Note: Rockwell PLC5 driver uses CRC checksum.

HMI SETTING

Parameters Recommended Options Notes
PLC type Rockwell PLC5
PLC I/F RS232
Baud rate 19200 9600, 19200
Data bits 8 8
Parity Even Even, Odd, None
Stop bits 1 1
HMI sta. no. 0
PLC sta. no. 1 1-31

PLC SETTING

Communication mode DF1 Full Duplex protocol 19200, None, 8, 1 (default)

Allen-Bradley PLC-5 Family PLCs use DF1 Full Duplex protocol.
For PLC-5/10, PLC-5/15 and PLC-5/25, MT8000 should be connected to the DF1 port on the 1785-KE module.
For PLC-5/11, PLC-5/20, PLC-5/30 and PLC-5/40, MT8000 should be connected to the Channel 0 Port on the PLC.

DEVICE ADDRESS

Bit/Word Device Format Range Memo
B I1 DDDdd 0 ~ 25515 Input (I)
B O0 DDDdd 0 ~ 25515 Output (O)
B B3 DDDdd 0 ~ 99915 Bit data file (B3)
B B10 ~ 13 DDDdd 0 ~ 99915 Bit data file (B10 ~ 13)
B S_Bit DDDDDDdd 0 ~ 25599915
B Bfn FFFDDDdd 0 ~ 25599915
B NfnBit FFFDDDdd 0 ~ 25599915
W T4PV DDD 0 ~ 999 Timer Preset Value (T4)
W T4PV DDD 0 ~ 999 Timer Accumulator Value (T4)
Bit/Word Device Format Range Memo
W C5sV DDD 0 ~ 999 Counter Preset Value (C5)
W C5PV DDD 0 ~ 999 Counter Accumulator Value (C5)
W TfnSV FFFDDD 0 ~ 255999
W TfnPV FFFDDD 0 ~ 255999
W CfnSV FFFDDD 0 ~ 255999
W CfnPV FFFDDD 0 ~ 255999
W N7 DDD 0 ~ 999 Integer data file (N7)
W N10 ~ 15 DDD 0 ~ 999 Integer data file (N10 ~ 15)
W Nfn FFFDDD 0 ~ 255999 Integer data file (V2.5.0 or newer)
W S DDD 0 ~ 255
W F8 DDD 0 ~ 999 Floating point data file (F8)
W Ffn FFFDDD 0 ~ 255999 Floating point data file (V2.5.0 or newer)

WIRING DIAGRAM

Diagram 1

RS-232 (9P D-Sub to 25P D-Sub: PLC5 CPU CH0)
The serial port pin assignments may vary between HMI models, please click the following link for more information.

Wiring Diagram

IMPORT TAGS

Note:

The default error checking of Rockwell PLC5 is BCC, whereas our driver is CRC.

Import Tags

Access [Channel Configuration] from RSLogix5, under Channel 0 tab, please select “CRC” for [Error Detect].

Import Tags

CUSTOMER SUPPORT

Website: https://www.rockwellautomation.com/

Logo

Documents / Resources

WEINTEK PLC5 Ethernet Compatible [pdf] User Guide
PLC-5-10, PLC-5-15, PLC-5-25, PLC-5-11, PLC-5-20, PLC-5-30, PLC-5-40, PLC5 Ethernet Compatible, PLC5, Ethernet Compatible, Compatible

References

Leave a comment

Your email address will not be published. Required fields are marked *