1. Introduction
This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Schneider Electric TeSys Deca Contactor, model LC1D40AM7C. The TeSys Deca series is designed for motor management, offering robust control and protection solutions for various industrial applications.

2. Safety Information
Always observe the following safety precautions to prevent personal injury or damage to the equipment:
- Installation and maintenance should only be performed by qualified personnel.
- Disconnect all power sources before working on the contactor or connected equipment.
- Ensure proper grounding of the equipment.
- Use appropriate personal protective equipment (PPE).
- Verify all wiring connections are secure and correct before applying power.
- Do not operate the contactor if it appears damaged or malfunctioning.
3. Specifications
The LC1D40AM7C is a 3-pole TeSys Deca contactor designed for AC loads. Key technical specifications are detailed below:
| Feature | Specification |
|---|---|
| Product Series | TeSys Deca |
| Product Type | Contactor |
| Product Short Name | LC1D |
| Contactor Application Field | AC loads (PF ≥ 0.95), non-inductive/micro-inductive load, resistance furnace |
| Category of Use | AC-4, AC-1, AC-3, AC-3e |
| Number of Poles | 3P |
| Rated Operating Voltage [Ue] | ≤ 690 V AC 25-400 Hz, ≤ 300 V DC |
| Rated Operating Current [Ie] | 40 A (AC-3, AC-3E), 60 A (AC-1) at ≤ 440 V AC |
| Control Circuit Voltage [Uc] | 220 V AC 50/60 Hz |
| Motor Power (kW) (AC-3/AC-3E) | 11 kW (220/240V AC), 18.5 kW (380/400V AC), 22 kW (500V AC), 30 kW (660/690V AC) |
| Loop Contact Type | 3 NO |
| Conventional Heating Current [Ith] | 10 A (signal loops), 60 A (power supply circuit) |
| Rated Short-Time Withstand Current [Icw] | 320 A (40°C-10s), 720 A (40°C-1s), 72 A (40°C-10min), 165 A (40°C-1min) for power circuit; 100 A-1s, 120 A-500ms, 140 A-100ms for signal circuit |
| Fuse for Use with Relay | 10 A gG (signal loop), 80 A gG (power supply circuit) |
| Average Impedance | 1.5mΩ-Ith 60 A 50 Hz (Power supply circuit) |
| Rated Insulation Voltage [Ui] | 690 V (Power supply circuit), 690 V (Signal loop) |
| Overvoltage Class | III |
| Pollution Level | 3 |
| Rated Impulse Withstand Voltage [Uimp] | 6 kV |
| Mechanical Life | 6 Mcycles |
| Electrical Life | 1.6 Mcycles (40 A AC-3/AC-3e ≤ 440 V), 1.4 Mcycles (60 A AC-1 ≤ 440 V) |
| Control Loop Characteristic | AC 50/60 Hz |
| Surge Suppression Module | No built-in |
| Control Voltage Limit | 0.3-0.6 Uc (release), 0.8-1.1 Uc (run) |
| Power Consumption (VA) | 140 VA (60 Hz), 160 VA (50 Hz) |
| Power Consumption (VA) (Hold) | 13 VA (60 Hz), 15 VA (50 Hz) |
| Dissipation of Heat | 4-5 W |
| Action Time | 4-19 ms (disconnected), 12-26 ms (closure) |
| Maximum Operating Frequency | 3600 times/hour at ≤ 60 °C |
| Auxiliary Contact Type | 1 NO + 1 NC |
| Signal Loop Frequency | 25-400 Hz |
| Minimum Switching Current [Imin] | 5 mA for signal loop |
| Insulation Resistance | > 10 MΩ for signal loop |
| No Overlapping Time | 1.5ms power loss between NC and NO contact |
| Installation Mode | Rail mounting, Base mounting |
| Standard | GB 14048.4, IEC 60947-4-1 |
| Product Certification | CCC, CE, UKCA |
| IP Protection Level | IP2X front panel (main/coil loop) |
| Protective Measure | TH complies with IEC 60068-2-30 |
| Ambient Air Temperature | -40 to 60 °C (Operating), 60 to 70 °C (with capacity reduction), -60 to 80 °C (Storage) |
| Working Altitude | 3000 m |
| Fire Resistance | 850 °C complies with IEC 60695-2-11 |
| Shock/Vibration Resistance | Seismic (2gn open, 4gn closed), Impact (10gn open, 15gn closed) |
| Dimensions (Altitude x Breadth x Profundity) | 122 mm x 55 mm x 120 mm |
| Net Weight | 0.85 kg |
4. Installation
The TeSys Deca contactor can be installed via rail mounting or base mounting. Ensure proper clearance and ventilation around the unit.
