TOSHIBA-logo

TOSHIBA AS3 Application

TOSHIBA-AS3-Application

Sleep Function (Non-PID control)
How to program and operate AS3 with the sleep function

Estimated Time: 15 Minutes
Level: 2

Prerequisite:
AS3 Application Note 1.1.1
Navigating Menus & Parameters

Connections

STEP A
The sleep function on the VFAS3 is used for energy saving and elongating the lifespan of the motor. This function puts the drive to sleep when there is no demand for mass flow, which would decrease the run time for the motor and prolong the lifespan.
Sleep function over a run cycle per respective diagram below.

TOSHIBA-AS3-Application-1

Check Your Work
Verify VFAS3 operates under normal condition before programming Sleep function.
Note: Refer to Section 6.9 in the AS3 Instruction Manual (E6582062) for additional information on the Sleep function.

Explanation

STEP B
The Sleep function will automatically decelerate and bring the drive to a stop when condition programmed have been met.
The drive’s Sleep function begins once the output frequency is at the <LL: Lower Limit frequency> programmed.

The drive must continue to run at the <LL: Lower Limit frequency> for the specified time programmed in the <F256: Run Sleep detection time> parameter prior to the drive’s sleep cycle.
Once the drive has met these condition, the screen will display “LStP” during the sleep cycle.

You can also enable a feature with the Sleep function that will automatically stop the drive after a time period programmed in <F259: Run Sleep detection time at start-up> if the output frequency does not increase past the <LL: Lower Limit frequency> due to load error.

This function is cancelled when the frequency command value is over the values of the <LL: Lower Limit frequency> and the <F391: Sleep detection hysteresis> or when the run command is turned OFF.

Check Your Work
Check your understanding of the condition required to enable or disable the Sleep function.

Programming

STEP C

Program the Lower Limit Frequency.
The lower limit frequency will determine the frequency at which the drive will go to sleep.

Parameter Description Default Value New Value
 

F013

LL: Lower Limit Fre- quency  

0.0

 

Choose New LL Value

Program the Sleep detection time.
The drive will need to run at the lower limit for the set period of time to go into a sleep state.

Parameter Description Default Value New Value
 

F256

 

Sleep Detection Time

 

0.0

 

Choose New Value

(If applicable) Program the Sleep detection hysteresis. This will be the threshold value that will awake the drive from the sleep cycle.

Parameter Description Default Value New Value
 

F391

Sleep Detection Hyste- resis  

0.0

 

Choose New Value

(If applicable) Program the Sleep detection time at startup. This will automatically stop the drive upon start-up if there is a load issue preventing the drive to ramp past the lower limit frequency.

Parameter Description Default Value New Value
 

F259

Sleep Detection Time at Start-up  

0.0

 

Choose New Value

Check Your Work
Verify parameter change was made by verifying new value programmed.

Verification

STEP D
Program the following below.

Parameter Description Default Value New Value
 

F013

LL: Lower Limit Fre- quency  

0.0

 

20.0 Hz

Parameter Description Default Value New Value
 

F256

 

Sleep Detection Time

 

0.0

 

5.0 s

Parameter Description Default Value New Value
F391 Sleep Detection Hysteresis 0.0  

5.0 Hz

Start at the main operation screen below and follow the steps as shown.

TOSHIBA-AS3-Application-2

TOSHIBA-AS3-Application-3

Documents / Resources

TOSHIBA AS3 Application [pdf] Owner's Manual
AS3 Application, AS3, Application

References

Leave a comment

Your email address will not be published. Required fields are marked *