1. Bubuka
This manual provides comprehensive instructions for the installation, operation, and maintenance of the Acrel DTSD1352 Three Phase Bidirectional Energy Meter. This device is designed for accurate measurement of three-phase energy consumption and generation, featuring RS485 communication for integration into monitoring systems. Please read this manual thoroughly before installation and operation to ensure safe and efficient use.
2. Émbaran Kasalametan
PERHATOSAN: Résiko Setrum Listrik!
- Pamasangan sareng pangropéa ngan ukur kedah dilakukeun ku tukang listrik anu mumpuni.
- Ensure all power is disconnected before installing or servicing the meter.
- Do not touch live terminals.
- Verify correct wiring connections to prevent damage to the meter or electrical system.
- The meter must be installed in a dry, well-ventilated area, free from excessive dust, corrosive gases, and direct sunlight.
3. Produk Langkungview
The Acrel DTSD1352 is a compact and robust three-phase multi-function energy meter. It features a clear LCD display for real-time data, intuitive control buttons, and various connection terminals.

Gambar 3.1: Hareupeun view of the DTSD1352 meter. This image displays the main LCD screen showing power readings (e.g., 0.00 kW), the "SET" button, and three orange arrow buttons for navigation. Terminal blocks are visible at the top and bottom for electrical connections.

Gambar 3.2: Angled view of the DTSD1352 meter. This perspective highlights the compact design and the various input/output terminals on the top and bottom, as well as the side labeling for model identification.
4. Spésifikasi
The following table outlines the key technical specifications of the Acrel DTSD1352 energy meter. For detailed information, refer to the product datasheet.

Gambar 4.1: Detailed technical specifications. This image presents a table covering various parameters such as reference voltage (3*57.7/100V, 3*220/380V, 3*380V), reference frequency (50Hz), maximum current (6A, 80A), accuracy (Class 0.5S), communication interface (RS485, MODBUS-RTU), dimensions (127*88*70 mm), and environmental conditions (operating temperature -25~55℃, humidity ≤95%).
| Parameter | Nilai |
|---|---|
| Rujukan Voltage | 3*57.7/100V, 3*220/380V, 3*380V |
| Frékuénsi Rujukan | 50Hz |
| Arus maksimum | 6A, 80A (depending on model) |
| Accuracy of active kWh | Kelas 0.5S |
| Antarbeungeut Komunikasi | RS485 |
| Protokol Komunikasi | MODBUS-RTU |
| Ukuran (L * W * H) | 127mm * 88mm * 70mm |
| Suhu Operasi | -25 ℃ nepi ka 55 ℃ |
| Suhu Panyimpenan | -40 ℃ nepi ka 70 ℃ |
| Kalembaban | ≤95% (Euweuh kondensasi) |
| Luhurna | <2000m |
| Item Beurat | 7.1 ons (kira-kira 200g) |
5. Instalasi jeung Wiring
Proper installation and wiring are critical for the accurate and safe operation of the DTSD1352 meter. Refer to the diagrams below for connection methods.

