Cerberus Pyrotronics CE-S IXL Control Element Module - Technical Specifications

Cerberus Pyrotronics

CE-S IXL Control Element Module

ENGINEER AND ARCHITECT SPECIFICATIONS

  • Form C Relay Contacts
  • Field Programmable
  • Requires No DIP Switch Programming
  • Solid LED to Indicate Activation
  • Screw Terminals Provided
  • UL, ULC Listed, FM, CSFM and NYMEA Approved

Description

The CE-S Addressable Control Element provides a set of Form C relay contacts and addressable electronics, enabling its use on the IXL System's Network Communication Lines. An optional trim plate, model FR5, is available for flush mounting. Each control element features an LED for indicating normal monitoring status or alarm activation.

Engineer and Architect Specifications

A control element shall be provided as model CE-S. This device shall connect to the Network Communication Lines and be field programmable for one of the following options: Remote Relay (Form C, 1 Amp. 24 VDC, 200mA 120 VAC) with supervised relay operation, or Remote Signal/Audio Circuit (1 Amp.). The device shall include an LED that flashes to indicate the unit is being monitored and remains steady to indicate the unit has been activated.

Operation

The CE-S Control Element connects directly to the system's Network Communication Line using either NFPA Standard 72, Style 6 (Class A) or NFPA Standard 72 Style 4 (Class B) wiring configuration. In the quiescent mode, the addressable electronics monitor the unit's internal operational status. The Control Element in its quiescent mode will flash a red LED to indicate that the monitored device is active and functional. In this state, the Form C contacts are de-energized. When an alarm occurs, the system program causes the associated Control Element to activate, energizing its relay. The relay remains energized as long as the Control Element is activated. The LED on the cover plate will remain lit continuously to indicate activation.

Trouble Reporting

The Control Element will report a Trouble condition whenever there is a break in the external wiring, internal circuitry fails, or if there is a Network Communication Line Break.

Programming

Programming of Control Elements must be performed when a new unit is installed. To program a Control Element, the control panel must be placed in programming mode. The address will be assigned to the Control Element that has the Programming Tool applied to it. The CE-S must have an EOL device in place to program if it is configured as a remote signal circuit. Refer to the IXL Programming Manual for CE-S and system configuration programming details.

Installation

CE-S Control Element(s) should be installed in accessible locations for maintenance purposes. They should be mounted (surface or flush) in visible locations so that their status LED may be seen for quick and easy verification.

Wiring Diagram

The wiring diagram illustrates connections from the IXL Control Panel to the CE-S module. It shows terminals labeled R, DATA, E, -V, and +24, with numbered connections 1, 2, 3, and 4. The diagram also indicates the path for 'TO NEXT DEVICE OR RETURN FOR CLASS A (STYLE 6)' and a 'SEE DETAILS' callout.

Diagram 1 depicts the Form C relay contacts, with terminals labeled NO (Normally Open), C (Common), and NC (Normally Closed).

Diagram 2 illustrates the Audio Circuit, suitable for UL Listed Audio Panels, Speaker Circuits, or UL Auxiliary VOC Power Supplies for Fire Protection Signalling. It includes a polarized indicating device and an End of Line (EOL) resistor (10K 1/2W).

Mechanical and Environmental Specifications

Parameter Value
Operating Temperature 0°C to 49°C
Relative Humidity 93%, non-condensing
Input Current 1.5mA (deactivated)
10mA (relay activated)
Operating Voltage 24 VDC (from Network Communication Line)
Contact Rating 1 Amp. at 30 VDC
0.2 Amp. at 120 VAC
Relay Type Form C Contact
Control Element Housing Standard electrical box
Dimensions (Module) 4 11/16" x 4 11/16" x 2"
Flush Ring Dimensions 4 3/4" x 4 3/4" x 1 5/8"
5 3/4" x 5 3/4" x 1/2"

Ordering Information

Supplied Quantity Part Number Description
CE-S Surface Mount Control Element
FR5 Flush Trim Ring
MAG Programming Tool

Notes

  • Use 18 AWG minimum wire.
  • Limit the maximum ohms per pair to 80.
  • Use shielded twisted pair.
  • End the shield ONLY at the MMB-1 enclosure.
Models: CE-S IXL Control Element Module, CE-S IXL, Control Element Module, Element Module

File Info : application/pdf, 2 Pages, 949.38KB

?tmstv=1676733018

References

Acrobat PDFWriter 3.0 for Windows

Related Documents

Preview Cerberus Pyrotronics RemCon IXL Remote Control Module Specifications
Technical specifications and overview of the Cerberus Pyrotronics RemCon module for the IXL fire alarm system, detailing its features, installation, programming, and ordering information.
Preview Cerberus Pyrotronics System 3 Supplementary Relay Model SR-35 Specifications
Technical specifications, features, and ordering information for the Cerberus Pyrotronics System 3 Supplementary Relay Model SR-35. Details include 8 relays, 2A SPDT contacts, input activation modes, electrical requirements, and agency approvals.
Preview Cerberus Pyrotronics MSI-10B & MSI-20B Intelligent Manual Fire Alarm Boxes - Technical Specifications
Detailed technical specifications, features, and ordering information for Cerberus Pyrotronics MSI-10B and MSI-20B intelligent manual fire alarm boxes, designed for MXL and XL3 control panels.
Preview Cerberus Pyrotronics RR-35 System 3 Remote Reset Device - Technical Specifications & Wiring Diagram
Technical specifications and product overview for the Cerberus Pyrotronics RR-35 System 3 Remote Reset Device. Includes features, detailed description, ordering information, and wiring diagram for fire alarm system integration.
Preview Cerberus Pyrotronics TSP-40 Thermal Strip Printer: Specifications and Installation Guide
Detailed specifications, features, and electrical installation instructions for the Cerberus Pyrotronics TSP-40 Thermal Strip Printer, a key component for event logging and system status reporting in MXL fire alarm systems.
Preview Cerberus Pyrotronics DI-4A Ionization Smoke Detector - Technical Specifications and Features
Detailed technical specifications, features, application data, and ordering information for the Cerberus Pyrotronics DI-4A Ionization Smoke Detector. Learn about its dual-chamber ionization technology, adjustable sensitivity, and base mounting options.
Preview Cerberus Pyrotronics FM-200™ Extinguishing Systems: Engineer and Architect Specifications
Detailed technical specifications for the Cerberus Pyrotronics FM-200™ Automatic Pre-Engineered Modular Type Extinguishing Systems, covering general requirements, cylinder details, valve specifications, nozzle requirements, piping, control equipment, system checkout, and warranty information.
Preview Cerberus Pyrotronics U-MMT Series 8-Tone Horn and Horn/Strobe Devices
Detailed specifications and ordering information for the Cerberus Pyrotronics U-MMT Series of 8-tone horns and horn/strobe notification devices, designed for fire alarm systems. Features include universal mounting, low inrush current, multiple tone selections, and ADA/UL 1971 compliance for horn-strobe models.