1. Bubuka
This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Chatsworth P5-1C0A5 Switched Vertical eConnect Power Distribution Unit (PDU). Please read this manual thoroughly before using the product and retain it for future reference.
2. Émbaran Kasalametan
Observe the following safety precautions to prevent injury and damage to the PDU or connected equipment:
- Ensure the PDU is installed by qualified personnel in accordance with all local and national electrical codes.
- Do not open the PDU enclosure. There are no user-serviceable parts inside.
- Connect the PDU only to a properly grounded power source.
- Do not overload the PDU. The total current draw of connected devices must not exceed the PDU's rated capacity (20A).
- Operate the PDU within its specified environmental conditions, including the maximum ambient temperature of 149°F (65°C).
- Cabut daya sateuacan ngalaksanakeun prosedur pangropéa atanapi pamasangan naon waé.
3. Produk Langkungview
The Chatsworth P5-1C0A5 is a Switched Vertical eConnect PDU designed for efficient power distribution and remote management in data center environments. It features 24 individually switched 5-20R outlets, a graphical local display, and comprehensive network monitoring capabilities.

Gambar 1: Leuwihview of the Chatsworth P5-1C0A5 PDU. This image displays the vertical PDU with its numerous 5-20R outlets, labeled circuit breakers (CB1, CB2, CB3), and the integrated control panel featuring a graphical display, navigation buttons, Ethernet ports, and a USB port.
Komponén konci:
- L5-20 Input Plug: For connecting the PDU to the main power source.
- Circuit Breakers (CB1, CB2, CB3): Provide overcurrent protection for groups of outlets. Each breaker has an ON/OFF switch.
- 5-20R Outlets: Twenty-four (24) individually switched outlets for connecting IT equipment.
- Graphical Local Display: Provides real-time power monitoring, configuration, and status information directly on the unit.
- Port Ethernet: For network connectivity, enabling IP-based remote monitoring and management.
- Port USB: Used for firmware updates and configuration backups.
- Palabuhan Serial: For direct console access and management.
4. Setélan
4.1 Pamasangan
The P5-1C0A5 is a vertical PDU designed for tool-less mounting in standard server racks. Ensure the rack has appropriate mounting points and sufficient space for the PDU and its connected cables. Refer to your rack's documentation for specific mounting instructions.
4.2 Sambungan Daya
- Ensure all circuit breakers on the PDU are in the OFF position.
- Connect the PDU's L5-20 input plug to a dedicated 1-Phase, 110-125V, 20A power circuit.
- Verify the power source is properly grounded.
4.3 Parabot Nyambungkeun
- With the PDU still powered off (breakers OFF), connect your IT equipment power cords to the 5-20R outlets on the PDU.
- Distribute the load evenly across the PDU's outlets and circuit breaker groups to prevent overloading any single breaker.
4.4 Sambungan Jaringan
For remote monitoring and management, connect an Ethernet cable from your network switch to one of the Ethernet ports on the PDU's control panel. Refer to the PDU's network configuration guide for initial setup of IP addresses and network settings.
5. Nyuping
5.1 Powering on / Pareum
- After connecting all equipment, switch the main circuit breakers (CB1, CB2, CB3) on the PDU to the ON position.
- The graphical local display will illuminate, indicating the PDU is operational.
- Individual outlets can be switched ON or OFF via the local display interface or remotely through the network interface.
5.2 Operasi Tampilan Lokal
Use the navigation buttons adjacent to the graphical display to browse through menus, view real-time power metrics (voltage, current, power, energy), and configure basic settings. Consult the detailed eConnect PDU user guide for comprehensive local display functionality.
5.3 Pemantauan sareng Manajemén Jarak Jauh
Access the PDU's web interface via its assigned IP address to perform advanced monitoring, configuration, and control. This includes:
- Real-time power monitoring of the entire PDU and individual outlets.
- Individual outlet switching and sequencing.
- Setting up alerts and notifications for power events.
- User management and security settings.
The PDU also supports serial monitoring for direct console access.
6. Pangropéa
6.1 beberesih
Periodically clean the exterior of the PDU with a soft, dry cloth. Do not use liquid cleaners or solvents. Ensure the PDU is powered off and disconnected from the power source before cleaning.
6.2 Apdet firmware
Chatsworth may release firmware updates to improve performance or add new features. These updates can typically be applied via the USB port or through the network interface. Refer to the Chatsworth support websitus kanggo parentah firmware sareng apdet panganyarna.
6.3 Pertimbangan Lingkungan
The PDU is designed to operate in high ambient temperatures up to 149°F (65°C). Ensure proper airflow around the unit to prevent overheating. Regularly check the operating environment to ensure it remains within specified limits.
7. Cara ngungkulan
7.1 No Power to Outlets
- Verify the main L5-20 input plug is securely connected to a live power source.
- Check if the PDU's circuit breakers (CB1, CB2, CB3) are in the ON position. If a breaker has tripped, switch it OFF, wait a few seconds, and then switch it back ON. If it trips again, reduce the load on that breaker.
- Confirm that individual outlets are switched ON via the local display or remote interface.
7.2 Masalah Konektipitas Jaringan
- Ensure the Ethernet cable is securely connected to both the PDU and the network switch.
- Verify network settings (IP address, subnet mask, gateway) on the PDU are correct.
- Check network switch port status and connectivity.
7.3 Breaker Trips Repeatedly
A repeatedly tripping breaker indicates an overload condition. Reduce the total current draw of devices connected to that breaker's group of outlets. If the issue persists with a reduced load, contact technical support.
8. Spésifikasi
| Fitur | Spésifikasi |
|---|---|
| Nomer modél | P5-1C0A5 |
| merek | Chatsworth |
| Input Colokkeun | L5-20 |
| Masukan Voltage | 1-Phase, 110-125V |
| Input Ayeuna | 20A |
| Outlet | (24) 5-20R Outlets |
| Pegatna | 1 x 2P 20A Hydraulic Magnetic Breakers |
| Surge Protection | No |
| Ngawaskeun | Ethernet, IP, Serial, USB, Graphical Local Display |
| Suhu Operasi | Nepi ka 149°F (65°C) |
| Approximate Dimensions (Package) | 82 x 10 x 8 inci |
| UPC | 703957370393 |
9. Garansi jeung Rojongan
For warranty information, technical support, or service inquiries, please contact Chatsworth Products customer service or visit their official websitus. Simpen resi pameseran sareng nomer seri produk anjeun nalika ngahubungi dukungan.





