Rockwell PLC5
Rockwell PLC5
Website: https://www.rockwellautomation.com/ Note: Rockwell PLC5 driver uses CRC checksum.

PLC Connection Guide

HMI Setting:

Parameters PLC type PLC I/F Baud rate Data bits Parity Stop bits HMI sta. no. PLC sta. no.

Recommended Rockwell PLC5 RS232 19200 8 Even 1 0 1

Options

Notes

9600, 19200 8 Even, Odd, None 1
1-31

PLC Setting:
Communication mode

DF1 Full Duplex protocol 19200, None, 8, 1 (default)

Allen-Bradley PLC-5 Family PLCs use DF1 Full Duplex protocol. For PLC-5/10, PLC-5/15 and PLC-5/25, MT8000 should be connected to the DF1 port on the 1785-KE module. For PLC-5/11, PLC-5/20, PLC-5/30 and PLC-5/40, MT8000 should be connected to the Channel 0 Port on the PLC.

Device Address:

Bit/Word Device

B

I1

B

O0

B

B3

B

B10 ~ 13

B

S_Bit

B

Bfn

B

NfnBit

W

T4SV

W

T4PV

Format

Range

DDDdd

0 ~ 25515

DDDdd

0 ~ 25515

DDDdd

0 ~ 99915

DDDdd

0 ~ 99915

DDDDDDdd 0 ~ 25599915

FFFDDDdd 0 ~ 25599915

FFFDDDdd 0 ~ 25599915

DDD

0 ~ 999

DDD

0 ~ 999

Memo
Input (I) Output (O) Bit data file (B3) Bit data file (B10 ~ 13)
Timer Preset Value (T4) Timer Accumulator Value (T4)

Bit/Word Device

W

C5SV

W

C5PV

W

TfnSV

W

TfnPV

W

CfnSV

W

CfnPV

W

N7

W

N10 ~ 15

W

Nfn

W

S

W

F8

W

Ffn

Format DDD DDD FFFDDD FFFDDD FFFDDD FFFDDD DDD DDD FFFDDD DDD DDD
FFFDDD

Range 0 ~ 999 0 ~ 999 0 ~ 255999 0 ~ 255999 0 ~ 255999 0 ~ 255999 0 ~ 999 0 ~ 999 0 ~ 255999 0 ~ 255 0 ~ 999
0 ~ 255999

Memo

PLC Connection Guide

Counter Preset Value (C5)

Counter Accumulator Value (C5)

Integer data file (N7) Integer data file (N10 ~ 15) Integer data file (V2.5.0 or newer)
Floating point data file (F8) Floating point data file (V2.5.0 or newer)

Wiring Diagram:

Diagram 1
RS-232 (9P D-Sub to 25P D-Sub: PLC5 CPU CH0) The serial port pin assignments may vary between HMI models, please click the following link for more information.

HMI

PLC

Link

AB CPU CH0 RS232 25P D-Sub Male

Rx

2

Tx

3

GND

7

Note:

PLC Connection Guide

The default error checking of Rockwell PLC5 is BCC, whereas our driver is CRC.

Access [Channel Configuration] from RSLogix5, under Channel 0 tab, please select "CRC" for [Error Detect].