Gambar 5.1: Wiring diagrams. This image illustrates two primary wiring methods: a 3-phase 4-wire (3P4W) direct connection where power lines (A, B, C, N) connect directly to the meter, and a connection via Current Transformers (CTs) for higher current applications, showing the CTs connected to the respective phase lines and then to the meter.
5.1 Direct Connection (3P4W)
For direct connection, ensure the phase lines (A, B, C) and neutral (N) are connected to the corresponding terminals on the meter. This method is typically used for lower current applications where the meter can directly handle the load current.
- Connect Phase A to terminal 'A'.
- Connect Phase B to terminal 'B'.
- Connect Phase C to terminal 'C'.
- Connect Neutral to terminal 'N'.
- Pastikeun sadaya sambungan aman sareng insulated leres.
5.2 Connection via Current Transformers (CTs)
For higher current applications, the DTSD1352 meter can be connected via external Current Transformers (CTs). This method scales down the current to a measurable level for the meter.
- Install the CTs on each phase line (A, B, C).
- Connect the secondary windings of the CTs to the corresponding current input terminals (e.g., Ia*, Ia, Ib*, Ib, Ic*, Ic) on the meter.
- Ensure the polarity of the CTs is correct (P1/K to the source side, P2/L to the load side, and S1/S2 to the meter). Incorrect polarity will result in inaccurate readings.
- Sambungkeun voltage inputs (Ua, Ub, Uc, N) directly from the respective phases and neutral to the meter.
- It is recommended to install a fuse on the voltage input lines for protection.
Important: Always ensure the CT secondary circuit is closed before applying power to the primary circuit. Never open the secondary circuit of a live CT.
6. Operasi
Once installed and powered, the DTSD1352 meter will automatically begin measuring. The LCD display shows various parameters, which can be navigated using the control buttons.
6.1 Pintonan Napigasi
- Layar LCD: Shows real-time measurements such as voltage, current, active power, reactive power, power factor, frequency, and total energy (kWh).
- "SET" Button: Used to enter the parameter setting mode or confirm selections.
- Arrow Buttons (Left, Right, Up, Down): Used to navigate through different display screens or adjust parameter values in setting mode.
6.2 Reading Energy Data
Press the arrow buttons to cycle through the various measurement screens. Common readings include:
- Total Active Energy (kWh)
- Forward Active Energy (kWh)
- Reverse Active Energy (kWh)
- Voltage (V) per phase
- Current (A) per phase
- Active Power (kW) per phase and total
- Reactive Power (kVar) per phase and total
- Faktor Kakuatan (PF)
- Frékuénsi (Hz)
6.3 RS485 Komunikasi
The meter supports RS485 communication with MODBUS-RTU protocol. This allows for remote reading of meter data and configuration. Refer to the MODBUS communication protocol document for detailed register addresses and commands.
7. Pangropéa
The DTSD1352 energy meter is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.
- beberesih: Jaga méter tetep bersih sareng bébas tina lebu. Anggo lawon anu lemes sareng garing pikeun ngabersihkeun. Entong nganggo pembersih atanapi pangleyur anu abrasif.
- Sambungan: Periodically check all wiring connections to ensure they are tight and secure. Loose connections can lead to inaccurate readings or overheating.
- Lingkungan: Pastikeun lingkungan operasi tetep dina kisaran suhu sareng kalembaban anu ditangtukeun.
- Kalibrasi: The meter is factory calibrated. If you suspect inaccuracies, contact qualified service personnel for recalibration.
8. Cara ngungkulan
This section provides solutions to common issues you might encounter with the DTSD1352 meter.
| Masalah | Mungkin Cukang lantaranana | Solusi |
|---|---|---|
| Layar méterna kosong. | Teu aya catu daya ka méterna. | Check the main power supply and wiring connections to the meter's voltage input terminals. Ensure fuses are intact. |
| Pamacaan énergi anu teu akurat. | Incorrect wiring, incorrect CT ratio setting (if applicable), faulty CTs, or meter malfunction. | Verify all wiring connections according to Section 5. Ensure CT polarity is correct. Check if the CT ratio programmed in the meter matches the physical CTs. If issues persist, contact technical support. |
| gagalna komunikasi RS485. | Incorrect wiring of RS485 terminals (A/B), incorrect communication parameters (baud rate, parity, address), or software issue. | Check RS485 A and B terminal connections. Verify communication settings (baud rate, data bits, stop bits, parity, meter address) in your master device match the meter's settings. Ensure proper termination resistors are used if necessary. |
| Meter shows "Error" or specific error codes. | Internal fault or specific operational issue. | Note down the error code and consult the full product manual or contact technical support for specific error code interpretations and solutions. |
9. Garansi jeung Rojongan
This product is manufactured by TGLGTQPX and sold under the Acrel brand. For specific warranty terms and conditions, please refer to the documentation provided at the time of purchase or contact your vendor. General support for the Acrel DTSD1352 meter can be obtained through the manufacturer's official channels or your authorized distributor.
For technical assistance, troubleshooting beyond this manual, or spare parts, please contact:
- Pabrikan: TGLGTQPX
- Merk produk: Acrel
- model: DTSD1352
- (Contact information such as website or email would typically be provided here by the manufacturer.)