KMC CONTROLS FlexStat BACnet Advanced Application Controller User Guide

KMC-CONTROLS-logo

KMC CONTROLS FlexStat BACnet Advanced Application Controller

KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-product

Overview

Use this document to facilitate FlexStat model selection according to desired applications and options. For additional specifications, see the BAC-12xxxx/13xxxx Series FlexStat Data Sheet (914-035-01). Additional award-winning resources for configuration, application, operation, program-ming, upgrading and much more are available on the KMC Controls web site (www.kmccontrols. com). To see all available files, you will need to log-in to the KMC Partners site.

Model Code

BAC-1xmhraCEW:
BAC- 1 x m h r a C E W
 

BACnet Device

 

Model Series

CO2

Sensor

Type*

 

Motion Sensor

 

Humidity Sensor

Number of Relay Outputs Number of Analog Outputs Real- Time Clock  

IP/Ethernet Communication

 

Case Color

     

2 = None

1 =

Included

1 =

Included

 

3

 

3

 

RTC

standard on all models

 

E = Included

W =

White

3 = Zones with Unoccupied Periods  

0 = None

 

0 = None

 

6

 

6

 

No E = MS/TP only

No W

= Light Almond

*In models with CO2 sensors, humidity sensors come standard.

KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (1)

Sensor Options

Temperature (Standard)KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (2)

  • Internal temp. sensor standard on all models.
  • Optional remote temperature sensor (connected to IN7) allows configuration for onboard (inter-nal), remote, averaging of the two, the lowest reading, or the highest reading.

HumidityKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (3)

  • BAC-1xx1xxC.
  • For optional dehumidification (AHU, RTU, HPU, or 4-pipe FCU) or humidification (AHU, RTU, or 4-pipe FCU).
  • Comes standard when optional CO2 sensor (BAC-13xxxxC) is ordered.

Motion/OccupancyKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (4)

  • BAC-1x1xxxC.
  • For optional occupancy standby and/or override.

CO2 with DCV (Demand Control Ventilation)KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (5)

  • BAC-12xxxxC = No internal sensor, but has built-in DCV sequences and IN9 can be config-ured for remote CO2 sensor.
  • BAC-13xxxxC = Internal sensor (with ABC Logic) for applications where concentrations will drop to outside ambient conditions at least three times in a 14 day period. The BAC-13xxxx series (only) has been certified to comply with CA Title 24, Section 121(c), as well as sub-para-graph 4.F.

NOTE: DCV is only available when using an AHU, RTU, or HPU application with a modulating economizer option enabled. For additional important information about the CO2 sensors and DCV, see the FlexStat Data Sheet and FlexStat Operation Guide!

Usage Instruction

Application Options

  • Supported AHU, FCU, HPU, and RTU options depend on whether the FlexStat is a BAC-1xxx36C (3 relays and 6 analog outputs) or a BAC-1xxx63C (6 relays and 3 analog outputs).
  • See Applications and Models.KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (6)

BACnet Network Communication Options
MS/TP (Standard)

  • Integral peer-to-peer BACnet MS/TP LAN net-work communications standard on all models, including those with Ethernet/IP option.
  • Screw terminal blocks accept twisted-pair wire size 14–22 AWG, and a data port on the under-side of the case enables easy temporary com-puter connection to the BACnet network (access with a KMD-5624 cable—requires use of KMD-5576 or third-party interface).
  • BAC-1xxxxxCE.
  • “E” versions add BACnet over Ethernet, BACnet over IP, and BACnet over IP as Foreign Device.
  • “E” versions add RJ-45 jack for Ethernet cable.
    KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (7)

Color Options

  • White (Standard)
    • BAC-1xxxxxCW.
    • Standard on all models. KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (8)
  • Light Almond
    • BAC-1xxxxxC (W removed).
    • Optional on all models. KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (9)