4.1 Wiring Connections
Refer to the product labels and diagrams for correct terminal identification. The contactor features multi-standard screws for easier installation.

Wiring Capacity:
- Power Loop (EverLink BTR Terminal):
- 1-35 mm² (no terminals), 1-25 mm² (no terminals)
- 2-35 mm² (with terminals), 2-25 mm² (with terminals)
- Soft cables: 1-25 mm² (with terminals)
- Control Loop (Bolted):
- 1-2.5 mm² (no terminals), 1-2.5 mm² (with terminals)
- 1-4 mm² (no terminals)
Tightening Torque:
- Control Loop: 1.7 N.m (screwdriver Ø6 flat port or No. 2 Phillips/Pozidriv)
- Power Loop: 8 N.m (35 mm² cable, Hexagonal type 4 mm), 6 N.m (M6 screws, Hex 10 mm), 5 N.m (1-25 mm² cable, Hexagonal type 4 mm)
4.2 Video Overview
Watch this official video for an overview of the TeSys Deca series, highlighting features like multi-standard screws for easier installation and improved fire resistance.
5. Operation
The TeSys Deca contactor is primarily used for on-off control of AC loads, such as motors. When the control circuit voltage (220 V AC 50/60 Hz) is applied to terminals A1 and A2, the main contacts (L1-T1, L2-T2, L3-T3) close, allowing power to flow to the connected load. When the control voltage is removed, the contacts open, disconnecting the load.
The contactor includes auxiliary contacts (1 NO + 1 NC) for signaling or interlocking purposes within a control system.
6. Maintenance
Regular inspection and maintenance are crucial for ensuring the longevity and reliable operation of your TeSys Deca contactor.
- Visual Inspection: Periodically check for any signs of physical damage, discoloration, loose connections, or excessive dust accumulation.
- Terminal Tightness: Re-tighten terminal screws to the specified torque values if necessary, especially after initial installation and during routine checks.
- Cleaning: Keep the contactor clean and free from dust and debris. Use a dry, lint-free cloth for cleaning. Do not use solvents or abrasive cleaners.
- Contact Wear: While designed for long electrical life, inspect contacts for excessive wear or pitting during scheduled shutdowns.
- Digital Customer Portal: For detailed maintenance guides and paperless product information, scan the QR code located on the product. This provides access to up-to-date resources.
7. Troubleshooting
If the contactor is not functioning as expected, consider the following common issues:
- Contactor Fails to Energize:
- Check control circuit voltage (220 V AC).
- Verify control wiring connections (A1, A2).
- Inspect for open auxiliary contacts in the control circuit.
- Contactor Energizes but Load Does Not Operate:
- Check main power supply voltage.
- Verify power wiring connections (L1, L2, L3, T1, T2, T3).
- Inspect for open main contacts or overload conditions.
- Contactor Overheats:
- Ensure the load current does not exceed the rated operating current (40 A AC-3/AC-3e, 60 A AC-1).
- Check for proper ventilation around the contactor.
- Verify terminal connections are tight to prevent resistive heating.
- Excessive Noise/Chattering:
- Check for stable control voltage.
- Ensure the contactor is securely mounted.
If issues persist, consult a qualified electrician or refer to the detailed documentation available via the product's QR code.
8. User Tips
- The TeSys Deca series is designed for harsh environments, featuring dustproof auxiliary blocks.
- The robust design includes an improved rotary handle for enhanced durability.
- Utilize the QR code on the product for quick access to paperless product information and maintenance guides, promoting efficiency and sustainability.
9. Warranty and Support
Schneider Electric is committed to providing reliable products. In the event of product issues:
- Damaged Items: If items are damaged upon arrival, a refund may be available.
- Lost Packages: If a package is lost during transit, a refund may be available.
For further assistance, please refer to the official Schneider Electric support channels. The TeSys Deca series is part of the 'Green Premium Product' initiative, emphasizing environmental performance and sustainable development.