systemair CAV Integrated Sensor Control Module

Specifications
- Model: Quick Guide CAV kit
- Manufacturer: Puravent
- Service Password: Default 1111
- Address: Puravent, Adremit Limited, 6 County Business Park, Darlington Road, Northallerton, DL6 2NQ
Installation
Step 1
Step 2
Step 3
- A — yellow,
- B — red,
- C — gray,
- D — blue
Configuration
- Activate the accessory
- Service > Enter Service Password (default 1111) > Input > Universal > Pressure Card 1 > Enabled.
- Stop the fans
- Service > Output > SAF OUTPUT > Value Type > Manual > Value > 0 % (remember original value, it will have be to restored after calibration).
- Service > Output > EAF OUTPUT > Value Type > Manual > Value > 0 % (remember original value, it will have be to restored after calibration).
- Calibrate the accessory
- Service > Input > UNIVERSAL > Pressure Card 1. Increase or decrease the sensor correction value to make the SAF Value and EAF Value equal to 0 Pa.
- Start the fans
- Restore SAF OUTPUT and EAF OUTPUT values to the original values.
- Change the airflow type and set new airflow levels
- Service > Control Regulation > Fan Control > Airflow Type > Flow > Airflow Levels Settings.
Systemair UAB Linų st.
101, LT–20174 Ukmergė, LITHUANIA
Phone: +370 340 60165
Fax: +370 340 60166
Get In Touch
Call: 01729 824108
Email: info@puravent.co.uk
Our Address
Puravent, Adremit Limited, 6 County Business Park, Darlington Road, Northallerton, DL6 2NQ
FAQs
Q: What should I do if the SAF Value and EAF Value are not equal to 0 Pa after calibration?
A: If the values are not equal, re-adjust the sensor correction value until both SAF Value and EAF Value are at 0 Pa.
Q: How can I contact customer support for further assistance?
A: You can reach us by calling 01729 824108 or emailing info@puravent.co.uk.