Applications & Models

KMC Controls FlexStat Models and Outputs

Applications and Options 6 Relays and 3 Analog Outputs 3 Relays and 6 Analog Outputs
BAC-1x0063CW BAC-1x0163CW BAC-1x1063CW BAC-1x1163CW BAC-1x0036CW BAC-1x0136CW BAC-1x1036CW BAC-1x1136CW
Packaged Unit (Air Handling Unit and Roof Top Unit)
1 Heat and 1 Cool ✓ ✓ ✓ ✓
1 or 2 Heat and 1 or 2 Cool In all BAC-1xxx63 models, but appears in RTU menu only
1 or 2 Heat and Modulating Cool ✓ ✓ ✓ ✓
Modulating Heat and 1 or 2 Cool ✓ ✓ ✓ ✓
Modulating Heat and Modulating Cool In all BAC-1xxx63 models, but appears in AHU menu only ✓ ✓ ✓ ✓
Optional Outside Air Damper, Modulating ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Optional Outside Air Damper, 2 Position In all BAC-1xxx63 models, but appears in RTU menu only ✓ ✓ ✓ ✓
Optional Fan Speed Control ✓ ✓ ✓ ✓
Optional Dehumidification (with Humidity) ✓ ✓ ✓ ✓
Optional Humidifier (with Humidity) ✓ ✓
Optional Motion/Occupancy Sensor ✓ ✓ ✓ ✓
Optional CO2 Sensor with DCV BAC-13xxxx; BAC-12xxxx has no CO2 sensor
Optional IP/Ethernet Communications Add an E to the model number: BAC-1xxxxxxCEx (see Model Code section)
FCU (Fan Coil Unit)
2 Pipe, Modulating ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
2 Pipe, 2 Position ✓ ✓ ✓ ✓
4 Pipe, Modulating ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
4 Pipe, 2 Position ✓ ✓ ✓ ✓
Optional Dehumidification (4 pipe only) ✓ ✓ ✓ ✓
Optional Humidifier (4 pipe only) ✓ ✓
Optional Fan Speed (With 3-speed fan) With 3-speed fan With 3-speed fan
Optional CO2 Sensor (DCV N/A for FCU) DCV N/A for FCU Applications (but sensor will still show CO2 levels)
HPU (Heat Pump Unit)
Compressor Support 1 or 2 compressors with auxiliary and emergency heat N/A
Optional Outside Air Damper, Modulating ✓ ✓ ✓ ✓
Optional Dehumidification ✓ ✓
Optional Motion/Occupancy Sensor ✓ ✓
Optional CO2 Sensor with DCV BAC-13xxxx; BAC-12xxxx has no CO2 sensor
Optional IP/Ethernet Communications Add an E to the model number: BAC-1xxxxxxCEx (see Model Code section)

Model Chart

Model* Outputs** Optional Sensors*** Typical Applications
BAC-12xxxx models (e.g., BAC-120036CW) are standard and do not have a CO2 sensor. BAC-13xxxx models (e.g., BAC-130036CW) have CO2 sensors to add Demand Control Ventilation to the applications below. DCV is only available when using an AHU, RTU, or HPU application with a modulating economizer option enabled.
BAC-1x0036CW 3 Relays and 6 Analog Outputs None
  • 1H/1C, fan, and 6 analog outputs
  • 3-speed fan, 2- or 4-pipe FCUs with modulating valves
  • Central station AHUs with modulating/1/2 Heat/Cool
  • Variable-speed fan output
  • Single-stage applications
BAC-1x0136CW Humidity****
  • Same as BAC-1x0036CW
  • Dehumidification sequence
  • Humidification sequence (AHU or 4-pipe FCU)
BAC-1x1036CW Motion/Occupancy
  • Same as BAC-1x0036CW
  • Occupancy-based operation
BAC-1x1136CW Humidity and Motion/Occupancy****
  • Same as BAC-1x0136CW
  • Occupancy-based operation
BAC-1x0063CW 6 Relays and 3 Analog Outputs None
  • 1 or 2 H and 1 or 2 C, fan
  • Multi-stage packaged or split systems
  • Multi-stage heat pumps with or without factory-packaged economizers
  • Central station AHUs with modulating Heat/Cool
  • 3-speed fan, 2- or 4-pipe FCUs with modulating or 2-position valves
BAC-1x0163CW Humidity****
  • Same as BAC-1x0063CW
  • Dehumidification sequence (AHU, 4-pipe FCU, or RTU)
BAC-1x1063CW Motion/Occupancy
  • Same as BAC-1x0063CW
  • Occupancy-based operation
BAC-1x1163CW Humidity and Motion/Occupancy****
  • Same as BAC-1x0163CW
  • Occupancy-based operation
  • The standard color is white. To order the optional light almond color, remove the “W” at the end of the model number (e.g., BAC-121163C instead of BAC-121163CW). To order the IP version, add an E after the C (e.g., BAC-121163CEW). All models have a real-time clock.
  • Analog outputs produce 0–12 VDC @ 20 mA maximum, and relays carry 1 A max. per relay or 1.5 A per bank of 3 relays (relays 1–3 or 4–6) @ 24 VAC/VDC.
  • All models have a 32-bit processor, an internal temperature sensor, and 6 analog inputs. All models have optional discharge air temperature monitoring/trending and fan status monitoring. Optional sensors include humidity, motion, and CO2.
  • In models with CO2 sensors, humidity sensors come standard.
  • For additional specifications, see the BAC-12xxxx/13xxxx Series FlexStat Data Sheet (914-035-01).
  • NOTE: For specifications on the older BAC-10000 Series FlexStats (with only three external inputs and no Ethernet or CO2 options), see the data sheet (913- 035-01) for that series.
  • FlexStats come with a printed Installation Guide. Additional award-winning resources for configuration, application, operation, programming, upgrading, and much more are available on the KMC Controls web site (www.kmccontrols.com). To see all available files, you will need to log-in to the KMC Partners site.KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (10)

