GE logo

GE 9T10A1004 Transformer

GE 9T10A1004 Transformer

Catalog Number

9T10A1004

  • 75.0 KVA 60 HZ
  • 40 C AMB.
  • 3 PH 4.5 % IMP
  • 220 C SYSTEM IS-19C
  • 150 C RISE

PRIMARY (H)

  • 480 VOLTS (LINE-LINE)

SECONDARY X)

  • 208 VOLTS(LINE-LINE)
  • 120 VOLTS (LINE-NEUTRAL)

JUMPER CONNECTION

TAP VOLTS

  • 1: 502
  • 2: 491
  • 3:480
  • 4: 469
  • 5: 455
  • 6:444
  • 7:433

GE 9T10A1004 Transformer 1

COIL TAP ARRANGEMENT

GE 9T10A1004 Transformer 2

ASSEMBLED IN MEXICO

  • x3
  • H3
  • x2
  • H2
  • X1
  • H1

BEFORE HANDLING, INSTALLING AND OPERATING, SEE INSTRUCTION 475A667AAPO01

  • ALUMINUM CONDUCTOR
  • PRIMARY: 10 KV BIL
  • SECONDARY: 10 KV BIL

IN ACCORDANCE WITH NEC SECTION 450-9, ALLOW AT LEAST SIX INCHES CLEARANCE FOR VENTILATION. CHECK ADDITIONAL NEC AND LOCAL CODE