protector for single-phase AC 230V systems. Details features, parameters, and setting methods for electrical equipment protection.
Preview SINOTIMER WiFi Smart Switch Instruction Manual
Comprehensive instruction manual for the SINOTIMER WiFi Smart Switch, detailing network setup via the Graffiti Smart APP, device unbinding and reset procedures, indicator light status, electricity consumption display, and configuration of overvoltage, undervoltage, and overcurrent protection settings.
Preview Sinotimer MT-S PID Temperature Controller: Features, Specifications, and Setup Guide
Detailed information on the Sinotimer MT-S Intelligent PID Temperature Control Relay, including features, technical specifications, wiring diagrams, and setup instructions for PID and On-Off control modes.
Preview SINOTIMER DDS6619 Series Guide Rail Metering Switch Instruction Manual
Instruction manual for SINOTIMER DDS6619 series guide rail type metering switches. Details technical specifications, wiring, app control via Smart Life/Tuya, operating instructions, and safety precautions for smart energy monitoring.
Preview SINOTIMER TM618s Digital Programmable Timer - User Manual and Specifications
Comprehensive guide to the SINOTIMER TM618s digital programmable timer, covering features, specifications, programming, wiring, and installation. Ideal for controlling electrical devices with daily ON/OFF schedules.