Accessories

Damper (OAD/RTD) Actuators (Fail-Safe)

  • MEP-7552: 22.5 ft2 max. damper area, 180 in-lb., 0–10 VDC, 25 VA
  • MEP-7852: 40 ft2 max. damper area, 320 in-lb., 0–10 VDC, 40 VAKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (18)

Mounting Hardware

  • HMO-10000: Horizontal or 4 x 4 handy box wall mounting plate for BAC-12xxxx models (not needed for BAC-13xxxx models), light almond (shown)
  • HMO-10000W: HMO-10000 in white

KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (11)

  • SP-001: Screwdriver (KMC branded) with flat blade (for termi-nals) and hex end (for cover screws)

Network Communications and Firmware

  • HTO-1104: FlexStat firmware upgrade kitKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (12)
  • KMD-5567 : Network surge suppressorKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (13)
  • KMD-5575: Network repeater/ isolatorKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (14)
  • KMD-5624: PC data port (EIA-485) cable (FlexStat to USB Communica-tor)—included with the KMD-5576 (buy for third-party EIA-232 interfaces)KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (15)

Relays (External)

  • REE-3112: (HUM) SPDT, 12/24 VDC con-trol relay

Sensors (External)

  • CSE-110x: (FST) differential air pressure switch
  • STE-1402: (DAT) duct tempera-ture sensor with 8-inch rigid probeKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (17)
  • STE-1416: (MAT) flexible 12-foot duct averaging temp. sensor
  • STE-1451: (OAT) outside air temp. sensor
  • STE-6011: Remote space temp. sensor
  • SAE-10xx: Remote CO2 sensor, space or ductKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (16)
  • STE-1454/1455: (W-TMP) 2-inch strap-on water temp. sensor (with or without enclosure)

Transformers, 120 (or more) to 24 VAC (TX)

  • XEE-6111-040: 40 VA, single-hub
  • XEE-6112-040: 40 VA, dual-hub
  • XEE-6311-050: 50 VA, dual-hub
  • XEE-6311-075: 75 VA, single-hub
  • XEE-6311-100: 96 VA, dual-hubKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (20)

Valves (Heating/Cooling/Humidification)

  • VEB-43xxxBCL: (HUMV/CLV/HTV) Fail-safe control valve, w/ MEP-4×52 proportional actuator, 20 VA
  • VEB-43xxxBCK: (VLV/CLV/HTV) control valve w/ MEP-4002 proportional actuator, 4 VAKMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (21)
  • VEZ-4xxxxMBx:(VLV/CLV/HTV) fail-safe control valve, 24 VAC, 9.8 VA

NOTE: For details, see the respective product data sheets and installation guides. See also the FlexStat Application Guide.

Troubleshooting

  • DCV not operating as expected: Verify the system configuration meets the documented requirement: DCV is only available with an AHU, RTU, or HPU application that has a modulating economizer option enabled.
  • CO2/DCV sensor behavior mismatch: For BAC-13xxxx models, CO2 is an internal sensor using ABC Logic; for BAC-12xxxx models, CO2 uses built-in DCV sequences with IN9 configurable for a remote CO2 sensor.
  • Humidity sensor missing when CO2 is used: If the model has a CO2 sensor (BAC-13xxxx), humidity sensors come standard in those models.
  • Network connection issues (MS/TP): Ensure twisted-pair wire is 14–22 AWG on the MS/TP screw terminal blocks.
  • Ethernet/IP not present: Confirm the model includes the “E” option (E versions add BACnet over Ethernet/IP and add an RJ-45 jack).

Support

To Order:

  • Telephone: 877.444.5622 (574.831.5250)
  • Fax: 574.831.5252
    KMC-CONTROLS-FlexStat-BACnet-Advanced-Application-Controller-fig (22)

Documents / Resources

PDF thumbnailFlexStat BACnet Advanced Application Controller
User Guide · FlexStat BACnet Advanced Application Controller, FlexStat, BACnet Advanced Application Controller, Advanced Application Controller, Application Controller

Ask a Question

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Ask a Question

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.